AEMC INSTRUMENTS MiniFlex 3000-14-1-1 Flexible AC Current Sensor
Statement of Compliance
Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments certifies that this instrument
has been calibrated using standards and instruments traceable to international
standards. We guarantee that at the time of shipping your instrument has met
its published specifications. An NIST traceable certificate may be requested
at the time of purchase, or obtained by returning the instrument to our repair
and calibration facility, for a nominal charge. The recommended calibration
interval for this instrument is 12 months and begins on the date of receipt by
the customer. For recalibration, please use our calibration services. Refer to
our repair and calibration section at www.aemc.com.
Serial #:
Catalog #: 2132.60/2132.63
Model #: 3000-14-1-1 / 3000-24-1-1
Please fill in the appropriate date as indicated:
Date Received:
Date Calibration Due: __
Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments
www.aemc.com
INTRODUCTION
WARNING
These safety warnings are provided to ensure the safety of personnel and the
proper operation of the instrument.
- Read this instruction manual completely and follow all the safety information before attempting to use or service this instrument.
- Safety is the responsibility of the operator. The MiniFlex® must be used only by qualified personnel using applicable safety precautions.
- Wear protective clothing and gloves as required.
- Use caution on any circuit: potentially high voltages and currents may be present and may pose a shock hazard.
- Read the safety specifications section prior to using the current probe. Never exceed the maximum voltage ratings given.
- ALWAYS de-energize the circuit before wrapping the MiniFlex® around bare conductors, bus bars, or near live parts. Do not wrap on live conductors.
- ALWAYS connect the electronic module to the display device before wrapping the MiniFlex® around the sample being tested.
- ALWAYS inspect the module, sensor, sensor cable, and output terminals prior to use. Replace any defective parts immediately. Use only factory parts.
- NEVER use the MiniFlex® on electrical conductors rated above 1000V CAT III; and 600V CAT IV.
International Electrical Symbols
Definition of Measurement Categories
CAT II: For measurements performed on circuits directly connected to the
electrical distribution system. Examples are measurements on household
appliances or portable tools.
CAT III: For measurements performed in the building installation at the
distribution level such as on hardwired equipment in fixed installation and
circuit breakers.
CAT IV: For measurements performed at the primary electrical supply
(<1000V) such as on primary overcurrent protection devices, ripple control
units, or meters.
Receiving Your Shipment
Upon receiving your shipment, make sure that the contents are consistent with
the packing list. Notify your distributor of any missing items. If the
equipment appears to be damaged, file a claim immediately with the car- rier
and notify your distributor at once, giving a detailed description of any
damage. Save the damaged packing container to substantiate your claim.
Ordering Information
- MiniFlex® Model 3000-14-1-1 ………………………………………….. Cat. #2132.60
- MiniFlex® Model 3000-24-1-1 ………………………………………….. Cat. #2132.63
Order Accessories and Replacement Parts Directly Online Check our Storefront at www.aemc.com/store for availability
PRODUCT FEATURES
Description
The MiniFlex® is a compact flexible AC current transformer composed of a flexible sensor and an electronic module. The flexible sensor permits measurements on conductors where standard clamp-on probes could not be used. In particular, it can be installed in confined spaces, places where access is difficult, or even wrapped around irregular shapes. The MiniFlex® is lightweight. It does not use magnetic cores like standard transformers. The transformation principle is based on an air core. It pres- ents virtually no load to the system under test, has a low phase shift and excellent frequency response, and cannot be damaged by overloads. The sensor assembly is insulated for 1000V CAT III; and 600V CAT IV. The Mini- Flex® meets EN 61010 and is CE- marked. The MiniFlex® has an mV output proportional to the current measured for direct readings on DMMs, data loggers, oscilloscopes, and power or harmonic meters. TRMS measurements are taken when connected to a TRMS meter. The MiniFlex® is insensitive to DC currents and only the AC component of the measured signal is measured.
Features
- Measures from 0.5Arms to 3000Arms (model dependent)
- Accuracy 1% of Reading ± 0.25A
- TRMS measurements when connected to a TRMS instrument
- No core saturation or damage if overloaded
- Overrange LED indication
- EN 61010; 1000V CAT III; 600V CAT IV; CE Mark
- 9V battery for a typical 140 hours of continuous operation
- 20kHz frequency response
- Low phase shift for power measurements
- Insensitive to DC, measures only AC component on DC + AC signals
- Excellent linearity
- Lightweight
- The sensor is resistant to oils and aliphatic hydrocarbons
Control Features
- Flexible sensor
- Sensor opening device
- Shielded cord
- BNC output connector
- Red OL (overload) indicator
- Green ON/OFF and Low Battery indicator
- Range selection switch
SPECIFICATIONS
REFERENCE CONDITIONS
Quantity of influence| Reference values
Temperature| 73° ± 9° F (23° ± 5° C)
Relative humidity| 20 to 75% RH
Frequency of the signal measured| 40 to 400Hz
Type of signal| sinusoidal
External electric field| < 1V/m
External DC magnetic field (earth field)| < 40A/m
External AC magnetic field| none
Position of the conductor| centered in the measurement coil
Shape of the measurement coil| nearly circular
Input impedance of the display device connected to housing| ≥1MΩ
ELECTRICAL
Measurement Range| 3000A
Current Range| 0.5A to 3000A
Output Signal| 1mV/A
Frequency Range| 10Hz to 20kHz with current derating
Frequency Limitation| see § 3.1 (up to 300Arams there is no frequency
limitation)
Influence Of Conductor Positioning| 1.5% typical, 3% max
Influence Of Conductor Positioning In Sensor Against Handle| 4% typical, 6%
max
External Conductor Influence| 35dB to 40dB on contact
Accuracy| ± 1% +0.25A
Common Mode Rejection| 100dB typical, 80dB min
Max peak factor (1) at I nominal| 1.5
Residual noise at I = 0 (Arms) (2)| 0.25
Max phase shift at 50 Hz| 1.5°
Max offset voltage (mVDC)| 2
Max output voltage (Vpeak)| ± 4.5
Output impedance (kΩ)| 1
Overload| Red LED ON when output around >4.5V
Power Source| 9V Alkaline, Type LF22
Battery Life| >140 hours continuous
Battery Indicator| Green LED blinks when battery needs replacement.
- Peak factor PF = Vpeak/Vrms
- The residual noise affects the measurement uncertainty according to the formula:
If the current measured is zero, the uncertainty is equal to the residual noise.
MECHANICAL
Module Output| 10 ft. (3m) BNC cable
Module Dimensions| 4.0 x 2.5 x 1.1″ (103 x 64 x 28mm)
Weight with Sensor| 7.76 oz. (210g)
Sensor Diameter| 5mm Ø
Sensor Length| 3000-14-1-1: 14″ (356mm)
3000-24-1-1: 24” (610mm)
Max Conductor Size| 3000-14-1-1: 3.93” (100mm)
3000-24-1-1: 7.5” (190mm)
Connection Cable Length (Module to Sensor)| 6ft (2m)
Flammability Rating| Sensor: UL94V0 Housing: UL94V2
Drop Test| Per IEC 68-2-32
Vibration| Per IEC 68-2-6
Mechanical Shock| Per IEC 68-2-27
Weatherproofing| IP50 (Module)
Temperature Resistance| The flexible sensor can withstand a temperature of 194
°F (90 °C) and is resistant to oil and Aliphatic hydrocarbons
ENVIRONMENTAL
Operating Temperature| 14° to 131°F (-10° to +55°C)
Storage Temperature| -40° to 158°F (-40° to +70°C)
Influence of Temperature| Sensor:
14° to 212°F (-10° to 100°C): < 0.5% of Reading per 18°F (10°C)
Module:
14 to 131°F (-10° to 55°C): < 0.5% of Reading per 18°F (10°C)
Relative Humidity| 10 to 90% RH: 0.1% typical, 0.3% max
Altitude| Operating: 0 to 6562 ft. (0 to 2000m), working voltage derating
above
Non-operating: 0 to 39,000 ft. (0 to 12,000m)
SAFETY
Double Insulation| Yes, per IEC 1010-2-32
CE Rated| Yes
Safety Rating| EN/IEC 61010-1 600 V CAT IV, 1000V CAT III,
EN/IEC 61010-2-032:2002
Pollution Level| 2
Immunity and Emission| Industrial environment
Electromagnetic Compatibility| EN 61326-1
**Typical Frequency Response Graphs
**
Amplitude Error
Phase Error
Frequency Limitation Versus Amplitude
OPERATION
Compatibility
The MiniFlex® is compatible with any multimeter, AC voltmeter, or other
voltage-measuring instrument with an input impedance greater than 1MΩ. To
achieve the best overall accuracy, use the MiniFlex® with an AC voltmeter
having an accuracy of 0.75% or better.
Tips for Making Precise Measurements
When using the MiniFlex® with a meter, it is important to select the range
that provides the best resolution. Failure to do this may result in
measurement errors. Make sure the DMM or measuring instrument can accurately
measure mVAC. Certain inexpensive DMMs have poor resolution and accuracy when
measuring low VMC. For best accuracy, center the MiniFlex® around the
conductor to be measured. The overall measurement accuracy is the sum of the
MiniFlex® accuracy and the displaying instrument accuracy.
Making Measurements
- Connect the electronic module to the AC Volt range of a multimeter or measuring instrument. Select the highest range on the MiniFlex®.
- Press the sensor’s yellow opening device to open the flexible coil.
- Wrap the coil around the conductor to be tested. If possible, within range, select the lowest range to obtain the best resolution.
- Do not exceed the specified current range for the output. Do not use the selected range if the overload LED goes on.
- Read the displayed value on the multimeter and divide it by the range selected (i.e. if reading = 2.59V with the 1mV/A output range, the current flowing through the probe is 2590mV = 2590A).
- For best accuracy, carefully center the conductor inside the flexible core, and if possible, avoid being in the proximity of other conductors which may create noise and interference (particularly near the latch).
- True RMS measurements are obtained when the MiniFlex® is connected to a True RMS meter. Note that the DC component is not measured.
MAINTENANCE
Warning
- For maintenance use only specified replacement parts.
- To avoid electrical shock, do not attempt to perform any servicing unless you are qualified to do so.
- To avoid electrical shock and/or damage to the instrument, do not get water or other foreign agents into the case.
- Turn the instrument OFF and disconnect the unit from all the circuits before opening the case.
Battery Replacement
The battery must be replaced when the green indicator flashes or remains off
when the instrument is switched on.
- Disconnect everything connected to the instrument and set the switch to OFF.
- Use a screwdriver to unscrew the two screws on the housing.
- Replace the old battery with a new one (9V alkaline or lithium battery of type 6LF22).
- Close the housing, making sure that it is completely and correctly closed, then screw both screws back in.
Cleaning
- It is important to keep the sensor latch mating surfaces clean to prevent foreign matter from entering the closing.
- The sensor may be gently cleaned with a soft cloth, soap, and water. Dry immediately after cleaning. Avoid water penetration into the electronic module.
- Make sure the sensor, electronic module, and all leads are completely dry before any further use.
Repair and Calibration
To ensure that your instrument meets factory specifications, we recommend that it be scheduled back to our factory Service Center at one-year intervals for recalibration, or as required by other standards or internal procedures.
For instrument repair and calibration
You must contact our Service Center for a Customer Service Authorization
Number (CSA#). This will ensure that when your instrument arrives, it will be
tracked and processed promptly. Please write the CSA# on the outside of the
shipping container. If the instrument is returned for calibration, we need to
know if you want a standard calibration, or a calibration traceable to
N.I.S.T. (Includes calibration certificate plus recorded calibration data).
Ship To: Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments
15 Faraday Drive
Dover, NH 03820 USA
Phone: 800-945-2362 (Ext. 360)
603-749-6434 (Ext. 360)
Fax: 603-742-2346 or
603-749-6309 E-mail:
repair@aemc.com
(Or contact your authorized distributor)
Costs for repair, standard calibration, and calibration traceable to N.I.S.T.
are available.
NOTE: You must obtain a CSA# before returning any instrument.
Technical and Sales Assistance
If you are experiencing any technical problems, or require any assistance with
the proper operation or application of your instrument, please call, mail,
fax, or e-mail our technical support team:
Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments 200 Foxborough Boulevard
Foxborough, MA 02035 USA
Phone: 800-343-1391
508-698-2115
Fax: 508-698-2118
E-mail: techsupport@aemc.com
www.aemc.com
NOTE: Do not ship Instruments to our Foxborough, MA address.
Limited Warranty
The MiniFlex® is warranted to the owner for a period of two years from the date of original purchase against defects in manufacture. This limited warranty is given by AEMC® Instruments, not by the distributor from whom it was pur- chased. This warranty is void if the unit has been tampered with, or abused or if the defect is related to service not performed by AEMC® Instruments. Full warranty coverage and product registration are available on our website at www.aemc.comPlease print the online Warranty Coverage Information for your records.
What AEMC® Instruments will do
If a malfunction occurs within the warranty period, you may return the
instrument to us for repair, provided we have your warranty registration
information on file or proof of purchase. AEMC® Instruments will, at its
option, repair or replace the faulty material.
Warranty Repairs
What you must do to return an Instrument for Warranty Repair: First, request a
Customer Service Authorization Number (CSA#) by phone or by fax from our
Service Department (see address below), then return the instrument along with
the signed CSA Form. Please write the CSA# on the outside of the shipping
container. Return the instrument, postage, or shipment pre-paid to:
Ship To: Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments
15 Faraday Drive Dover, NH 03820 USA Phone:
800-945-2362 (Ext. 360)
603-749-6434 (Ext. 360)
Fax: 603-742-2346 or
603-749-6309 E-mail:
repair@aemc.com
www.aemc.com To protect yourself against in-transit
loss, we recommend you insure your returned material.
NOTE: You must obtain a CSA# before returning any instrument.
Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments
15 Faraday Drive Dover, NH 03820 USA Phone:
603-749-6434 Fax:
603-742-2346
www.aemc.com