AEMC INSTRUMENTS 3910 True RMS Power Meter User Manual
- June 13, 2024
- AEMC INSTRUMENTS
Table of Contents
AEMC INSTRUMENTS 3910 True RMS Power Meter
Product Information
- Product Name: True RMS Power Meter
- Model Number: 3910
- Manufacturer: Not specified
- User Manual: https://manual-hub.com/
- Catalog Number: 2111.27
- Serial Number: [Serial number is located inside the battery compartment]
- Purchase Date: [Purchase date needs to be recorded]
- Distributor: [Distributor name needs to be recorded]
Product Usage Instructions 1. Introduction International Electrical Symbols
- This symbol indicates that the instrument is protected by double or reinforced insulation. Only use specified replacement parts during servicing.
-
- The symbol on the instrument indicates a WARNING, and the user must refer to the user manual for instructions before operating the instrument. The symbol preceding instructions in the manual indicates that not following the instructions may result in bodily injury, installation/sample damage, or product damage.
-
- Risk of electric shock. The voltage at the parts marked with this symbol may be dangerous.
Receiving Your Shipment
- Upon receiving your shipment, check that the contents match the packing list.
- Notify your distributor if any items are missing.
- If the equipment appears to be damaged, file a claim immediately with the carrier and notify your distributor with a detailed description of the damage.
- Keep the damaged packing container as evidence for your claim.
- Do not use an instrument that appears to be damaged.
INTRODUCTION
WARNING
These safety warnings are provided to ensure the safety of personnel and
proper operation of the instrument.
- Read this instruction manual completely before attempting to use or service this instrument and follow all the safety information.
- Use caution on any circuit: Potentially high voltages and currents may be present and may pose a shock hazard.
- The instrument must not be operated beyond its specified operating range.
- Safety is the responsibility of the operator.
- Never open the back of the instrument while connected to any circuit or input.
- Always make connections from the instrument to the circuit under test.
- Always inspect the instrument and accessory leads for serviceability prior to use, and replace defective parts immediately.
- Do not use the meter or any test leads, connectors, probes or clips if they look damaged.
- Never use the Model 3910 on electrical conductors rated above 600V.
- On the current probe input, only use the current probe(s) supplied with the instrument.
- Never use the Model 3910 without its rubber holster.
International Electrical Symbols
- This symbol signifies that the instrument is protected by double or reinforced insulation. Use only specified replacement parts when servicing the instrument.
- This symbol on the instrument indicates a WARNING and that the operator must refer to the user manual for instructions before operating the instrument. In this manual, the symbol preceding instructions indicates that if the instructions are not followed, bodily injury, installation/sample and product damage may result.
- Risk of electric shock. The voltage at the parts marked with this symbol may be dangerous.
Receiving Your Shipment
Upon receiving your shipment, make sure that the contents are consistent with
the packing list. Notify your distributor of any missing items. If the
equipment appears to be damaged, file a claim immediately with the carrier and
notify your distributor at once, giving a detailed description of any damage.
Save the damaged packing container to substantiate your claim. Do not use an
instrument that appears to be damaged.
Ordering Information
TRMS Power Meter Model 3910…………………………………. Cat. #2111.27
Includes 3910 power meter, shock-proof safety holster, 500AAC clamp-on current
probe, two 5 ft (1.5m) leads, two test probes, two probe grips, batteries (not
installed), user manual and hard carrying case.
Accessories and Replacement Parts
Probe Adaptor…………………………………………………………….
Cat. #2118.34 Clamp-on Current Probe Model SR652 (1000AAC)…………. Cat. #2113.46
Order Accessories and Replacement Parts Directly Online Check our Storefront
at www.aemc.com for availability
PRODUCT FEATURES
Description
The True RMS Power Meter Model 3910 is designed for today’s electrical
environments. Operation is simple. There are no programming requirements or
menus, just four push-buttons for direct access. The Model 3910 is auto-
ranging and ensures the best range for measurements.
Troubleshooting and measuring power is done simply by connecting two voltage
leads and clamping on the current probe. The Model 3910 is easier to operate
than most DMMs and may even replace your multimeter for individual voltage or
current measurements.
Small and compact in its protective holster, the Model 3910 provides seven
essential power measurement values. Four measurements are displayed at a time
on its extra large multi-display LCD.
The Model 3910 performs current and voltage measurements in True RMS, and
provides immediate readings of power factor (PF), active power (kW), reactive
power (kVar), apparent power (kVA) and frequency (Hz). The Model 3910 displays
Vrms, Arms, kW and PF on the first screen; pressing and holding the PAGE
button gives access to kVar, kVA and Hz on a second screen.
The Peak function allows selection of a specific parameter (A, V or W) for
peak measurement, and also displays the associated values at the particular
peak (for example, the Model 3910 displays the actual V, kW, PF, kVar, kVA and
Hz values when Apeak is selected).
The unique memory function permits not only storing the measurements at any
time, but also comparing subsequent readings by displaying the difference
between the stored values and the new readings. This is helpful in analyzing
and measuring the impact of loads being turned on and off.
A selector switch on the front panel selects power measurements for single-
phase or balanced three-phase, three-wire systems.
Control Features
-
SEL Button
Selects the parameter (A, W, V) whose peak is to be measured. -
MEM Button
Accesses two functions:- Memory
- Measurements of differences in voltage, current and active power between stored values and subsequent readings.
-
ON/OFF Switch
Turns the instrument ON or OFF. The Model 3910 takes a few seconds to power up when turned “ON”. -
Clamp Input
FRB socket for connecting the clamp-on current probe. Use only specified current probes, which have a voltage output (1mVAC/AAC). -
Display
LCD (40x50mm), displays the seven measurements on two pages.
NOTE: A beep sounds when the PAGE, PEAK, SEL or MEM button is pressed. -
PEAK Button
Selects “PEAK” measurement mode. -
PAGE Button
Displays Vrms, Arms, W, PF (or Cos Φ) on page 1 automatically;
pressing PAGE gives access to Var, VA and Hz on page 2. -
1Ø / 3Ø
Selects the type of network to be tested.- 1Ø: single-phase
- 3Ø: balanced three-phase, three-wire
-
Voltage Inputs
Two safety input terminals (4mm) for lead connection. Voltage measurement may be made up to 600VAC/DC.
Display Features
When the Model 3910 is switched ON, page 1 is displayed automatically.
- RMS voltage (V)
- RMS current (A)
- Active power (W)
- Power factor (pF) (or Cos Φ)
Hold down the PAGE button to display page 2:
- Reactive power (Var)
- Apparent power (VA)
- Frequency (Hz)
To return to page 1, release the PAGE button.;
Button Functions
PEAK Button
When this button is activated, PEAK values of a measurement can be displayed.
To activate the PEAK mode, press the PEAK button once. The Model 3910 changes
initially to peak current measurements and “PEAK A” is displayed.
Press the SEL button to choose the desired parameter (A, W, V). The SEL button
can only be used after the PEAK button has been activated.
NOTE: The peak measurement is:
- the maximum value for the current (A)
- the maximum value for the active power (W)
- the minimum value for the voltage (V)
The Model 3910 stores all the measurements present when peak is selected. The
first four measurements (V, A, W, PF) are displayed on page 1 and the
following three measurements (Var, VA, Hz) on page 2 (press the PAGE button).
For example, you can find the voltage, the power, etc., at the moment when
current is at a peak.
In PEAK mode, the typical acquisition time is 400ms. Each new peak is taken
into account as long as the PEAK button is activated. To exit PEAK mode, press
the PEAK button.
Memory Button
This button has two functions:
-
First Function – Memory
To store page 1 of the display, press the MEM button once. “MEM” will show on the display. Voltage, current, active power and power factor are stored. -
Second Function – Differential
Measurements Once the values are memorized (MEM is displayed), press the PAGE button. Page 2 will display the differences between the values in memory and the values that the instrument continues to measure. Measurements of differences in voltage, current and active power.
NOTE: The power factor is no longer displayed.
If the difference between measurements is a negative value, a minus “-” sign is displayed.
To exit memory mode, press the MEM button again.
SPECIFICATIONS
Reference Conditions: Temperature 23°C ± 5K, 45 to 75% RH; battery voltage 6V; conductor centered in the probe jaws; DC magnetic field; earth’s field; no external AC magnetic field; no external electrical field; sine wave 45 to 65Hz. In Peak, basic accuracy is based on 1 ms samples and on a signal from 10 to 500Hz.
Electrical Specifications
CURRENT (TRMS)
Input Range: 1 to 500ARMS
Typical Accuracy (and Phase Shift) with 500A Current Probe MD313:
- 25A: 5% of Reading (4°)
- 100A: 2% of Reading (2°)
- 500A: 2% of Reading (1.5°)
Typical Accuracy (and Phase Shift) with 1000A Current Probe SD652:
- 50A: ± 0.9% of Reading (1.5°)
- 200A: ± 0.5% of Reading (0.5°)
- 1000A: ± 0.5% of Reading (0.5°)
Resolution:
- 1 to 9.99A: 10mA
- 10 to 99.9A: 100mA
- 100 to 500A: 1A
- VOLTAGE (TRMS)
- Input Range: 0 to 600VRMS
Accuracy :
- 1 to 99.9V: 0.5% ± 0.6V
- 100 to 600V: 0.3% ± 2V
Resolution:
- 0 to 99.9V: 0.1V, 100 to 600V: 1V
FREQUENCY
Input Range (from voltage input):
- 30 to 100Hz
- 101 to 999Hz
Accuracy:
- 30 to 100Hz: 0.03% of Reading ± 0.1Hz
- 101 to 999Hz: 0.5% of Reading ± 1Hz
POWER FACTOR
- Range: -0.00 (Lag) to +0.00 (Lead)
- Accuracy: Sum of the V and A accuracy plus the probe phase shift
ACTIVE POWER
- Range: 30W to 300kW (600kW with SR652 probe)
- Accuracy: Sum of the V and A accuracy
REACTIVE POWER
- Range: 0 to 300kVar (600kVar with SR652 probe)
- Accuracy: Sum of V and A accuracy @ Sin Φ = 1 plus the probe phase shift
APPARENT POWER
- Range: 0 to 300kVA (600kVA with SR652 probe)
- Accuracy: Sum of the V and A accuracy
Mechanical Specifications
- Display: 1.58 x 1.97″ (40 x 50mm) multi-display LCD
- Power Supply: Four 1.5V AA alkaline batteries
- Low Battery Indicator: “BAT” on display
- Battery Life: 50 hours approx, continuous use
Dimensions:
- 3.2 x 6.9 x 1.3″ (80 x 175 x 32mm) – without holster
- 3.5 x 7.7 x 2.1″ (90 x 195 x 54mm) – with holster
Weight (with battery):
- 15 oz (400g) – without holster
- 17.6 oz (500g) – with holster
Supplied 500A current probe:
- Accommodates two 500 MCM or one 750 MCM
Safety Specifications
- Protection Level: EN 61010, Class II
- Protection Index: IP40 per IED 529
- Max. Voltage Overload: 825Vrms, 1170Vpeak
OPERATION
Single-Phase Networks
WARNING: Maximum voltage rating 600V
- Set the selector switch to the 1Ø position.
- Connect the Model 3910 as shown in the diagram, with phase connected to the right terminal and the probe on phase.
NOTE: Only clamp the current probe around one conductor.
The arrow on the current probe should always point towards the load for
correct polarity indication during power measurements.
Balanced Three-Phase Networks
WARNING : Maximum voltage rating 600V
- Set the selector switch to the 3Ø position.
- Connect the Model 3910 as shown in the diagram. Note that the current probe is clamped onto the conductor that is not connected to a voltage input.
The Model 3910 will automatically display the system power on balanced three- phase, three-wire circuits (two wattmeter method).
Three-Phase, Four-Wire Networks
WARNING: Maximum voltage rating 600V
- Set the selector switch to the 1Ø position.
- Connect the Model 3910 as shown for single-phase (phase-to-neutral) and measure on each phase.
- Add all three readings for system total.
Total W = W1 + W2 + W3
Using as a Voltmeter
WARNING: Maximum voltage rating 600V
- Plug voltage leads into the safety input terminals.
- The selector switch may be set at either 1Ø or 3Ø position.
- Connect the Model 3910 as shown in the diagram below.
Note: The Model 3910 may also measure DC volts. DC will be displayed on the LCD.
Using as an Ammeter
WARNING: Maximum voltage rating 600V
- Connect the current probe to the FRB socket.
- The selector switch may be set at either 1Ø or 3Ø position.
- Connect the Model 3910 as shown in the diagram.
- Only use the supplied current probes (MD313 or optional SR652)
Measurements: Review of Formulas Used
MAINTENANCE
Warning
Use only factory specified replacement parts. AEMC® will not be held
responsible for any accident, incident, or malfunction following a repair done
other than by its service center or by an approved repair center.
- Do not allow water or other foreign substances into the instrument.
- Disconnect the unit from all circuits and test cables before opening the case.
Battery Replacement
The TRMS Power Meter Model 3910 is powered by four 1.5V “AA” alkaline
batteries. When the battery indicator shows that the batteries are low (“BAT”
appears on the LCD), the batteries should be replaced.
- Unplug the leads and the clamp from the instrument.
- Remove the shock-proof case.
- Lift the fold-away stand and pry off the battery compartment cover with a small screwdriver.
- Insert four new 1.5V “AA” alkaline batteries, being sure to observe the
- polarity shown in the battery housing.
- Replace the cover of the battery compartment and the shock-proof case before use.
Cleaning
Disconnect the instrument from any power source. Use a soft cloth slightly
moistened with soapy water. Rinse with a damp cloth and quickly dry with a dry
cloth or forced dry air. Do not use any abrasives or solvents.
Repair and Calibration
To ensure that your instrument meets factory specifications, we recommend
Bthat it be scheduled back to our factory Service Center at one-year intervals
for recalibration, or as required by other standards or internal procedures.
For instrument repair and calibration:
You must contact our Service Center for a Customer Service Authorization
Number (CSA#). This will ensure that when your instrument arrives, it will be
tracked and processed promptly. Please write the CSA# on the outside of the
shipping container. If the instrument is returned for calibration, we need to
know if you want a standard calibration, or a calibration traceable to
N.I.S.T. (Includes calibration certificate plus recorded calibration data).
Ship To: Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments
15 Faraday Drive Dover, NH 03820 USA
Phone : 800-945-2362 (Ext. 360)
603-749-6434 (Ext. 360)
Fax: 603-742-2346 or
603-749-6309
E-mail: repair@aemc.com
(Or contact your authorized distributor)
Costs for repair, standard calibration, and calibration traceable to N.I.S.T.
are available.
NOTE: You must obtain a CSA# before returning any instrument.
Technical and Sales Assistance
If you are experiencing any technical problems, or require any assistance with
the proper operation or application of your instrument, please call, fax or
e-mail our technical support team: Chauvin Arnoux® , Inc. d.b.a. AEMC®
Instruments
Phone: 800-945-2362 (Ext. 351)
603-749-6434 (Ext. 351)
Fax: 603-742-2346
E-mail: techsupport@aemc.com
Limited Warranty
The Model 3910 is warranted to the owner for a period of 2 years from the date
of original purchase against defects in manufacture. This limited warranty is
given by AMC® Instruments, not by the distributor from whom it was pur-chased.
This warranty is void if the unit has been tampered with, abused or if the
defect is related to service not performed by AEMC® Instruments. For full and
detailed warranty coverage, please read the Warranty Coverage Information,
which is attached to the Warranty Registration Card (if enclosed or is
available at www.aemc.com. Please keep the Warranty
Coverage Information with your records.
What AEMC® Instruments will do:
If a malfunction occurs within the warranty period, you may return the
instrument to us for repair, provided we have your warranty registration
information on file or a proof of purchase. AMC® Instruments will, at its
option, repair or replace the faulty material.
REGISTER ONLINE AT: www.aemc.com
Warranty Repairs
What you must do to return an Instrument for Warranty Repair:First, request a
Customer Service Authorization Number (CA#) by phone or by fax from our
Service Department (see address below), then return the instrument along with
the signed CSA Form. Please write the CSA# on the outside of the shipping
container. Return the instrument, postage or shipment pre-paid to:
Ship To : Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments
15 Faraday Drive • Dover, NH 03820 USA
Phone: 800-945-2362 (Ext. 360)
603-749-6434 (Ext. 360)
Fax: 603-742-2346 or
603-749-6309
E-mail : repair@aemc.com.
Caution: To protect yourself against in-transit loss, we recommend you
insure your returned material.
NOTE : You must obtain a CSA# before returning any instrument.
Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments 15 Faraday Drive
Dover, NH 03820 USA
Phone: 603-749-6434
Fax: 603-742-2346
www.aemc.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>