GOSSEN METRAWATT U282A Single Phase Digital Energy Meters Direct connection 80 A Instruction Manual
- June 12, 2024
- GOSSEN METRAWATT
Table of Contents
- Operating instructions
- Display
- Commands
- Symbols
- Dimension
- Display Back light
- Diagnostic Message
- Service and Maintenance
- Wiring diagram
- Applications
- Safety Instructions
- Symbols on the Instrument
- Standards, Regulations and Directives
- Transport & Storage
- Maintenance
- Recalibration
- Repairs & Manufacturer’s Guarantee
- Disposal & Environmental Protection
- Technical Data
- Support and Contact
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
3-447-130-15
METRALINE I ENERGY
Single-phase Digital Energy meters
Direct connection 80 A
Operating instructions
- This family of metering equipments provides the essential measurement capabilities required to monitor a single phase electrical installation.
- There are 3 models, mainly distinguished by the type of remote communication: ( *) certification parameters: 0.25-5 (80) A, Class B, 230 VAC 50 Hz,-25 °C … +55 °C, 4 Quadrants, 2 Tariffs.
- Active Energy Class B (according to EN-50470) and Reactive Energy Class 2 (according to IEC 62053-23)
- Direct connected (up to 80 A)
- Backlightet LCD display and 3 push-button keys (to read Energies, V, I, PF, F, P, Q and to configure some parameters)
- Display with 8 digits.
- Self supplied (by the input voltage itself)
- 2 DIN modules width (36 mm)
- 2 Tariffs controlled by a 230 VAC digital input
- epending on the models:
– 2 S0 standard low voltage pulse outputs, or
– communication via Modbus RTU or
– communication via M-Bus (1 unit load)
RISK OF ELECTRIC SHOCK, BURNS OR EXPLOSION
This device must be installed and maintained ONLY by qualified and duly
authorized personnel.
During its installation, be sure there is no voltage applied.
Ordering information
Model | Communication |
---|---|
U282A | S0 Pulse outputs MID certified |
U282B | Built in RS-485 Modbus RTU MID certified |
U282C | Built in M-Bus (1 unit Load) MID certified |
(*) For swiss market only active energy on display
Display
- Energy value
- kWh / kvarh display
- Running tarif, called tarif
- Energy value “Partial”
- Precision control LED
Commands
- Scroll Key: This key is used to scroll pages and to modify parameters value. Its pushing is accepted only if it is shorter than 1.5 second.
- OK key: This key is used alone to enable a new menu function or to confirm a parameter value during its modification. Its pushing is accepted only if shorter than 1.5 seconds
- ESC key: This key is used alone to exit from a sub-menu, to cancel a parameter modification or to go back to the main page. In these cases, its pushing is accepted only <1.5 seconds
- A long pushing (>1.5 seconds) of the “ESC key” is used in the Partial Energy Registers Pages to reset their values.
- Push these 2 keys together, for at least 1.5 seconds, to enter into the Configuration Menu
Symbols
- Measuring elements
- Protected by double insulation
MID calibrated
A) Device code and certification data indications
B) Safety-sealing between upper and lower housing part
Dimension
Sealable terminal covers
Cable stripping length and terminal screw torque
80 A direct connection main terminals Screw driver PZ2|
---|---
Tariff and Pulse outputs terminals Screw driver blade 0.8×3.5 mm|
Communication terminals Screw driver blade 0.8×3.5 mm|
Device Switch-on and Main Page
Main Page:
This page appears not only at device switch on, but also in case for 30
seconds no key is pushed. The value is the sum of 2 registers:
Imported Act. Energy Tariff T1 + Imported Act. Energy Tariff T2. (or,
alternatively, the sum of the Exported ones).
Display Back light
- If no button is pushed for 40 seconds, the display goes back to the Main Page and the backlight is switched off.
- The first button pushing does not change the page but is used to switch the backlight on.
Main Menu
Tariff 1-2 Energy Registers List
Instantaneous Measurements List
Partial Energy Registers Reset Procedure
Access to the Configuration Menu
Parameters Available in U282B
Parameters Available in U282C
Parameters Available in U282A
Multivalue Parameters Modification
In this example the Parity value is changed from None to Even. In any moment,
push the “ ” key to stop the modification
Numeric Parameters Modification
In this example the Address value is modified from 167 to 18.
Diagnostic Message
Error Condition
If the display shows these messages, the meters has got a malfunction and must
be replaced.
Service and Maintenance
It should not be necessary to recalibrate device during its lifetime as it is
an electronic meter with no moving parts with electronics and voltage and
current sensors that do not naturally degrade or change with time under
specified environmental conditions. If a degradation in the performance is
observed the device has probably been partly damaged and should be sent for
repair or exchanged.
If the meter is dirty and needs to be cleaned, use lightly moistened tissue
with a water based mild detergent. Make sure no liquid goes into the meter as
this could damage the meter.
Wiring diagram
Model S0
Model Modbus
Model M-Bus
Applications
Please read this important information!
Intended Use / Use for Intended Purpose
The instrument is a digital multifunctional energy meter certified in
accordance with MID. Integrated 4-quadrant measurement permits measurement of
energy import and export.
Thanks to MID certification, acquired data (display) can also be used for the
purpose of billing energy costs to third parties.
Via integrated communication interfaces, the values are also forwarded to
superordinate management systems. Protection against tampering is provided
through adequate measures (tamper-proof cover).
Safety of the operator, as well as that of the instrument, is only assured
when it’s used for its intended purpose
Use for Other than Intended Purpose
Using the instrument for any purposes other than those described in the
product documentation is contrary to use for intended purpose.
Liability and Guarantee
Gossen Metrawatt GmbH assumes no liability for property damage, personal
injury or consequential damage resulting from improper or incorrect use of the
product, in particular due to failure to observe the product documentation.
Furthermore, all guarantee claims are rendered null and void in such cases.
Nor does Gossen Metrawatt GmbH accept any liability fordata loss.
Scope of Delivery
1 instrument ( (U282A) – (U282B) – (U282C) )
1 operating instructions
Safety Instructions
Read and follow these instructions carefully and completely in order to ensure
safe and proper use. Keep for future reference.
DANGER
Electric shock due to live components!
Life endangering due to electric arcs!
Touching voltage conducting components is life endangering!
- The installation and any work performed on the instrument may only be carried out by a qualified electrician.
- Observe and comply with all safety regulations which are applicable for your work environment.
- Wear suitable and appropriate personal protective equipment (PPE) whenever working with the instrument.
- During installation, the installation environment must be voltage-free. For that, observe the five safety rules in accordance with DIN VDE 0105-100.
ATTENTION
Faulty installation & incorrect operation
Faulty installation/incorrect operation can damage your instrument/system.
Risk of malfunctions and disruptions
- Comply with the specified technical data and conditions
- Do not install the instrument in potentially explosive atmospheres.
- Do not install the instrument in locations where it may be exposed to direct sunlight.
- Install and operate the instrument only if it and all connection cables and leads are in good working order and damage-free. Inspect the instrument at regular intervals.
- If the instrument doesn’t function flawlessly, permanently remove it from operation and secure it against inadvertent use.
Symbols on the Instrument
**** European conformity marking
Double insulation (protection category II)
CE and metrology mark with indication of year (M22) and registration number of
the notified body for module D, country-specific calibration validity period
Standards, Regulations and Directives
- DIN 43880
- EN 50470-1
- EN 50470-3
- EN 60715
- EN 62053-31
- IEC 62053-23
Transport & Storage
Transport and store the instrument only within the limits of permissible
ambient conditions.
Also use suitable packaging in order to ensure adequate protection against
environmental influences and mechanical stress.
Maintenance
The instrument is maintenance-free. Keep outside surfaces clean.
Clean the instrument only with a dry cloth.
Recalibration
Comply with national recalibration regulations and laws. The calibration
period in Germany is 8 years.
A broken manufacturer’s seal means equals invalidated calibration. The
instrument must not be used for billing purposes.
Repairs & Manufacturer’s Guarantee
If your instrument requires repair, please contact our service department; see
Support & Contact.
Unauthorized modification of the instrument is prohibited. This also includes
opening the meter.
If it can be ascertained that the instrument has been opened by unauthorized
personnel, no guarantee claims can be honored by the manufacturer with regard
to personal safety, measuring accuracy, compliance with applicable safety
measures or any consequential damages. If the manufacturer’s seal is damaged
or removed, all guarantee claims are rendered null and void.
The instruments are guaranteed for a period of 2 years after shipment.
The manufacturer’s guarantee covers materials and workmanship.
Damage resulting from use for any other than the intended purpose or operating
errors, as well as any and all con sequential damage, are excluded.
Disposal & Environmental Protection
- The following comments refer specifically to the legal situation in the Federal Republic of Germany. Owners or end users who are subject to other national requirements are required to comply with the respectively applicable national requirements and to implement them correctly on site
- The symbol on the left depicting a crossed-out garbage can on wheels refers to the legal obligation of the owner or end user (German electrical and electronic equipment act ElektroG and German battery act BattG) not to dispose of used electrical quipment and batteries with unsorted municipal waste (“household trash”).
- Old devices, electrical or electronic accessories and waste batteries (including rechargeable batteries) used in Germany can be returned free of charge to Gossen Metrawatt GmbH or the service provider responsible for their disposal. Further information can be found on our website.
Technical Data
Data in compliance with EN 50470-1, EN 50470-3, EN 62053-23 and EN 62053-31| |
Direct Connection 80 A
Pulse output SO| Direct Connection 80 A built-in
Comm. Modbus/M-Bus
---|---|---|---
General characteristics
•Housing DIN 43880| DIN| 2 Modules| 2 Modules
•Mounting EN 60715| 35 mm| DIN rail| DIN rail
•Depth| mm| 70| 70
•Weight| g| 175| 175
Operating features
• Connection | to single-phase network | n° wires | 22 | 22 |
---|---|---|---|---|
• Storage of energy values and config. | Internal flash memory | – | yes | yes |
• Tariff | for active and reactive energy | n° 2 | T1 / T2 | T1 / T2 |
Approval (according to EN 50470-1, EN 50470-3)
• Reference Voltage Un| VAC| 230| 230|
---|---|---|---|---
• Reference Current (Iref)| A| 5| 5|
• Minimum Current (Imin)| A| 0.25| 0.25|
• Maximum Current (Imax)| A| 80| 80|
• Starting Current (Ist)| A| 0.015| 0.015|
• Reference Frequency (fn)| Hz| 50| 50|
• Number of phases (number of wires)| –| 1 (2)| 1 (2)|
• Certified Measures| kWh| ⇒ kWh T1, ⇒kWh T1
⇒kWh T2, ⇒kWh T2| ⇒kWh T1, ⇒ kWh T1
⇒kWh T2, ⇒ kWh T2
•Accuracy| Active Energies (accor. to EN 50470-3) and Active Powers| classe|
B| B
Reactive Energies (accor. to EN 62053-23) and Reactive Power| classe| 2| 2
Supply Voltage and Power Consumption
• Operating Supply Voltage range | V | 92 … 276 | 92 … 276 |
---|---|---|---|
• Maximum Power Dissipation (Voltage circuit) | VA (W) | ⩽2 (1) | ⩽2 (1) |
• Maximum VA burden (Current circuit) @ Imax | VA | ⩽1 | ⩽1 |
• Voltage Input Waveform | – | AC | AC |
• Voltage impedance | MΩ | 11 | 11 |
• Current impedance | mΩ | ⩽20 | ⩽20 |
Overload capability
• Voltage | continuous | VAC | 276 | 276 |
---|---|---|---|---|
Temporary (1 s) | VAC | 300 | 300 | |
• Current | continuous | A | 80 | 80 |
Temporary (10 ms) | A | 2400 | 2400 |
Measuring Features
• Voltage range | VAC | 92 … 276 | 92 … 276 |
---|---|---|---|
• Current range | A | 0.015 … 80 | 0.015 … 80 |
• Frequency range | Hz | 45 … 65 | 45 … 65 |
• Measured Quantities | – | V, A, kWh, kVARh, PF, Hz, kW, kVAR | V, A, kWh, |
kVARh, PF, Hz, kW, kVAR
Display features
• Display type | LCD backlightet | – | 6.2 +3 | 6.2 +3 |
---|---|---|---|---|
Energy digits dimension | mm | 6 x 3 | 6 x 3 | |
• Active Energy | 6 digits + 2 decimal digits | min. … max. kWh | 0.01 … | |
999999.99 | 0.01 … 999999.99 | |||
• Reactive Energy | 6 digits + 2 decimal digits | min. … max. kvarh | 0.01 … | |
999999.99 | 0.01 … 999999.99 | |||
• Voltage | 3 digits + 2 decimal digits | V | 92.00 … 276.00 | 92.00 … 276.00 |
• Current | 2 digits + 2 decimal digits | A | 0.00 … 80.00 | 0.00 … 80.00 |
• Power factor | 1 digits + 3 dec. digits + capac./induc. indic. | – | 0.000 … | |
1.000 | 0.000 … 1.000 | |||
• Frequency | 2 digits + 2 decimal digits | Hz | 45.00 … 65.00 | 45.00 … 65.00 |
• Active Power | 2 digits + 2 ecimal digits with sign | kW | 0.00 … 17.40 | 0.00 |
… 17.40
• Reactive Power| 2 digits + 2 ecimal digits with sign| kVAR| 0.00 … 17.40|
0.00 … 17.40
• Running Tariff| 1 digit| –| T1 / T2| T1 / T2
• Display refresh period| s| 11| 1
Optical metrological LED
• Front mounted red LED (meter constant)| proportional to active imp/exp
Energy| p/kWh| 1000| 1000
---|---|---|---|---
Safety
• Protective class | classe | II | II |
---|---|---|---|
• AC voltage test (EN 50470-3, 7.2) | kV | 44 | 44 |
• Degree of pollution | – | 22 | 22 |
• Operational voltage | V | 300 | 300 |
• Impulse voltage test | 1.2/50 μs-kV | 66 | 66 |
• Housing material flame resistance UL94 | classe | V0 | V0 |
• Safety-sealing between upper and lower housing part – | – | yes | yes |
Pulse Outputs (S0 signals, acc. to IEC 62053-31)
• Pulse Ouput 1 or 2| selectable| –| kWh ⇒, kWh ⇒
kvarh ⇒, kvarh ⇒
kWh (T1)⇒, kWh (T2) ⇒| –
---|---|---|---|---
• Pulse Rate| adjustable| p/kWh – p/kvarh| 1 … 1000| –
• Pulse ON duration| adjustable| msec| 30 … 100| –
• Operating voltage| Min. – Max.| VAC (DC)| 5 … 28 (5 … 39)| –
• Pulse ON maximum current| in the range 3 … 28 VAC (5 … 39 VDC)| mA| 90| –
• Pulse OFF leakage current| in the range 3 … 28 VAC (5 … 39 VDC)| μA| 1| –
• Isolation class| –| SELV| –
Tariff
• Tariff 1 | – | open contact | open contact |
---|---|---|---|
• Tariff 2 | VAC | 230 ±20% | 230 ±20% |
• Input impedance | kΩ | 224 | 224 |
Embedded communication
• Modbus RTU | RS-485 – 3 wires | – | – | baud rate min.-max. 1200-38400 bps |
---|---|---|---|---|
• M-Bus | 2 wires | – | – | baud rate min.-max. 300-9600 bps |
• Isolation class | – | – | SALV |
IR Connectable Communication Modules
• For communication moduls connection| (LAN-TCP/IP / M-Bus / ModbusRTU / KNX)|
–| yes| yes
---|---|---|---|---
Connection terminals
• Screwdriver for mains terminals| head with Z +/-| POZIDRIV|
PZ2| PZ2
---|---|---|---|---
•Screwdriver for tariff and communic. terminals| slotted head| mm| 0.8 x 3.5|
0.8 x 3.5
•Terminal capacity main current paths| solid wire min. (max)| mm2| 1.65 (33)|
1.65 (33)
| stranded wire with sleeve min. (max)| mm2| 1.65 (33)| 1.65 (33)
•Terminal capacity for tariff and communication| solid wire min. (max)| mm2| 1
(4)| 1 (4)
| stranded wire with sleeve min. (max)| mm2| 1 (2.5)| 1 (2.5)
Environmental conditions (storage)
• Temperature range | °C | -25 … +70 | -25 … +70 |
---|
Environmental conditions (operating)
• Temperature range | °C | -25 … +55 | -25 … +55 | |
---|---|---|---|---|
•Mechanical environment | – | M1 | M1 | |
•Electromagnetic environment | – | E2 | E2 | |
•Installation | Indoor | – | yes | yes |
•Altitude (max) | m | -__2000 | 0 | |
•Humidity | yearly average, not condensing | – | -__75% | -_75% |
on 30 days per year (not condensing) | – | -_95% | -_95% | |
•IP rating | – | 1P51(*)/IP40 | 1P51(*)/IP40 |
(*) The metering equipment must be installed inside a cabinet with IP rating IP51 or better.
Support and Contact
Please contact us at
+49 911 8602-0
Monday – Thursday: 08:00 Uhr – 16:00 Uhr
Friday: 08:00 Uhr – 14:00 Uhr
support.industrie@gossenmetrawatt.com
Please contact GMC-I Service GmbH for repairs, replacement parts and
calibration:
+49 911 817718-0
service@gossenmetrawatt.com
www.gmci-service.com
CE Declaration
The device fulfills all requirements of applicable EU directives and national
regulations.We confirm this with the CE mark.
The CE declaration is available on our website: https://www.gmc-
instruments.de/en/services/download-center/download-center/
Gossen Metrawatt GmbH
Südwestpark 15
90449 Nürnberg
Germany
Phone +49 911 8602-0
Fax +49 911 8602-669
E-mail info@gossenmetrawatt.com
www.gossenmetrawatt.com
© Gossen Metrawatt GmbH
- Prepared in Germany
- Subject to change, errors excepted
- PDF version available on the Internet.
All trademarks, registered trademarks, logos, product names and company names are the property of their respective owners.