RAB SWISH34 LED Center Basket Troffer Instruction Manual
- June 12, 2024
- RAB
Table of Contents
- OTHER MODEL
- IMPORTANT!
- RECESSED CEILING MOUNTING
- SAFETY INSTRUCTIONS
- 0-10V DIMMABLE WIRING
- CLEANING
- TROUBLESHOOTING
- BATTERY BACKUP MODELS
- Specifications
- Setup & Installation
- Configuration
- Sensor Coverage
- Customer Support
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
RAB SWISH34 LED Center Basket Troffer
OTHER MODEL
SWISH34 2×2
SWISH34 2×4
RAB Lighting is committed to creating high-quality, affordable, well-designed
and energy-efficient LED lighting and controls that make it easy for
electricians to install and end users to save energy. We’d love to hear your
comments.
Please call the Marketing Department at 888-RAB-1000 or email:
marketing@rablighting.com
IMPORTANT!
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR
FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and
all applicable local codes. Proper grounding is required for safety. THIS
PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE
BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND
THE HAZARDS INVOLVED.
WARNING: Make certain power is OFF before installing or maintaining
fixture. No user serviceable parts inside.
RECESSED CEILING MOUNTING
The fixture is suitable only for indoor recessed ceiling application.
Above ceiling access required.
To mount in an insulated or non-insulated ceiling – 9/16” or 15/16” exposed
flat tee grid ceiling follow the steps below.
-
Firmly bend the pre-installed Grid Clips (up and out as shown in Fig. 1).
-
Rotate and slide the Fixture as required to fit through the Tee-Grid Bar and place it as indicated by the directional arrow as shown in Fig. 2. Secure the Fixture to the Tee-Grid Bar.
-
Support wires are required by installation Codes. Support the Fixture to the building structure by Support Wires (supplied by others) through the Grid Clip Hole as shown in Fig. 2.
-
Make sure that the orientation of the Splice Box and Access Plate faces an accessible tile to make electrical splices.
-
Loosen Access Plate Screw and remove the Access Plate. Knock out appropriate Conduit Knockouts on the Access Plate to route input conduit. Use appropriate conduit connectors as required by code (Fig. 3).
-
Connect wires as shown in wiring diagram (Fig. 4). Push all wires back into the Splice Box. Use appropriate UL approved wire connectors as required by code to complete wiring. Be careful not to pinch wires. WARNING: To prevent wiring damage or abrasion, do not expose wiring to edges of sheet\ metal or other sharp objects.
-
Replace Access Plate and tighten Access Plate Screw.
SAFETY INSTRUCTIONS
WARNING : Risk of fire or electric shock. Suitable for Damp locations.
WARNING : Suitable for 9/16” or 15/16” Flat Tee Grid in both Insulated
Ceilings and Non-Insulated Ceilings. Access above ceiling required.
WARNING : Do not handle energized fixture when hands are wet, when
standing on wet or damp surfaces, or in water.
WARNING : Vapor barrier must be suitable for 90° C.
WARNING : Fixture to be independently supported to building structure.
0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V thru 277V, 50 or 60 Hz. For
0-10V Dimming, follow the wiring directions as shown in below (Fig. 4).
Do not use any supply voltage other than 120V-277V.
- Insert the LINE supply lead into the black push connector.
- Insert the COMMON supply lead into the white push connector.
- Insert the GROUND supply lead into the green push connector.
- Insert Dim+ supply lead into the purple push connector.
- Insert Dim- supply lead into the pink (or gray) push connect
CLEANING
CAUTION: Be sure fixture temperature is cool enough to touch. Do not clean or maintain while fixture is energized.
- Clean polystyrene lens & fixture with non-abrasive cleaning solution.
- Do not open fixture to clean the LEDs. Do not touch the LEDs.
TROUBLESHOOTING
- Check the line voltage at fixture. Refer to wiring directions.
- Is the fixture grounded properly?
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.
BATTERY BACKUP MODELS
WIRING
CAUTION: FOR BATTERY BACKUP FIXTURE. Voltage can be present in BATTERY.
To prevent high voltage from being present on output leads, Inverter Connector
must be open. Do not join BATTERY connector until installation is complete and
AC power is supplied to the emergency driver. (Fig. 5)
NOTE: Make sure that the necessary branch circuit wiring is available. An
UNSWITCHED AC source of power is required.
The emergency driver must be fed from the same branch circuit as the LED
driver.
CAUTION: Do not use any supply voltage other than 120-277V 50/60 HZ.
- Connect UNSWITCHED HOT fixture lead to HOT AC supply line.
- If using an UNSWITCHED circuit, connect UNSWITCHED and SWITCHED lines together.
- If using a SWITCHED circuit, connect SWITCHED HOT AC fixture lead to the external.
- Connect the pink (or gray) fixture lead to the (V-) DIM lead.
- For 0-10V Dimming, connect DIM (+) and DIM (-) to the supply ground. Do not connect GROUND to the output leads.
- All unused leads must be capped and insulated.
- After installation is complete, supply AC power to the fixture and connect the BATTERY.
- When power is on, the fixture should be on and the Charging Indicator Light should illuminate to indicate the battery is charging.
- Once the BATTERY has charged for at least one hour, a short duration test may be performed by pressing the test button.
- After the battery has charged for 24 hours, a long duration test can be performed by shutting power to the fixture.
OPERATION
- When AC power is applied, the charging indicator light is illuminated, indicating that the BATTERY is being charged.
- When power fails, the standby power automatically switches to emergency power (internal battery), operating at reduced illumination. The emergency driver supplies 8W of power for SWISH 2X2 and 16W of power for SWISH 2X4 in standby power for a minimum of 90 minutes.
- When AC power is restored, the emergency driver automatically returns to charging mode.
MAINTENANCE
Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to ensure that it is working. The following schedule is recommended:
- Visually inspect the charging indicator light monthly. It should be illuminated.
- Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.
- Conduct a 90-minute discharge test once a year. Fixture will operate at reduced illumination for a minimum of 90 minutes.
TROUBLESHOOTING
- Is the fixture grounded properly?
- If the charging indicator light does not illuminate after pressing the test button, check if battery is connected properly
INSIDE FIXTURE
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.
Welcome
Luminaire Sensor
WE’RE HERE TO HELP: 1 (844) LIGHTCLOUD or 1
844-544-4825
Hello
The Lightcloud Luminaire Sensor is a dual-technology motion detector and
closed loop daylight harvester that can switch and dim both local and remote
circuits. The Luminaire Sensor requires a compatible lightcloud controller or
fixture.
Specifications
PART NUMBER
Edge: LCLCSENSE/EG
Standard: LCLCSENSE/SH
High Bay: LCLCSENSE/HB
INPUT
5VDC
OPERATING TEMPERATURE
-40°C to 40°C
DIMENSIONS
Ceiling Mount : 2.25”W x 1.74”H x 2.25”D
Edge: 1.30”W x 0.99”H x 2.34”D
Standard: 1.20”W x 1.05”H x 1.20”D
High Bay: 1.75”W x 1.08”H x 1.75”D
SENSOR COVERAGE
Edge: 20 ft. diameter at 9 ft.
Standard: 30 ft. diameter at 9 ft.
High Bay: 40 ft. diameter at 30 ft. 50 ft. diameter at 45 ft.
MOUNTING HEIGHT
Edge: 8 to 12 ft.
Standard: 8 to 12 ft.
High Bay: 25 to 45 ft.
CONNECTOR
RJ9 (RJ22)
RATING
Standard and High Bay: IP66
Setup & Installation
-
Remove Bezel Twist counter-clockwise.
-
Prepare Mounting Hole Use knockout or cut hole for sensor. Holes have +/- 1/8 in. tolerance.
-
Installing the Sensor
3a
Ceiling Mount
Place gasket and sensor into ceiling mount
Screw bezel onto sensor from below ceiling.
Fold up tabs on ceiling mount and push through hole cut in step 2.
**3b**
In-Fixture Mounting Place gasket and sensor through the hole cut in step 2.
**3**
Connect the Sensor
Controller: Use the adapter to connect the sensor to the Controller.
Controller: Use the adapter to connect the sensor to the Controller.
If a longer cable is needed, an extension cable (RJ9) up to 10 ft. can be used.
Configuration
To configure the Luminaire Sensor, please login to the Web App at
control.lightcloud.com or call Lightcloud
Support at 1(844) Lightcloud.
For additional startup information, please visit
lightcloud.com/start.
Sensor Coverage
Customer Support
© RAB Lighting, Inc. 2020 170 Ludlow Ave., Northvale, NJ 07647 Custom
manufactured in China
WE’RE HERE TO HELP:
or 1 844-544-4825
Easy Answers
rablighting.com
Visit our website for product info Tech Help Line
Call our experts: 888 722-1000
e-mail Answered promptly –
sales@rablighting.com
Free Lighting Layouts
© 2022 RAB LIGHTING Inc. Answered online or by request
SWISH34 2X2, 2X4 – 1221 73696-RAB
RAB WARRANTY: RAB’S Warranty is subject to all terms and conditions found
atrablighting.com/warranty.