ELKOep CRM-9S Multifunction Time Relay Instructions

June 12, 2024
ELKOep

ELKOep-logo

ELKOep CRM-9S Multifunction Time Relay

ELKOep-CRM-9S-Multifunction-Time-Relay-product

Product Information

Product Name Multifunction Time Relay – SSR
Manufacturer ELKO EP, s.r.o.
Country of Origin Czech Republic
Model CRM-9S

Product Usage Instructions

Connection

Possibility to connect load onto controlling input:

It is possible to connect the load (e.g.: contactor) between terminals S-A2, without any interruption of correct relay function.

Technical Parameters

Parameter Value
Voltage Range 3 VA/0.7 W -15 %; +10 %
Current Rating 60 A/< 10 ms
Maximum Voltage 250 V AC
Power Consumption 1.4 W
Maximum Voltage Drop max. 0.9 V/I max.
Isolation Voltage Yes/I max.
Switching Current 1.5 A
Operating Cycles 100,000,000 ops.
Response Time A1-S Yes min. 25 ms / max. unlimited max. 150 ms
Mounting any DIN rail EN 60715
Ingress Protection IP40 front panel / IP20 terminals

Functions

Function Description
ON DELAY When the input voltage U is applied, timing delay t begins.

Relay contacts R change state after time delay is complete.
Contacts R return to their shelf state when input voltage U is
removed. Trigger switch is not used in this function.
SINGLE SHOT| Upon application of input voltage U, the relay is ready to
accept trigger signal S. Upon application of the trigger signal S,
the relay contacts R transfer and the preset time t begins. During
time-out, the trigger signal S is ignored. The relay resets by
applying the trigger switch S when the relay is not energized.
INTERVAL ON| When input voltage U is applied, relay contacts R change state
immediately and timing cycle begins. When time delay is complete,
contacts return to shelf state. When input voltage U is removed,
contacts will also return to their shelfstate. Trigger switch is
not used in this function.
FLASHER – OFF first| When input voltage U is applied, time delay t begins. When time
delay t is complete, relay contacts R change state for time delay
t. This cycle will repeat until input voltage U is removed. Trigger
switch is not used in this function.
ON/OFF DELAY| Input voltage U must be applied continuously. When trigger
switch S is closed, time delay t begins. When time delay t is
complete, relay contacts R change state and remain transferred
until trigger switch S is opened. If input voltage U is removed,
relay contacts R return to their shelf state.
FLASHER – ON first| When input voltage U is applied, relay contacts R change state
immediately and time delay t begins. When time delay t is complete,
contacts return to their shelf state for time delay t. This cycle
will repeat until input voltage U is removed. Trigger switch is not
used in this function.
MEMORY LATCH| Input voltage U must be applied continuously. Output changes
state with every trigger switch S closure. If input voltage U is
removed, relay contacts R return to their shelf state.
OFF DELAY| Input voltage U must be applied continuously. When trigger
switch S is closed, relay contacts R change state. When trigger
switch S is opened, delay t begins. When delay t is complete,
contacts R return to their shelf state. If trigger switch S is
closed before time delay t is complete, then time is reset. When
trigger switch S is opened, the delay begins again, and relay
contacts R remain in their energized state. If input voltage U is
removed, relay contacts R return to their shelf state.

Warning: Ensure proper understanding of the product manual before usage to avoid any misuse or damage.

Characteristic

  • Multifunction time relay for universal use in automation, control and regulation or in house installations
  • Universal supply voltage AC 12 – 240 V
  • Noiseless switching output
  • Comfortable and well-arranged function and time-range setting by rotary switches.
  • Time scale 0.1 s – 10 days divided into 10 ranges: (0.1 s – 1 s / 1 s – 10 s / 0.1 min – 1 min / 1 min – 10 min / 0.1 hrs – 1 h / 1 h – 10 hrs / 0.1 day – 1 day / 1 day – 10 days / only ON / only OFF)
  • Output contact: 1× static contactless output (triac) 1.5 A, switches potential A1
  • Multifunction red LED fl ashes or shines depending on the operating states

Description

ELKOep-CRM-9S-Multifunction-Time-Relay-
fig-3

  1. Control input (S)
  2. Supply voltage indication
  3. Time range setting
  4. Fine time setting
  5. Function setting
  6. Output contact (B1-18-18)
  7. Supply voltage terminals
  8. Indication of operating states

Symbol

Connection

Possibility to connect load onto controlling input:
It is possible to connect the load (e.g.: contactor) between terminals S-A2, without any interruption of correct relay function.

Technical parameters

Power supply

Supply terminals: A1-A2
Supply voltage: AC 12 – 240 V (50-60 Hz)
Consumption (max.): 3 VA/0.7 W
Supply voltage tolerance: −15 %; +10 %

Time circuit

Number of functions: 10
Time ranges: 0.1 s – 10 days
Time setting: rotary switch and potentiometer
Time deviation: 5 % – mechanical setting
Repeat accuracy: 0.2 % – set value stability
Temperature coefficient: 0.01 %/°C, at = 20 °C (0.01 %/°F, at = 68 °F)

Output

Output contact: 1× static contactless output
Current rating: 1.5 A
Inrush current: 60 A/< 10 ms
Switching voltage: 250 V AC
Power dissipation (max.): 1.4 W
Voltage drop across switch: max. 0.9 V/I max.
Load to terminal B1: Yes/I max. 1.5 A
Electrical lifetime (AC1): 100.000.000 ops.

Control

Control terminals: A1-S
Load between S-A2: Yes
Impulse length: min. 25 ms / max. unlimited
Reset time: max. 150 ms

Other information

Operating temperature: −20 °C .. +55 °C
Storage temperature: −30 °C .. +70 °C
Operating position: any
Mounting: DIN rail EN 60715
Protection degree: IP40 front panel / IP20 terminals
Overvoltage category: III.
Pollution degree: 2
Cross-wire section – solid/ stranded with ferrule (mm2): max. 1× 2.5, 2× 1.5/

max. 1× 2.5 (AWG 14)

Dimensions:| 90 × 17.6 × 64 mm (3.5˝ × 0.7˝ × 2.5˝)
Weight:| 55 g (1.95 oz)
Standards:| EN 61812-1

Warning
The device is constructed for connection in 1-phase network AC 12 – 240 V and must be installed in accordance with regulations and standards applicable in the country of use. Installation, connection, setting and servicing should be installed by qualified electrician staff only, who has learned this instruction and the functions of the device. This device contains protection against overvoltage peaks and disturbances in supply. For correct function of the protection of this device there must be suitable protections of higher degree (A,B,C) installed in front of them. According to standards elimination of disturbance must be ensured. Before installation the main switch must be in position “OFF” and the device should be de-energized. Don´t install the device to sources of excessive electromagnetic interference. By correct installation ensure ideal air circulation so in case of permanent operation and higher ambient temperature the maximal operating temperature of the device is not exceeded. For installation and setting use a screw-driver cca 2 mm. The device is fully-electronic – installation should be carried out according to this fact. Non-problematic function depends also on the way oftransportation, storing and handling. In case of any signs of destruction, deformation, non- function or missing part, don´t install and claim at your seller it is possible to dismount the device after its lifetime, recycle it, or store in the protective dump.

Functions

ON DELAY
When the input voltage U is applied, timing delay t begins. Relay contacts R change state after time delay is complete. Contacts R return to their shelf state when input voltage U is removed. Trigger switch is not used in this function.

INTERVAL ON
When input voltage U is applied, relay contacts R change state immediately and timing cycle begins. When time delay is complete, contacts return to shelf state. When input voltage U is removed, contacts will also return to their shelf state. The trigger switch is not used in this function.

FLASHER – OFF first
When input voltage U is applied, time delay t begins. When time delay t is complete, relay contacts R change state for time delay t. This cycle will repeat until input voltage U is removed. Trigger switch is not used in this function.

FLASHER – ON first
When input voltage U is applied, relay contacts R change state immediately and time delay t begins. When time delay t is complete, contacts return to their shelf state for time delay t. This cycle will repeat until input voltage U is removed. The trigger switch is not used in this function.

OFF DELAY
Input voltage U must be applied continuously. When trigger switch S is closed, relay contacts R change state. When trigger switch S is opened,  delay t begins. When delay t is complete, contacts return to their shelf state. If trigger switch S is closed before time delay t is complete, then time is reset. When trigger switch S is opened, the  delay begins again, and relay contacts R remainin their energized state. If input voltage U is removed, relay contacts R return to their shelf state.

SINGLE SHOT
Upon application of input voltage U, the relay is ready to accept trigger signal S. Upon application of the trigger signal S, the relay contacts R transfer and the preset time t begins. During time-out, the trigger signal S is ignored. The relay resets by applying the trigger switch S when the relay is not energized.

SINGLE SHOT falling edge
Upon application of input voltage U, the relay is ready to accept trigger signal S. Upon application of the trigger signal S, the relay contacts R transfer and the preset time t begins. At the end of the preset time t, the relay contacts R return to their normal condition unless the trigger switch S is opened and closed prior to time out t (before preset time elapses). Continuous cycling of the triggerswitch S at a rate faster than the preset time will cause the relay contacts R to remain closed. If input voltage U is removed, relay contacts R return to their shelf state.

ON/OFF DELAY
Input voltage U must be applied continuously. When trigger switch S is closed, time delay t begins. When time delay t is complete, relay contacts R change state and remain transferred until trigger switch S is opened. If input voltage U is removed, relay contacts R return to their shelf state.

MEMORY LATCH
Input voltage U must be applied continuously. Output changes state with every trigger switch S closure. If input voltage U is removed, relay contacts R return to their shelf state.

PULSE GENERATOR
Upon application of input voltage U, a single output pulse of 0.5 seconds is delivered to relay after time delay t. Power must be removed and reapplied to repeat pulse. Trigger switch is not used in this function.

  • ELKO EP, s.r.o.
  • Palackého 493 769 01 Holešov, Všetuly Czech Republic
  • Tel.: +420 573 514 211
  • e-mail: elko@elkoep.com
  • www.elkoep.com.
  • Made in Czech Republic

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals