ELKOep RFIM-20B Wireless Contact Converter Instruction Manual
- June 5, 2024
- ELKOep
Table of Contents
RFIM-20B, RFIM-40B
Wireless contact converter
RFIM-20B RFIM-40B
02-45/2015 Rev.3
Characteristics
-
RFIM-40/BP-SL: this wireless converter of the contact changes the wired pushbutton / switch to a wireless one.
– 4 inputs enable mutually independent control of 4 elements.
– battery power supply (3V/CR123A – included in the packing) with a lifespan of approx. 8 years, depending on the frequency of use.
– the contact may be closed permanently. -
RFIM-40B/230-SL: this converter of the contact changes the pushbutton / switch with local commercial power supply to a wireless one.
– 4 inputs enable mutually independent control of 4 elements.
– power supply from the network; the inputs respond to activation of the commercial power supply. -
It can be used for transmission of information about closing of a contact (of a detector, pushbutton, technology, logic output).
-
After pressing the pushbutton the preset command (ON/OFF, dimming, timed switching off/on, pulling the blinds up/down) is sent.
-
Optional setting of scenes, where one pressing of a pushbutton controls more iNELS RF Control elements.
-
Reach up to 200m (in open space); in case of insufficient signal strength between the controller and elements, a signal repeater type RFRP-20 can be used, or use the elements with the RFIO2 protocol that support this function.
-
Communication frequency with the RFIO two-way protocol.
-
The BOX design offers installation directly in an installation box under a pushbutton/switch.
Assembly
mounting into an installation box under the existing button / switch
Connection
RFIM-40B/BP-SL RFIM-40B/230-SL
buttons, switch buttons, switch
Control options
RF controlers can control:
-
switches
RFSA-11B, RFSA-61B, RFSA-62B, RFSA-61M, RFSA-66M, RFSAI-61B, RFSC-11, RFSC-61, RFUS-11, RFUS-61, RFJA-12B -
dimmers
RFDA-73/RGB, RFDA-11B, RFDA-71B, RFDEL-71B, RFDEL-71M, RFDSC-11, RFDSC-71, RFDAC-71B -
lighting
RF-RGB-LED-550, RF-White-LED-675
Indicators, settings
Newly produced drivers work in the RFIO² data protocol mode. These drivers are loaded in the actuators in a different way than before. Among other things, it eliminates the risk of inadvertently loading another randomly occurring controller within range. Drivers can still be switched to so-called compatibility mode, and loaded in a simpler (older way). The mode in which the controllers are working is changed and indicated after 8-second pressing of the ‘Prog’ button. The LED diode under the pushbutton is on when the button is kept pressed; after 8 seconds it indicates the chosen mode by different flashing intervals. The mode changes to the inverse mode after each pressing of the button.
RFIO² mode
= Double flash (flash, flash, gap, flash, flash)
Compatibility mode
= Flash fast (flash, flash, flash, flash, flash)
Update the controller actuators in RFIO² mode
If the controller is used in RFIO² mode, then to update the controller
actuators, it is necessary to switch not only the actuator to the update mode
(according to the instructions for the actuator), but also the controller in
the following way: Press the programming button on the controller, converter
for more than 1 second (it is indicated by short extinction of the LED) and
release it. The LED diode under the button starts flashing in second
intervals. Leave the LED flashing on the (controller, converter). Then
activate the programming mode on the actuator by pressing the programming
button for more than 1 second. The actuator is also put into the programming
mode. The desired function can be selected by the respective number of
pressing of the control pushbuttons or inputs (of the converter). The
programming modes on the controller and actuator can be closed by pressing the
programming button for less than 1 second. The LEDs stop flashing.
Device description
Safe handling
When handling a device unboxed it is important to avoid contact with liquids. Never place the device on the conductive pads or objects, avoid unnecessary contact with the components of the device.
Radio frequency signal penetration through various construction
materials
| | | |
---|---|---|---|---
60 – 90 %| 80 – 95 %| 20 – 60 %| 0 – 10 %| 80- 90 %
brick walls| wooden structures with plaster boards| reinforced concrete| metal
partitions| common glass
Technical parameters
| RFIM-240B/BP-SL| RFIM-40-40B/230-SL
---|---|---
Supply voltage:| 1 x 3V battery| 230 V AC
Battery life:| 8 years
Transmission indication| red
Number of inputs:| 4| 4
Supply voltage tolerance:| +10%; -15%
Control|
Communication protocol:| RFIO2
Frequency:| 866-922 MHz
Repeater function:| ne
Signal transmission method:| one-way addressed message
Reach| in the open up to 200 m
Other data|
Operating temperature:| -10 až +50 °C
Operating position:| any
Resist. of connection between terminals – for switched on button:| < 300 Ω
– for disconnected contact:| > 10 kΩ
Mounting:| free at lead-in wires
Protection:| IP40
Voltage category:| III.
Contamination degree:| 2
| screwless terminals
Dimensions:| 43 x 44 x 22 mm
Cross section of connecting wires (mm2)| 0.2-1.5 mm2 solid/flexible
Weight:| 37 g| 25 g
Contact voltage:| 3 V| 230 V
Length of cable to contact:| max. 5 m| max. 100 m
parallel line
Related standards:| EN 60730, EN 63044, EN 300 220, EN 301 489
- RFIM-40B – on condition, that contact is permanently closed- battery life is approx. 1 year.
Attention:
When you instal iNELS RF Control system, you have to keep minimal distance 1
cm between each units.
Between the individual commands must be an interval of at least 1s.
Insertion and replacement of a battery
Using a screwdriver and a light lever in the groove outwards, unlock the four sides of the snap.
Remove the top cover of the product.
Remove the old battery and dispose of it in an environmentally friendly manner.
Insert a new battery, paying attention to the polarity of the battery.
Replace the cover, pushing the tabs in the corners.
Warning
Instruction manual is designated for mounting and also for user of the device. It is always a part of its packing. Installation and connection can be carried out only by a person with adequate professional qualification upon understanding this instruction manual and functions of the device, and while observing all valid regulations. Trouble-free function of the device also depends on transportation, storing and handling. In case you notice any sign of damage, deformation, malfunction or missing part, do not install this device and return it to its seller. It is necessary to treat this product and its parts as electronic waste after its lifetime is terminated. Before starting installation, make sure that all wires, connected parts or terminals are de-energized. While mounting and servicing observe safety regulations, norms, directives and professional, and export regulations for working with electrical devices. Do not touch parts of the device that are energized – life threat. Due to transmissivity of RF signal, observe correct location of RF components in a building where the installation is taking place. RF Control is designated only for mounting in interiors. Devices are not designated for installation into exteriors and humid spaces. The must not be installed into metal switchboards and into plastic switchboards with metal door – transmissivity of RF signal is then impossible. RF Control is not recommended for pulleys etc. – radiofrequency signal can be shielded by an obstruction, interfered, battery of the transceiver can get flat etc. and thus disable remote control.
ELKO EP declares that the RFIM-20B/40B type of equipment complies with
Directives 2014/30/EU, 2011/65/EU, 2015/863/EU and 2014/35/EU. The full EU
Declaration of Conformity is available at:
https://www.elkoep.com/wireless-contact-converter-rfi
m-20b
https://www.elkoep.com/wireless-contact-converter-rfi
m-40b
ELKO EP, s.r.o., Palackého 493, 769 01 Holešov, Všetuly, Czech Republic
Tel.: +420 573 514 211, e-mail:elko@elkoep.com,
www.elkoep.comMade in Czech Republic
ELKO EP, s.r.o. | Palackého 493 | 769 01 | Holešov, Všetuly | Česká republika
e-mail: elko@elkoep.cz | EN Support: +420 778 427 366
Documents / Resources
|
ELKOep RFIM-20B Wireless Contact
Converter
[pdf] Instruction Manual
RFIM-20B, RFIM-40B, Wireless Contact Converter, RFIM-20B Wireless Contact
Converter
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>