sauermann TH 110 Humidity and Temperature Transmitter User Guide

June 12, 2024
sauermann

sauermann TH 110 Humidity and Temperature Transmitter

Operating temperature, protection of the instruments and information about storage
Conditions of use (°C/%RH/m): from -10 to +50 °C; in non-condensing conditions. From 0 to 2000 m.
Protection: IP65(2) or IP20(1)
Storage temperature: from -10 to +70 °C.

Dimensions

Duct model

Dimensions

Ambient model

Dimensions

Remote model
Dimensions

Standard model
Dimensions

Symbols used

For your safety and in order to avoid any damage of the device, please follow the procedure described in this document and read carefully the notes preceded by the following symbol:

The following symbol will also be used in this document, please read carefully the information notes indicated after this symbol:

Connections

Connections

  1. Switch 1 (S1)
  2. Switch 2 (S2)
  3. LCC-S software connection
  4. Output terminal block
  5. Power supply terminal block
  6. Cable gland

(1) Ambient model / (2) Duct, remote and standard model.

Electrical connections as per NFC15-100 standard

This connection must be made by a qualified and trained technician.
To make the connection, the transmitter must NOT BE ENERGIZED.

For TH 110-AOS, TH 110-ANS, TH 110-AOD, TH 100-AND, TH 110-AOA, TH 110-ANA TH 110-ANES, TH 110-AOES models with output 0-10 V – active:
Electrical connections as per NFC15-100 standard

To make a 3-wire connection, BEFORE POWERING UP the transmitter, please connect the output ground to the input ground. See drawing below.
Electrical connections as per NFC15-100 standard

For TH 110-POS, TH 110-PNS, TH 110-POD, TH 110-PND, TH 110-POA, TH 110-PNA, TH 110-PNES models with output 4-20 mA – passive:
Electrical connections as per NFC15-100 standard

Settings and use of the transmitter

Configuration

It is possible to set the measuring ranges and the unit of the instrument either by switch and/or via software.

**Active switch

**

To configure the transmitter, it must not be energized. Then, you can make the settings required, with the DIP switches (as shown on the drawing below).When the transmitter is configured, you can power it up.

Please follow carefully the combinations beside with the DIP switch.
If the combination is wrongly done, the following message will appear on the display of the transmitter “CONF ERROR”. In that case, you will have to unplug the transmitter, place the DIP switches correctly, and then power the transmitter up

Units setting – active switch Outputs setting – active switch

To set a unit of measurement, put the on-off switch 4 of the units as shown below.| To set an output, put the on-off switches 1, 2 and 3 of the measuring ranges as shown below.
Configurations| °C| °F| From 0 to +50 °C| From -20 to +80 °C| From -50 to +50 °C| From 0 to +100 °C
Combinations| | | | | |

Configuration via LCC-S software (option)

It is possible to configure intermediate ranges, an offset…
Example: for a 0-100 °C transmitter, minimum delta is 20 °C.
The instrument can be configured from 0 to +20 °C or from -10 to +10 °C. In order to compensate a possible drift of the sensor, it is possible to add an offset to the displayed value by the TH 110 transmitter: it shows 48% RH, a standard instrument shows 45% RH. It is then possible, via the software, to integrate an offset of -3 to the displayed value by the TH 110 instrument.

The configuration of the parameters can be done either with the DIP switch or via software (you can not combine both solutions).

PC configuration

Connect the cable of the LCC-S to the connection of the transmitter.

Active switch (S1)

Please refer to the user manual of the LCC-S software to make the configuration.

Mounting
To mount the transmitter, mount the ABS plate on the wall (drilling: Ø 6 mm, screws and pins are supplied).
Insert the transmitter on the fixing plate (see A on the drawing beside).
Rotate the housing in clockwise direction until you hear a “click” which confirms that the transmitter is correctly installed.
Mounting

Maintenance: please avoid any aggressive solvent. Please protect the transmitter and its probes from any cleaning product containing formalin, that may be used for cleaning rooms or ducts.

Precautions for use: please always use the device in accordance with its intended use and within parameters described in the technical features in order not to compromise the protection ensured by the device.

CUSTOMER SUPPORT

Download the LCC-S software user manual
CUSTOMER SUPPORT

Download the TH 110 data sheet
CUSTOMER SUPPORT

Customer service portal

Use our Customer service portal to contact us
https://sauermann-en.custhelp.com
CUSTOMER SUPPORT

www.sauermangroup.com

sauermann Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals