RAB GUSJR-2FT GUS JR Field Adjustable Instruction Manual

June 12, 2024
RAB

RAB GUSJR-2FT GUS JR Field Adjustable

RAB GUSJR-2FT GUS JR Field Adjustable

IMPORTANT

READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is  required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON
FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
WARNING : Make certain power is OFF before installing or maintaining fixture.
Suitable for damp locations. Suitable for continuous row mounting.

SURFACE MOUNTING

The fixture is suitable for indoor applications for ceiling or wall mounting, as follows:

  1. Carefully snap out Lens one side at a time from Housing.

  2. Rotate the Fasteners (4) 90 degrees and remove them from LED Tray Kit. Unclip pre-installed Tether Cables (2) as shown in Fig. 1 to separate LED Tray Kit from the Housing.
    Surface Mounting

  3. Pull supply wires from Junction Box (not supplied) through Center Access Hole of Housing as shown in Fig. 1. Use appropriate UL-rated wire connectors as required by code to make electrical splices to fixture leads.

  4. Secure Housing to junction box or mount Housing directly to a sturdy surface by using the Drill Locations (4 holes for 2 ft & 4 ft fixture) fixture. Use the appropriate mounting hardware for the mounting surface.

  5. Once connection is made reinstall the Tether Cable (2) to LED Tray Kit. Push the LED Tray Kit into the Housing and rotate the Fasteners (4) to secure. Ensure that the wires are not pinched between Housing and LED Tray Kit.

  6. Replace Lens. Hook Lens to one side of Housing and snap Lens into place as shown in Fig. 2.
    Surface Mounting
    WARNING: To prevent wiring damage or abrasion, do not expose wiring to edges of sharp objects.

V-HOOK MOUNTING

The fixture can be mounted using V-hook (ordered separately as VHOOKGUSJR).

  1. Mount V-hook to the housing as shown in Fig. 3. Use the appropriate mounting hardware for the mounting surface.
  2. For electrical wiring, snap out the Lens and LED Tray Kit as shown in Fig.1.
  3. Pull supply wires in fixture through Central Access Hole. Use appropriate UL-rated wire connectors as required by code to make electrical splices to fixture leads.

FIELD ADJUSTMENT

Follow instructions below to change the Fixture Power (W) and/or Color Temperature (CCT) from factory settings:

Factory Settings:
GUSJR2 20/15/10W 20W / 4000K
GUSJR44 40/30/20W 40W / 4000K

  1. Locate the Field-Adjustable Switches on the bottom side of Fixture Housing as shown in Fig. 5.
  2. Select Power (W) and Color Temperature (CCT) by sliding respective switch to the desired value (Fig. 5)
    Field Adjustment

ROW MOUNTING AND THROUGH WIRING

  1. Line up the fixtures end to end and secure together as shown in Fig. 4 using Screws (2) provided.
  2. Follow directions on Page 1 to secure housings to mounting surface. If necessary, feed wires through from one fixture to the other.
    Row Mounting And Through Wiring

PIR MODELS

Screw Sensor Head onto the Bracket as shown in Fig. 6. See factory settings below (optional remote sold separately for custom settings, CAT# MSR1).

Factory Settings:

  • Brightness: 100%
  • Hold Time: 1 Minute
  • Daylight: Disabled
  • Sensitivity: 50%
  • Stand-by dimming level: 20%
  • Stand-by time: 1 Minute
    Pir Models

MVS MODELS (Internal)

(optional remote sold separately for custom settings, CAT# MSR1).

  • Sensitivity: 100%

0-10V DIMMABLE WIRING

Universal voltage driver permits operation at 120V through 277V, 50 or 60 Hz. For 0-10V dimming follow the wiring directions as shown in Fig. 7.
0-10v Dimmable Wiring

  1. Connect the black fixture lead to the LINE supply lead
  2. Connect the white fixture lead to the COMMON supply lead.
  3. Connect the GROUND wire from fixture to supply ground.
  4. Connect the purple fixture lead to the (V+) DIM lead.
  5. Connect the pink fixture lead to the (V-) DIM lead.
  6. Cap the red fixture lead, if present. Do NOT connect.

CLEANING & MAINTENANCE

CAUTION: Be sure fixture temperature is cool enough to touch.
Do not clean or maintain while fixture is energized.

  1. Clean acrylic lens with non-abrasive cleaning solution.
  2. Do not open the fixture to clean the LEDs. Do not touch the LEDs.

TROUBLESHOOTING

  1. Check that the line voltage at the fixture is correct. Refer to wiring directions.
  2. Be sure the fixture is grounded properly

BATTERY BACKUP MODELS

WIRING

CAUTION: FOR BATTERY BACKUP FIXTURE.

Voltage can be present in BATTERY. To prevent high voltage from being present on output leads, Inverter connector must be open. Do not join BATTERY connector until installation is complete and AC power is supplied to the emergency driver (Fig. 8).
NOTE: Make sure that the necessary branch circuit wiring is available. An UNSWITCHED AC source of power is required. The emergency driver must be fed from the same branch circuit as the LED driver. CAUTION: Do not use any supply voltage other than 120-277V 50/60 HZ.
Wiring

  1. Connect UNSWITCHED HOT fixture lead to HOT AC supply line.
  2. If using an UNSWITCHED circuit, connect UNSWITCHED and SWITCHED lines together.
  3. If using a SWITCHED circuit, connect SWITCHED HOT AC fixture lead to the external.
  4. Connect the pink fixture lead to the (V-) DIM lead.
  5. For 0-10V dimming, connect DIM (+) and DIM (-) lead to the supply ground. Do not connect GROUND to the output leads.
  6. All unused leads must be capped and insulated.
  7. After installation is complete, supply AC power to the fixture and connect the BATTERY.
  8. When power is on, the fixture should be on and the Charging Indicator Light should illuminate to indicate the battery is charging.
  9. Once the BATTERY has charged for at least one hour, a short duration test may be performed by pressing the Test Button (Fig. 9).
  10. After the battery has charged for 24 hours, a long duration test can be performed by shutting power to the fixture.

OPERATION

  1. When AC power is applied, the charging indicator light is illuminated indicating that the BATTERY is being charged.
    Note: The charging indicator light and test switch are located on the LED tray below the lens.

  2. When power fails, the standby power automatically switches to backup mode at reduced power resulting in lower illumination. The emergency driver supplies power in standby mode for a minimum of 90 minutes.

  3. When AC power is restored, the emergency driver automatically returns to charging mode.

MAINTENANCE

Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to ensure that it is working. The following schedule is recommended:

  1. Visually inspect the Charging Indicator Light monthly. It should be illuminated.
  2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.
  3. Conduct a 90-minute discharge test once a year. Fixture would operate at reduced illumination for a minimum of 90 minutes.

TROUBLESHOOTING

  1. Is the fixture grounded properly?
  2. If the Charging Indicator Light does not illuminate after pressing the Test Button, check if battery is connected properly.

Note : These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.

Customer Support

rablighting.com
Visit our website for product info
Tech Help Line
Call our experts: 888 722-1000
e-mail
Answered promptly – sales@rablighting.com
Free Lighting Layouts
Answered online or by request

RAB Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals