RAB GUSJR-2FT GUS JR Field Adjustable
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR
FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and
all applicable local codes. Proper grounding is required for safety. THIS
PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE
BY A PERSON
FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS
INVOLVED.
WARNING : Make certain power is OFF before installing or maintaining
fixture.
Suitable for damp locations. Suitable for continuous row mounting.
SURFACE MOUNTING
The fixture is suitable for indoor applications for ceiling or wall mounting, as follows:
-
Carefully snap out Lens one side at a time from Housing.
-
Rotate the Fasteners (4) 90 degrees and remove them from LED Tray Kit. Unclip pre-installed Tether Cables (2) as shown in Fig. 1 to separate LED Tray Kit from the Housing.
-
Pull supply wires from Junction Box (not supplied) through Center Access Hole of Housing as shown in Fig. 1. Use appropriate UL-rated wire connectors as required by code to make electrical splices to fixture leads.
-
Secure Housing to junction box or mount Housing directly to a sturdy surface by using the Drill Locations (4 holes for 2 ft & 4 ft fixture) fixture. Use the appropriate mounting hardware for the mounting surface.
-
Once connection is made reinstall the Tether Cable (2) to LED Tray Kit. Push the LED Tray Kit into the Housing and rotate the Fasteners (4) to secure. Ensure that the wires are not pinched between Housing and LED Tray Kit.
-
Replace Lens. Hook Lens to one side of Housing and snap Lens into place as shown in Fig. 2.
WARNING: To prevent wiring damage or abrasion, do not expose wiring to edges of sharp objects.
V-HOOK MOUNTING
The fixture can be mounted using V-hook (ordered separately as VHOOKGUSJR).
- Mount V-hook to the housing as shown in Fig. 3. Use the appropriate mounting hardware for the mounting surface.
- For electrical wiring, snap out the Lens and LED Tray Kit as shown in Fig.1.
- Pull supply wires in fixture through Central Access Hole. Use appropriate UL-rated wire connectors as required by code to make electrical splices to fixture leads.
FIELD ADJUSTMENT
Follow instructions below to change the Fixture Power (W) and/or Color Temperature (CCT) from factory settings:
Factory Settings:
GUSJR2 20/15/10W 20W / 4000K
GUSJR44 40/30/20W 40W / 4000K
- Locate the Field-Adjustable Switches on the bottom side of Fixture Housing as shown in Fig. 5.
- Select Power (W) and Color Temperature (CCT) by sliding respective switch to the desired value (Fig. 5)
ROW MOUNTING AND THROUGH WIRING
- Line up the fixtures end to end and secure together as shown in Fig. 4 using Screws (2) provided.
- Follow directions on Page 1 to secure housings to mounting surface. If necessary, feed wires through from one fixture to the other.
PIR MODELS
Screw Sensor Head onto the Bracket as shown in Fig. 6. See factory settings below (optional remote sold separately for custom settings, CAT# MSR1).
Factory Settings:
- Brightness: 100%
- Hold Time: 1 Minute
- Daylight: Disabled
- Sensitivity: 50%
- Stand-by dimming level: 20%
- Stand-by time: 1 Minute
MVS MODELS (Internal)
(optional remote sold separately for custom settings, CAT# MSR1).
- Sensitivity: 100%
0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V through 277V, 50 or 60 Hz.
For 0-10V dimming follow the wiring directions as shown in Fig. 7.
- Connect the black fixture lead to the LINE supply lead
- Connect the white fixture lead to the COMMON supply lead.
- Connect the GROUND wire from fixture to supply ground.
- Connect the purple fixture lead to the (V+) DIM lead.
- Connect the pink fixture lead to the (V-) DIM lead.
- Cap the red fixture lead, if present. Do NOT connect.
CLEANING & MAINTENANCE
CAUTION: Be sure fixture temperature is cool enough to touch.
Do not clean or maintain while fixture is energized.
- Clean acrylic lens with non-abrasive cleaning solution.
- Do not open the fixture to clean the LEDs. Do not touch the LEDs.
TROUBLESHOOTING
- Check that the line voltage at the fixture is correct. Refer to wiring directions.
- Be sure the fixture is grounded properly
BATTERY BACKUP MODELS
WIRING
CAUTION: FOR BATTERY BACKUP FIXTURE.
Voltage can be present in BATTERY. To prevent high voltage from being present
on output leads, Inverter connector must be open. Do not join BATTERY
connector until installation is complete and AC power is supplied to the
emergency driver (Fig. 8).
NOTE: Make sure that the necessary branch circuit wiring is available. An
UNSWITCHED AC source of power is required. The emergency driver must be fed
from the same branch circuit as the LED driver. CAUTION: Do not use any supply
voltage other than 120-277V 50/60 HZ.
- Connect UNSWITCHED HOT fixture lead to HOT AC supply line.
- If using an UNSWITCHED circuit, connect UNSWITCHED and SWITCHED lines together.
- If using a SWITCHED circuit, connect SWITCHED HOT AC fixture lead to the external.
- Connect the pink fixture lead to the (V-) DIM lead.
- For 0-10V dimming, connect DIM (+) and DIM (-) lead to the supply ground. Do not connect GROUND to the output leads.
- All unused leads must be capped and insulated.
- After installation is complete, supply AC power to the fixture and connect the BATTERY.
- When power is on, the fixture should be on and the Charging Indicator Light should illuminate to indicate the battery is charging.
- Once the BATTERY has charged for at least one hour, a short duration test may be performed by pressing the Test Button (Fig. 9).
- After the battery has charged for 24 hours, a long duration test can be performed by shutting power to the fixture.
OPERATION
-
When AC power is applied, the charging indicator light is illuminated indicating that the BATTERY is being charged.
Note: The charging indicator light and test switch are located on the LED tray below the lens. -
When power fails, the standby power automatically switches to backup mode at reduced power resulting in lower illumination. The emergency driver supplies power in standby mode for a minimum of 90 minutes.
-
When AC power is restored, the emergency driver automatically returns to charging mode.
MAINTENANCE
Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to ensure that it is working. The following schedule is recommended:
- Visually inspect the Charging Indicator Light monthly. It should be illuminated.
- Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.
- Conduct a 90-minute discharge test once a year. Fixture would operate at reduced illumination for a minimum of 90 minutes.
TROUBLESHOOTING
- Is the fixture grounded properly?
- If the Charging Indicator Light does not illuminate after pressing the Test Button, check if battery is connected properly.
Note : These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.
Customer Support
rablighting.com
Visit our website for product info
Tech Help Line
Call our experts: 888 722-1000
e-mail
Answered promptly – sales@rablighting.com
Free Lighting Layouts
Answered online or by request
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>