BEGA 51219.6 Indoor Wall Luminaire Instruction Manual

June 13, 2024
BEGA

BEGA 51219.6 Indoor Wall Luminaire

Product Information

Parameter Value
Safety The installation and operation of this luminaire are subject to

national safety regulations. Installation and commissioning may
only be carried out by a qualified electrician. The manufacturer
accepts no liability for damage caused by improper use or
installation. If subsequent modifications are made to the
luminaire, the person responsible for these modifications shall be
considered the manufacturer.
Overvoltage Protection| The electronic components installed in the luminaire are
protected against overvoltage in accordance with DIN EN 61547. To
achieve an additional protection against e.g. transients, etc., we
recommend separate overvoltage protection components. You can find
them on our website at www.bega.com.
Lamp Module connected wattage| 25 W
Luminaire connected wattage| 28.4 W
Rated temperature| 25-30 °C
Ambient temperature| max 25-30 °C
Module designation| LED-1166/930
Colour temperature| 3000 K
Colour rendering index (CRI)| CRI > 90
Module luminous flux| 3900 lm
Luminaire luminous flux| 447 lm
Luminaire luminous efficiency| 15.7 lm / W

Product Usage Instructions

  1. The installation and commissioning of this luminaire should only be carried out by a qualified electrician.
  2. Ensure that the luminaire is operated within the rated temperature range of 25-30 °C.
  3. To achieve additional protection against overvoltage and transients, it is recommended to use separate overvoltage protection components, which can be found on the manufacturer’s website at www.bega.com.
  4. Do not make any modifications to the luminaire without proper authorization from the manufacturer.
  5. When replacing parts, use the specified spares such as LED power supply unit, LED module 3000 K, reflector, and component round blank.

Wall luminaire for indoor use

BEGA 51219.6 Indoor Wall Luminaire-fig1

Instructions for use

Application

Wall luminaire · Indoor luminaire with velvet black metal housing.
Luminaire with light source shielded to the front and metallic inside colour of the reflection surface.
Radial light emission 360°.

Product description

  • Wall luminaire “STUDIO LINE”

  • Luminaire housing made of aluminium, surface Colour velvet black inside hue matt copper Inside synthetic cover, translucent white 3 fixing holes ø 4.5 mm Angle 120° · Pitch circle ø 155 mm

  • 1 cable entry for through-wiring for mains cable Connection terminal 2.5@

  • Earth conductor connection

  • LED power supply unit
    220-240 V x 0/50-60 Hz
    DC 170-280 V

  • BEGA Thermal Switch®

  • Temporary thermal shutdown to protect temperature-sensitive components

  • Safety class I

  • c  – Conformity mark

  • Weight: 3.1 kg

Safety

  • The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
  • The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
  • To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at www.bega.com

Lamp

  • Module connected wattage 25 W
  • Luminaire connected wattage 28.4 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 30 °C

51 219.6 K3

  • Module designation LED-1166/930
  • Colour temperature 3000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 3900 lm
  • Luminaire luminous flux 447 lm
  • Luminaire luminous efficiency 15,7 lm / W

Installation

LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
Remove the mounting plate with LED unit from its packaging.
Please note: A round blank made of synthetic material covers the mains connection compartment. For the mains supply connection, this synthetic round blank must be removed and refitted after the mains supply connection.
Loosen the black knurled screw (slotted) and remove the round made of synthetic material from the LED unit.
Pass the power connecting cable through the cable entry in the mounting plate.

BEGA 51219.6 Indoor Wall Luminaire-fig2

Fasten the mounting plate with the supplied fastening material or other suitable fastening material to the installation surface.
Establish the earth conductor connection on the earthing screw (1) of the mounting plate. Make the electrical connection to the terminals. Observe the correct configuration of the connecting cable. Connect the live conductor to the brown wire (L) and the neutral conductor to the blue wire (N).
Insert the round made of synthetic material back into the LED unit and tighten the black knurled screw (slotted).
Remove the luminaire housing (reflector) from its packaging and carefully guide over the LED unit.
Place the luminaire housing (reflector) over the keyholes onto two threaded bolts of the LED unit and turn it clockwise until it stops. Tighten the two hex nuts M4 over the keyholes. Remove the supplied radial synthetic cover with round housing cover from the packaging, guide onto the centre of the grub screw of the LED unit and hand-tighten in the clockwise direction.

Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.

Replacing the LED module

Replacing the power supply unit

  • The designation of the LED module is noted on a label in the luminaire.

  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The replacement can be carried out by a qualified person using standard tools.
    Disconnect the system from the power supply. Loosen the radial synthetic cover with round housing cover by turning it anti-clockwise from the LED unit.

  • Loosen the black knurled screw (slotted) and remove the round made of synthetic material from the LED unit.

  • Disconnect the earth conductor connection and the electrical connection to the terminal. Loosen the mounting screws of the power supply unit, the round blank bracket and earthing screws (Torx).

  • Remove the pot with LED module. Install the replacement pot.

  • Please follow the installation instructions for the LED module.

  • Replace defective LED power supply unit. Tighten the mounting screws of the power supply unit, the round blank bracket and earthing screws (Torx) again.

  • Establish the earth conductor connection on the earthing screw (1) of the mounting plate. Make the electrical connection to the terminals. Observe the correct configuration of the connecting cable. Connect the live conductor to the brown wire (L) and the neutral conductor to the blue wire (N).

  • Insert the round made of synthetic material back into the LED unit and tighten the black knurled screw (slotted).

  • Guide the radial synthetic cover with round housing cover onto the centre of the grub screw of the LED unit and hand-tighten in the clockwise direction.

Spares

  • LED power supply unit DEV-0422/700
  • LED module 3000 K LED-1166/930
  • Reflector 71 003 561 B17
  • Component round blank 75 005 267

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals