BEGA 84 618 In Ground Floodlight Instruction Manual

June 12, 2024
BEGA

BEGA 84 618 In Ground Floodlight

Product Information

Overvoltage Protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve additional protection against transients, we recommend using separate overvoltage protection components. These can be found on our website at www.bega.com.

Main Supply Connection
Make sure to correctly configure the mains supply cable. Connect the mains supply at the brown (L), blue (N), and green-yellow lead (1). Control cables are connected using the leads marked with DALI. If these leads are not used, the luminaire will operate at full light output. Place the lamp enclosure into the recessed housing and align it properly. Tighten the locking screws firmly.

Technical Specifications

Lamp Module Connected Wattage| Luminaire Connected Wattage| Rated Temperature| Ambient Temperature
---|---|---|---
24 W| 27 W| ta = 25| ta max = 30

Lamp Module Information (84 618 K3)

Module Designation| Colour Temperature| Colour Rendering Index| Module Luminous Flux| Luminaire Luminous Flux| Luminaire Luminous Efficiency
---|---|---|---|---|---
3x LED-0897/830| 3000 K| CRI > 80| 4185 lm| 2626 lm| 97.3 lm/W

Lamp Module Information (84 618 K4)

Module Designation| Colour Temperature| Colour Rendering Index| Module Luminous Flux| Luminaire Luminous Flux| Luminaire Luminous Efficiency
---|---|---|---|---|---
3x LED-0897/840| 4000 K| CRI > 80| 4245 lm| 2663 lm| 98.6 lm/W

Light Technique

In-ground floodlight with wide beam asymmetrical light distribution. Particularly suitable for floodlighting objects with high uniformity. German patent DE 199 188 72. The values of thecharts show approximate value q on the illuminated surface.

Accessories

  • Distribution box for installation in soil (70 730)
  • Distribution box with 7 cable entries

Product Usage Instructions

Replacing the LED Module

The designation of the LED module is noted on a label in the luminaire. To replace the module, follow these steps:

  1. Make sure you are a qualified person using standard tools.
  2. Locate the label with the designation of the LED module.
  3. Remove the old LED module from the luminaire.
  4. Insert the new LED module, ensuring it matches the designation of the original module.

DIMENSIONS

BEGA-84-618-In-Ground-Floodlight-FIG-1

Instructions for use

Application

  • In-ground floodlight · Wall washer
  • The design of this in-ground floodlight makes it possible to fully illuminate a vertical surface, e.g. a façade, from the ground to the lower edge of the roof. The lower limit of the light distribution is a straight line, without the usual “light cone”.
  • The luminaires can be driven over by vehicles with pneumatic tyres.

Please note:
Luminaire must not be used for installation in road lanes, where the fixture is exposed to a horizontal strain due to braking, acceleration and change of direction.

Product description

  • Luminaire made of aluminium alloy, aluminium and stainless steel
  • BEGA Tricoat® coating technology
  • Recess housing made of stainless steel (Steel grade no. 1.4301) with 2 cable entries for cable conduit, max. ø 30 mm
  • Hardened crystal glass
  • Reflector surface made of pure aluminium 1,8 m water-resistant connecting cable 07
  • RN8-F 5 G 1@ with implemented water stopper and 1.2 m
  • PVC cable conduit
  • BEGA Ultimate Driver®
  • LED power supply unit
  • 220-240 V x 0/50-60 Hz
  • DC 176-276 V
  • DALI controllable
  • A basic isolation exists between power cable and control line
  • BEGA Thermal Control®
  • Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
  • Safety class I
  • Protection class IP 67
  • Dust-tight and protection against temporary immersion
  • Pressure load 1,000 kg (~10 kN)
  • Impact strength IK10
  • Protection against mechanical impacts < 20 joule
  • Maximum surface temperature 40 °C (measured according to EN 60598 of ta 15 °C)
  • – Conformity mark
  • – Safety mark
  • Weight: 6.3 kg
  • This product contains light sources of energy efficiency classes

Safety

  • The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
  • We recommend fuse protection via a residual current circuit breaker to be provided by the customer.
  • The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
  • To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at www.bega.com.

Notice prior to installation:

  • To accept the maximum pressure load of 1,000 kg (~10 kN) a proper foundation must be provided by the customer.
  • The luminaire is mounted in a recess housing made of stainless-steel.
  • The pressure load is transferred to the foundation by this housing provided at site. The foundation must be carried out on firm subgrade.
  • In order to obtain a firm stableness, the recess housing must be firmly concreted in. During preparation of the foundation proper drainage must be provided, so that entering surface water can drain off.
  • The floor covering prepared later should be either on the same level or below the top edge of the recess housing.

Installation

  • Luminaire housing must not be installed in heat-insulating material.
  • Dismantling the luminaire from the recess housing.
  • Open the luminaire by undoing 3 hexagon socket head screws (wrench size 6 mm) in the luminaire housing up to the stop. Turn luminaire counter-clockwise as far as it will go and lift floodlight out of the recess housing.
  • Position recess housing on the foundation (as described before) and fix it with enclosed or any other suitable fixing material. Note alignment to the surface to be illuminated.
  • Luminaire housing must not be installed in heat-insulating material.
  • A customer-provided connecting sleeve outside of the installation housing is required to connect the luminaire to the power supply.
  • We recommend to use a BEGA distribution box 70 730 or 71 053.
  • Pass the protective cable conduit from the connecting sleeve into the installation housing. Pass the connection cable through the protective conduit and connect it securely to the underground cable.
  • 0.5 m of cable is provided in the installation housing so that the luminaire may be removed. If a connection underneath the luminaire is planned, the customer must ensure that there is enough clearance.We recommend a DN 150 pipe and the 70 730 distribution box for drainage. After installation, the distribution box must be sealed.
  • Note correct configuration of the mains supply cable. Make mains supply connection at the brown (L), blue (N) and green-yellow lead (1). The connection of the control cables is achieved by means of the both leads marked with DALI.
  • In case these leads are not used the luminaire will be operated at full light output.
  • Place lamp enclosure into recessed housing and align. Tighten locking screws firmly.

Lamp

  • Module connected wattage 24 W
  • Luminaire connected wattage 27 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 30 °C

84 618 K3

  • Module designation 3x LED-0897/830
  • Colour temperature 3000 K
  • Colour rendering index CRI > 80
  • Module luminous flux 4185 lm
  • Luminaire luminous flux 2626 lm
  • Luminaire luminous efficiency 97,3 lm / W

84 618 K4

  • Module designation 3x LED-0897/840
  • Colour temperature 4000 K
  • Colour rendering index CRI > 80
  • Module luminous flux 4245 lm
  • Luminaire luminous flux 2663 lm
  • Luminaire luminous efficiency 98,6 lm / W

Light technique

  • In-ground floodlight with wide beam asymmetrical light distribution. Particularly suitable for floodlighting objects with high uniformity.
  • German patent DE 199 188 72
  • The values of the charts show approximate value q on the illuminated surface.

BEGA-84-618-In-Ground-Floodlight-FIG-5

  • A distance between luminaires and facade
  • H height of the facade
  • B distance between luminaires
  • Ē Average illuminance on the facade
  • Emin minimum illuminance

Replacing the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
  • Disconnect the electrical installation.
  • Clean dirt and deposits from key openings of screw head.
  • Do not use a high pressure cleaner. Dismantling the luminaire from the recess housing.
  • Open the luminaire by undoing 3 hexagon socket head screws (wrench size 6 mm) in the luminaire housing up to the stop. Turn luminaire counter-clockwise as far as it will go and lift floodlight out of the recess housing.
  • Open the luminaire and clean.
  • Take off reflector plate carefully.
  • Use only solvent-free cleaners.
  • The luminaire housing must be completely clean and absolutely dry.
  • Please follow the installation instructions for the LED module.
  • Check all screws and threads thoroughly and grease them.
  • Check the gasket and replace, if necessary.
  • A broken glass must be replaced.
  • Assembly to be carried out in reverse sequence.

Accessories

  • Distribution box for installation in soil
    70 730 Distribution box with 7 cable entries

  • Connection terminals 5 x 4@
    71 053 Distribution box with 10 cable entries

  • Connection terminals 6 x 16@

For the accessories a separate instructions for use can be provided upon request.

Spares

  • Spare glass 14 001 299
  • LED power supply unit DEV-0312/700
  • LED module 3000 K LED-0897/830
  • LED module 4000 K LED-0897/840
  • Reflector 76 001 814

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>