BEGA 12130.1 LED Ceiling and Wall Luminaire for Indoor Use
Product Information
- Product Description: Luminaire made of Aluminium, finish Colour white Hand-blown opal glass, satin matt, with screw neck
- Silicone gasket
- 2 cable entries for through-wiring for mains
- Distance apart 190 mm Connecting terminal 2.5@ with plug connection
- Earth conductor connection
- 2-pole connecting terminal for LED power supply unit 220-240 V x 0/50-60 Hz DC 176-276 V
- DALI-controllable
- Number of DALI addresses: 1
- Basic insulation is provided between the mains
- Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
- Safety class I
- Protection class IP 64
- Dust-tight and protection against splash water
- Impact strength IK05
- Weight: 2.4 kg
- This product contains light sources of energy efficiency class(es) D
Product Usage Instructions
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer. The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve an additional protection against e.g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.
Lamp Information
- Lamp Module connected wattage: 13.8 W
- Luminaire connected wattage: 16 W
- Colour temperature: 3000 K
- Colour rendering index (CRI): > 90
- Module luminous flux: 2255 lm
- Luminaire luminous flux: 1231 lm
- Luminaire luminous efficiency: 76.9 lm / W
DIMENSIONS
Instructions for use
Application
- Ceiling and wall luminaire · indoor luminaire made of aluminium and hand-blown opal glass, satin matt.
- For a variety of lighting applications.
Product Description
-
Luminaire made of Aluminium, finish Colour white
-
Hand-blown opal glass, satin matt, with screw neck
-
Silicone gasket
-
2 cable entries for through-wiring for mains supply
-
cable up to ø 10.5 mm max. 5 G 1.5@
-
2 mounting holes ø 5.5 mm
-
Distance apart 190 mm
-
Connecting terminal 2.5@ with plug connection
Earth conductor connection -
2-pole connecting terminal for digital control
-
BEGA Ultimate Driver®
-
LED power supply unit
-
220-240 V x 0/50-60 Hz
-
DC 176-276 V
-
DALI-controllable
-
Number of DALI addresses: 1
-
Basic insulation is provided between the mains and control cables
-
BEGA Thermal Control®
-
Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
-
Safety class I
-
Protection class IP 64
-
Dust-tight and protection against splash water Impact strength IK05
-
Protection against mechanical impacts < 0.7 joule
-
– Safety mark
-
– Conformity mark
-
Weight: 2.4 kg
This product contains light sources of energy efficiency class(es) D
Safety
- The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
- The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Overvoltage protection
- The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
- To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
- You can find them on our website at www.bega.com.
Lamp
- Module connected wattage 13.8 W
- Luminaire connected wattage 16 W
- Rated temperature ta = 25 °C
- Ambient temperature ta max = 45 °C
12 130.1 K3
- Module designation LED-0854/930
- Colour temperature 3000 K
- Colour rendering index CRI > 90
- Module luminous flux 2255 lm
- Luminaire luminous flux 1231 lm
- Luminaire luminous efficiency 76,9 lm / W
Installation
- LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
- Remove glass from luminaire housing by turning it counter-clockwise.
- Disassemble LED module.
- Disconnect plug connection.
- Lead the mains supply cable through the cable entry into the luminaire housing.
- Fix luminaire housing with enclosed or any other suitable fixing material onto the mounting surface.
- It is absolutely essential to use the enclosed gaskets.
- Push silicone sleeves over the lines, make ground and electrical connection to the terminal – plug connection.
- For digital control please use the 2-pole plug connector (DALI).
- In case this connector is not used the luminaire will be operated at full light output.
- Push plug into coupler as far as it will go. Assemble LED module.
- Screw glass with gasket firmly into the luminaire housing by turning it clock-wise.
- Make sure that gasket is positioned correctly.
Cleaning · Maintenance
- Clean luminaire regularly with solvent-free cleansers from dirt.
- Defective glass must be replaced.
Replacing the LED module
- The designation of the LED module is noted on a label in the luminaire.
- The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
- The module can be replaced by qualified persons using standard tools.
- Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module.
- Inspect and, if necessary, replace the luminaire gaskets.
- Defective glass must be replaced.
- Close the luminaire.
Spares
- Spare glass 11 003 081 40R G
- LED power supply unit DEV-0312/500
- LED module 3000 K LED-0854/930
- Gasket Glas 83 000 367
BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com
References
Read User Manual Online (PDF format)