BEGA 50696.1 Recessed Ceiling Downlight Instruction Manual
- June 12, 2024
- BEGA
Table of Contents
- BEGA 50696.1 Recessed Ceiling Downlight
- Product Information
- Product Usage Instructions
- DIMENSIONS
- Instructions for use
- Product description
- Safety
- Overvoltage protection
- Installation
- Cleaning · Maintenance
- Replacing the LED module
- Accessories
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
BEGA 50696.1 Recessed Ceiling Downlight
Product Information
Product Name: 50 696.1
Lamp Module: LED-0800/930
Color Temperature: 3000 K
Colour Rendering Index (CRI): > 90
Module Luminous Flux: 1255 lm
Luminaire Luminous Flux: 838 lm
Luminaire Luminous Efficiency: 85.5 lm/W
Lamp Module Connected Wattage: 8.1 W
Luminaire Connected Wattage: 9.8 W
Rated Temperature: 25°C – 55°C
Product Usage Instructions
- Safety: The installation and operation of this luminaire must comply with national safety regulations. Only a qualified electrician should perform the installation and commissioning. The manufacturer is not liable for any damage caused by improper use or installation. If modifications are made to the luminaire, the person responsible for the modifications will be considered the manufacturer.
- Overvoltage Protection: The luminaire’s electronic components have built-in protection against overvoltage according to DIN EN 61547. For additional protection against transients, it is recommended to use separate overvoltage protection components available on the manufacturer’s website.
- Connect to Power Supply: Connect the LED power supply unit to the luminaire. Route the power supply unit through the installation housing and place it in the suspended ceiling. Connect the 2-pin plug connector between the luminaire and the external LED power supply unit.
- Replacing the LED Module: The designation of the LED module is noted on a label inside the luminaire. Qualified individuals canreplace the module using standard tools. Before replacing, disconnect the system and open the luminaire. Follow the installation instructions provided for the LED module. Close the luminaire after replacement.
- Power Supply Units: The power supply units supplied are suitable for operating only one LED luminaire.
- Accessories: Separate instructions for use can be provided upon request for accessories.
- Spares: The following spare parts are available:
- Spare Glass: Ersatzglas
- LED Module 3000 K Reflector: LED-0800/930
DIMENSIONS
Instructions for use
Application
Recessed ceiling luminaire · indoor luminaire with direct and indirect light
distribution for connection to an external LED power supply unit.
For surface-mounted installation in indoor suspended ceilings of 5-25 mm
thickness.
Product description
- Recessed luminaire without power supply unit
- Luminaire housing made of cast aluminium
- Installation housing is made of glass-fibre reinforced polyamide with 2 fastening springs
- Reflector made of pure anodised aluminium Light-diffusing silicone lens
- Ceiling trim ring made of metal, Colour white Hand-blown opal glass, satin matt
- Recessed opening ø 130 mm
- Required installation depth 95 mm
- 1 connecting cable with strain relief and plug connector system for BEGA power supply unit, on/off or DALI
- Safety class III 3
- CE – Conformity mark
- Weight: 1.1 kg
- This product contains light sources of energy efficiency class(es) E
Safety
- The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
- The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Overvoltage protection
- The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
- To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
- You can find them on our website at www.bega.com.
Lamp
- Module connected wattage 8.1 W
- Luminaire connected wattage 9.8 W
- Rated temperature ta = 25 °C
- Ambient temperature ta max = 55 °C
- When installed in heat-insulating material ta max = 35 °C
50 696.1 K3
- Module designation LED-0800/930
- Colour temperature 3000 K
- Colour rendering index CRI > 90
- Module luminous flux 1255 lm
- Luminaire luminous flux 838 lm
- Luminaire luminous efficiency 85,5 lm / W
Lighting technology
- Half beam angle 50°
Installation
A separate power supply unit is required to operate the luminaire.
- For connection to external LED-power supply unit – accessory 13 143 or 13 168 – the luminaire is equipped with a 2-pin connector. Note operating instructions of the LED-power supply units.
- LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
- The recessed opening is covered by the frame of the luminaire housing.
- Fixing of the installation housing in the recessed opening is achieved by using two adjustable springs.
Installation into inserted ceilings:
- A recessed opening of 130 mm is necessary to accept the installation housing. Recessed depth min. 95 mm.
- Compress the fastening springs of the installation housing against their spring pressure on both sides towards the housing and slide the installation housing into the recessed opening.
- The fastening springs catch the ceiling panel from the back side. Minimum thickness of the ceiling panel is 5 mm. If minimum thickness of the panel is less than 5 mm it must be reinforced from the reverse side. Maximum thickness of the ceiling panel must be no more than 25 mm.
- Connect to the LED power supply unit.
- Route the LED power supply unit through the installation housing and place it in the suspended ceiling.
- Connect the 2-pin plug connector between luminaire and external LED power supply unit.
- Press together the two internal fixing sliders inside the luminaire housing.
- Push the luminaire housing to the end of the installation housing and then release the fixing sliders.
- This mechanism ensures that the luminaire housing sits securely inside the installation housing.
- Installation housing and external LED-power supply unit must not be installed in heat-insulating material.
- Please use the protective gloves provided for the installation to prevent finger prints on the reflector.
- Place the reflector with silicone lens on the ceiling trim ring. Twist the ceiling trim ring complete with the attached reflector to the right to fix the assembly inside the luminaire housing.
Cleaning · Maintenance
- Clean luminaire regularly with solvent-free cleansers from dirt.
Replacing the LED module
- The designation of the LED module is noted on a label in the luminaire.
- The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
- Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module.
- Close the luminaire.
Accessories
- Power supply units for LED luminaires 220-240 V · 0/50-60 Hz with strain relief and plug connector system.
- 13 143 Power supply unit on/off
- 13 168 Power supply unit DALI
- The power supply units are only suitable for the operation of one LED luminaire.
- For the accessories a separate instructions for use can be provided upon request.
Spares
- Spare glass 11 003 416 .0M 1RG
- LED module 3000 K LED-0800/930
- Reflector 75 002 722
BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>