Wall washer for indoor use
Instructions for use
Application
Wall washer · indoor luminaire with asymmetrical light distribution for
illuminating wall and ceiling surfaces. The luminaire can be installed with
the light distribution opening upwards or downwards.
Product description
- Die-cast aluminium and aluminium housing, finish Colour velvet white
- Matt safety glass
- Reflector made of pure anodised aluminium 2 mounting holes ø 4.5mm
- Distance apart 200mm 2 cable entries for through-wiring of mains supply cable ø 7-10.5mm, max. 5G1.5@
- Connecting terminal and earth conductor terminal 2.5@ 2-pole connecting terminal for digital control
- LED power supply unit 220-240 V x 0/50-60 Hz
- DC 170-276 V
- DALI-controllable
- Basic insulation is provided between the mains and control cables
- BEGA Thermal Control®
- Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
- Safety class I
- Impact strength IK07
- Protection against mechanical impacts < 2 joule
- Safety mark
- Conformity mark
- Weight: 2.9 kg
This product contains light sources of energy efficiency classes D, E
Safety
The installation and operation of this luminaire are subject to national
safety regulations. Installation and commissioning may only be carried out by
a qualified electrician. The manufacturer accepts no liability for damage
caused by improper use or installation. If subsequent modifications are made
to the luminaire, the person responsible for these modifications shall be
considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve an additional protection against e.g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.
Lamp
Module connected wattage 32.7 W
Luminaire connected wattage 36.1 W
Rated temperature ta=25 °C
Ambient temperature ta max=35 °C
50 201.1K27
Module designation LED-0609/927
Colour temperature 2700 K
Colour rendering index CRI >90
Module luminous flux 4675 lm
Luminaire luminous flux 3253 lm
Luminaire luminous efficiency 90,1 lm/W
50 201.1K3
Module designation LED-0609/930
Colour temperature 3000 K
Colour rendering index CRI >90
Module luminous flux 4830 lm
Luminaire luminous flux 3361 lm
Luminaire luminous efficiency 93,1 lm/W
50 201.1K4
Module designation LED-0609/940
Colour temperature 4000 K
Colour rendering index CRI >90
Module luminous flux 5025 lm
Luminaire luminous flux 3501 lm
Luminaire luminous efficiency 97 lm/W
Installation
Undo hexagon socket head screws (wrench size 3 mm) through the opening in the luminaire housing up to the stop and lift luminaire top. Loosen earth connection (plug connection) and LED-connection between luminaire top and luminaire base. LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping. Lead the mains supply cable through the cable entry of the luminaire base. Ensure correct directionality towards the area to be illuminated. Fix luminaire base with enclosed or any other suitable fixing material onto the mounting surface. Make the earth conductor connection and theelectrical connection. For digital control please use the connecting terminal DA, DA. In case this terminal is not used the luminaire will be operated at full light output. Make earth connection (plug connection) and LED-connection between luminaire top and luminaire base again. Install the luminaire top, press-on and tighten screws evenly
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Replacement of the LED module
The designation of the LED module is noted on a label in the luminaire. The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools. Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module. Defective glass must be replaced. Close the luminaire.
Spares
LED power supply unit DEV-0391/700
LED module 2700 K LED-0609/927
LED module 3000 K LED-0609/930
LED module 4000 K LED-0609/940
Reflector 76 001 485
BEGA Gantenbrink-Leuchten KG · Postfach 3160 · 58689 Menden ·