BEGA 24 140 Ceiling Mounted Downlight Instruction Manual

June 12, 2024
BEGA

BEGA 24 140 Ceiling Mounted Downlight

Instructions for use

Application
Hall downlights with symmetrical narrow beam light distribution for the illumination of large and tall rooms such as departure halls, factories, sports halls and auditoriums.

Product description

  • Luminaire made of aluminium alloy, aluminium and stainless steel
  • BEGA Unidure® coating technology
  • Clear safety glass
  • Silicone gasket
  • Reflector surface made of pure aluminium 2 mounting rails made of stainless steel for mounting on existing on-site structures or
  • Mounting with mounting frame 13 576 under ceilings and cantilever plates or from high ceilings with steel cable set 13 582 (see accessories)
  • Connection box with 2 cable entries for through-wiring of the mains supply cable ø 5-13 mm, max. 5×2,5@
  • BEGA Ultimate Driver®
  • LED power supply unit 220-240 V x 0/50-60 Hz
  • DC 176-264 V
  • During DC operation the LED power is reduced to 50 %
  • DALI-controllable
  • Basic insulation is provided between the mains and control cables
  • BEGA Thermal Control®
  • Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
  • Safety class I p Ballproof according to DIN VDE 0710 part 13
  • Protection class IP 65
  • Dust-tight and protection against water jets Impact strength IK08
  • Protection against mechanical impacts < 5 joule
    • r – Safety mark
    • c  – Conformity mark
    • Weight: 1 7.5 kg
  • This product contains light sources of energy efficiency class(es) C, D

Lamp

  • Module connected wattage 269 W
  • Luminaire connected wattage 298 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 40 °C

24 140 K3

  • Module designation 4x LED-0967/830
  • Colour temperature 3000 K
  • Colour rendering index CRI > 80
  • Module luminous flux 45600 lm
  • Luminaire luminous flux 35776 lm
  • Luminaire luminous efficiency 120,1 lm / W

24 140 K4

  • Module designation 4x LED-0967/840
  • Colour temperature 4000 K
  • Colour rendering index CRI > 80
  • Module luminous flux 46720 lm
  • Luminaire luminous flux 36655 lm
  • Luminaire luminous efficiency 123 lm / W

Lighting technology
Symmetrical narrow beam light distribution Half beam angle 29°

Safety
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
  • To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at: www.bega.com.

Installation

  • Secure the luminaire housing to the on-site construction using suitable fixing material. For thermal reasons, make sure to comply with the correct distance between the housing and installation-side mounting surface provided by the two mounting rails.
  • When mounting with mounting frame 13 576 or steel cable set 13 582 (BEGA accessories), please observe the corresponding instructions for use.
  • For the electrical connection, unscrew the round plug connector and pull it apart. Loosen the hexagon socket screws on the retaining bracket and remove the connection box.

BEGA-24-140-Ceiling-Mounted-Downlight-FIG-2

  • Use the supplied connection box to make the electrical connection (see illustration).
  • Undo hexagon socket head screws (wrench size 3 mm) and open the connection box. Run the power connecting cable through the M20 cable gland and into the connection box. For through-wiring, the factory-fitted dummy plugs must be removed.
  • Tighten the cable glands securely.
  • Make the earth conductor connection and the electrical connection.
  • Observe the correct configuration of the connecting cable. Connect the live conductor to the brown wire (L), the neutral conductor to the blue wire (N) and the earth conductor to the green-yellow wire (PE).
  • The control cables are connected via the two DALI-labelled wires.
  • If these wires are not assigned, the luminaire will work with full light output.
  • Close the connection box. Make sure the gasket is properly located.
  • Secure the connection box to the luminaire housing using the retaining bracket or to the mounting frame, as applicable.
  • Press the round plug connector firmly together and screw it in place.

BEGA-24-140-Ceiling-Mounted-Downlight-FIG-3

Reduction of luminous flux
Besides digital control you can limit the luminous flux manually by means of an integrated rotary coded switch inside the luminaire housing.
By this means an operation at higher ambient temperatures is possible.

  • Switch position 0 = 100 % max. ta: 40 °C
  • Switch position 1 = 70 % max. ta: 50 °C
  • Switch position 2 = 5 0 % max. ta: 65 °C
  • Switch position 3 = 30 % max. ta: 75 °C

Cleaning · Maintenance

  • Clean luminaire regularly with solvent-free cleansers from dirt and deposits.
  • Do not use high pressure cleaners.

Replacing the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
  • The module can be replaced by qualified persons using standard tools.
  • Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module.
  • Inspect and, if necessary, replace the luminaire gaskets.
  • Defective glass must be replaced.
  • Close the luminaire.

Accessories

  • 13 576 Mounting frame
  • 13 582 Steel cable set

A separate instructions for use can be provided upon request.

Spares

  • LED power supply unit DEV-0283/1000
  • LED module 3000 K LED-0967/830
  • LED module 4000 K LED-0967/840
  • Reflector 76 001 867 B1
  • Gasket glass frame 83 001 901
  • Gasket control gear box 83 001 902