BEGA 50349.4 Wall Luminaire Instruction Manual

June 12, 2024
BEGA

BEGA-LOGO

BEGA 50349.4 Wall Luminaire

Product Information

The product is a wall luminaire from the STUDIO LINE series. It features an aluminum luminaire housing with a velvet white finish. The luminaire contains LED modules for mains voltage 220-230 V at 50/60 Hz. It has a weight of 0.65 kg and contains light sources with energy efficiency class F. The electronic components in the luminaire are protected against overvoltage in accordance with DIN EN 61547.

Product Usage Instructions

  1. The installation and operation of this luminaire should be done in accordance with national safety regulations.
  2. Installation and commissioning should only be carried out by a qualified electrician.
  3. Do not make any modifications to the luminaire without proper authorization, as the person responsible for these modifications will be considered the manufacturer.
  4. If you require additional protection against transients or overvoltage, it is recommended to use separate overvoltage protection components. These components can be found on the BEGA website at www.bega.com.
  5. For replacing the LED module, follow these steps:
  6. Disconnect the system and open the luminaire.
  7. Refer to the installation instructions for the LED module.
  8. Inspect and, if necessary, replace the luminaire gaskets.
  9. Close the luminaire.

Please note that the product manual contains additional information that may be relevant for specific scenarios. It is recommended to refer to the complete user manual for detailed instructions and safety precautions.

Dimension

BEGA-50349.4-Wall-Luminaire-FIG-1

Instructions for use

Application
Wall luminaire · indoor luminaire with velvet white luminaire housing and inside hue. The light emits upwards and downwards.
Product description
Wall luminaire “STUDIO LINE” Aluminium luminaire housing, finish Colour velvet white inside hue matt brass Reflector made of pure anodised aluminium 2 elongated fixing holes Width 4.5 mm · 90 x 38 mm spacing 1 cable entry for through-wiring for mains cable Connecting terminal 2.5@ with plug connection Earth conductor connection-Module for mains voltage 220-230 V y 50/60 Hz BEGA Thermal Switch® Temporary thermal shutdown to protect temperature-sensitive components Safety class I r – Safety mark c – Conformity mark Weight: 0.65 kg This product contains light sources of energy efficiency class(es) F

Safety

The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.You can find them on our website at www.bega.com.

  • Lamp
    • Luminaire connected wattage 10 W
    • Rated temperature ta = 25 °C
    • Ambient temperature ta max = 40 °C
  • 50 349.4 K3
    • Module designation LED-0607/930
    • Colour temperature 3000 K
    • Colour rendering index Ra > 90
    • Module luminous flux 940 lm
    • Luminaire luminous flux 249 lm
    • Luminaire luminous efficiency 24,9 lm / W

Installation

LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation orrelamping. Undo set screw and lift off the luminaire housing. Loosen LED connection and earth connection (plug connection).Pass the power connecting cable through the cable entry in the mounting plate. Note position of application of the luminaire“arrow down”. Fasten the mounting plate with the supplied fastening material or other suitable fastening material to the installation surface. Make earth conductor connection. Push silicone sleeves over the lines and make electrical connection to terminal (plug connection). Make earth conductor connection between luminaire housing and mounting plate.Push LED plug into coupler as fa as it will go.Install luminaire housing over mounting plate and tighten set screw.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools. Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module. Inspect and, if necessary, replace the luminaire gaskets. Close the luminaire.
Spares
LED module 3000 K LED-0607/930