BEGA 50218.1 LED Ceiling and Wall Luminaire for Indoor Use Instruction Manual
- June 12, 2024
- BEGA
Table of Contents
50 218.1
Ceiling and wall luminaire for indoor use
Instructions for use
50218.1 LED Ceiling and Wall Luminaire for Indoor Use
Application
Ceiling and wall luminaire · indoor luminaire made of impact resistant
synthetic diffuser and aluminium housing.
Luminaire with free-radiating and uniform light distribution for linear
illumination in interior.
Product description
Luminaire made of Aluminium, finish Colour white Light-diffusing synthetic
luminaire cover 4 elongated fixing holesWidth Ø 5.5 mm Connection terminal
2.5@ Earth conductor connection 2-pole connecting terminal for digital control
LED power supply unit
220-240 V 0/50-60 Hz DC 176-276 V During DC operation the LED power is
reduced to 15 % DALI-controllable Number of DALI addresses: 1 Basic insulation
is provided between the mains and control cables BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components
without switching off the luminaire Safety class I
– Safety mark
** – Conformity mark
Weight:** 5.0 kg
This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation.
If subsequent modifications are made to the luminaire, the person responsible
for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.
Lamp
Module connected wattage| 70.4 W
Luminaire connected wattage| 80 W
Rated temperature| ta = 25 °C
Ambient temperature| ta max = 45 °C
50 218.1 K3
Module designation| 8x LED-0694/930
Colour temperature| 3000 K
Colour rendering index| CRI > 90
Module luminous flux| 10960 lm
Luminaire luminous flux| 9425 lm
Luminaire luminous efficiency| 117,8 lm / W
Please note:
If the luminaire is to be mounted onto a metallic, electroconductive surface,
it is mandatory to make sure that the mounting surface is connected conductive
to the earth conductor of the luminaire!
Note:
If you a planning a linear arrangement of several luminaires, you must keep a
minimum distance of 30 mm between the luminaire caps for installation reasons.
Installation
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.
Remove the luminaire from the packaging and put it down so that the open rear
side of its housing rests on a soft surface.
Undo the lateral Torx countersunk screw T25 and remove the luminaire cap.
Make earth conductor connection.
Push silicone sleeves over the lines and make electrical connection to the
terminals.
For digital control please use the connecting terminal DA, DA.
In case this terminal is not used the luminaire will be operated at full light
output.
Drill mounting holes into the mounting surface.
Secure the luminaire housing to the installation surface with the fixing
materials provided or other suitable materials.
For wall installation note the position of application “arrow down”.
To prevent dirt accumulating on the LED modules, press the supplied plugs into
the housing holes of the luminaire profile above the screw-fitting points.
Clip the luminaire cover into the groove of the aluminium profile and push it
until the stop of the luminaire housing.
Replace the housing cap and tighten lateral Torx countersunk screw T25.
Cleaning – Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted. The module can be replaced by
qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Defective luminaire cover must be replaced.
Close the luminaire.
Spares
Synthetic cover| 15 000 481 .1
LED power supply unit| DEV-0214/2100i
LED module 3000 K| LED-0694/930
Technical amendments reserved
BEGA Gantenbrink-Leucite KG
Postfach 31 60
58689 Menden
info@bega.com
www.bega.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>