BEGA 78047.1 Indoor Wall Luminaire Instruction Manual

June 12, 2024
BEGA

78 047.1
Wall luminaire for indoor use
Instructions for use

78047.1 Indoor Wall Luminaire

BEGA 78047.1 Indoor Wall Luminaire

**Application

**

Wall luminaire · indoor luminaire with integrated power supply unit for orientating lighting tasks.

Product description

Die-cast aluminium and aluminium housing, finish Colour white   Crystal glass, inside white 2 elongated fixing holes Width 4.5 mm · 68 mm spacing 1 cable entry for mains supply cable up to ø 10.5 mm max. 3 x 1.5@ Connection terminal 2.5@ Earth conductor connection BEGA Ultimate Driver® LED power supply unit 220-240 V 0/50-60 Hz DC 176-264 V Safety class I Impact strength IK05 Protection against mechanical impacts < 0.7 joule
– Safety mark
**  – Conformity mark
Weight:** 0.4 kg
This product contains light sources of energy efficiency class(es) D

Safety

The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.

Lamp

Module connected wattage| 2 W
Luminaire connected wattage| 2.7 W
Rated temperature| ta = 25 °C
Ambient temperature| ta max = 60 °C
78 047.1 K3
Module designation| LED-0234/930
Colour temperature| 3000 K
Colour rendering index| CRI > 90
Module luminous flux| 305 lm
Luminaire luminous flux| 227 lm
Luminaire luminous efficiency| 84,1 lm / W

Installation

LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during installation or relamping.
Undo the screws and lift off the luminaire top.
Lead the mains supply cable through the cable entry of the luminaire base.
Fix luminaire base with enclosed or any other suitable fixing material onto the mounting surface.
Be sure to use the gasket rings supplied.
Make earth conductor connection.
Push silicone sleeves over the lines and make electrical connection.
Make earth conductor connection (plug connection) between luminaire top and luminaire base.
Install luminaire top part, adjust it and tighten screws evenly.

Cleaning – Maintenance

Clean luminaire regularly with solvent-free cleansers from dirt.
Defective glass must be replaced.
Replacement of the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Defective glass must be replaced.
Close the luminaire.

Spares

LED power supply unit| DEV-0292/350
LED module 3000 K| LED-0234/930

BEGA Gantenbrink-Leuchten KG · Postfach 31 60
58689 Menden
[email protected]
www.bega.com