This product is a luminaire that requires installation and operation in accordance with national safety regulations. It is recommended to have a qualified electrician handle the installation and commissioning to ensure proper usage. The manufacturer does not accept liability for any damage caused by improper use or installation. Modifications to the luminaire should only be done by the person responsible for these modifications. The electronic components in the luminaire are protected against overvoltage according to DIN EN 61547. For additional protection against transients and other issues, separate overvoltage protection components are recommended, which can be found on the manufacturer’s website at www.bega.com.

The product specifications include:

  • Lamp Module connected wattage: 8.1 W
  • Luminaire connected wattage: 9.8 W
  • Rated temperature: 25°C to 55°C
  • Ambient temperature when installed in heat-insulating material: 35°C
  • Module designation: LED-0800/930
  • Colour temperature: 3000 K
  • Colour rendering index (CRI): > 90
  • Module luminous flux: 1255 lm
  • Luminaire luminous flux: 796 lm
  • Luminaire luminous efficiency: 81.2 lm / W

Product Usage Instructions

To replace the LED module, follow these steps:

  1. Identify the designation of the LED module from the label in the luminaire.
  2. Ensure that the light colour and light output of the replacement module match the original module.
  3. Disconnect the system and open the luminaire.
  4. Refer to the installation instructions for the LED module and follow them carefully.
  5. Close the luminaire once the replacement module is installed.

Note that the power supply units provided with the product are suitable for operating one LED luminaire only. If additional accessories are required, a separate instructions for use can be requested.

For spare parts, the following items are available:

  • Spare glass: 11 003 452 10M RG
  • LED module 3000 K Reflector: LED-0800/930 75 002 722

DIMENSIONS

BEGA-50687-LED-Recessed-Ceiling-Downlight-for-Indoor-Use-
fig-1

Instructions for use

Application

  • Recessed ceiling downlight · Interior luminaire with symmetrical narrow beam light distribution for connection to an external LED power supply unit.
  • For surface-mounted installation in indoor suspended ceilings of 5-25 mm thickness.

Product Description

  • Recessed luminaire without power supply unit Luminaire housing made of cast aluminium Installation housing is made of glass-fibre reinforced polyamide with 2 fastening springs Reflector made of pure anodised aluminium Optical silicone lens
  • Partially matt crystal glass
  • Recessed opening ø 130 mm
  • Required installation depth 95 mm
  • 1 connecting cable with strain relief and plug connector system for BEGA power supply unit, on/off or DALI

Safety class III 3

  • CE – Conformity mark
  • Weight: 1.3 kg
  • This product contains light sources of energy efficiency class(es) E

Safety

  • The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
  • The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
  • To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at www.bega.com.

Lamp

  • Module connected wattage 8.1 W
  • Luminaire connected wattage 9.8 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 55 °C
  • When installed in heat-insulating
  • material ta max = 35 °C

50 687 K3

  • Module designation LED-0800/930
  • Colour temperature 3000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 1255 lm
  • Luminaire luminous flux 796 lm
  • Luminaire luminous efficiency 81,2 lm / W

Lighting technology

  • Half beam angle 59°

Installation

  • A separate power supply unit is required to operate the luminaire.
  • For connection to external LED-power supply unit – accessory 13 143 or 13 168 – the luminaire is equipped with a 2-pin connector. Note operating instructions of the LED-power supply units.
  • LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
  • The recessed opening is covered by the frame of the luminaire housing.
  • Fixing of the installation housing in the recessed opening is achieved by using two adjustable springs.

Installation into inserted ceilings:

  • A recessed opening of 130 mm is necessary to accept the installation housing. Recessed depth min. 95 mm.
  • Compress the fastening springs of the installation housing against their spring pressure on both sides towards the housing and slide the installation housing into the recessed opening.
  • The fastening springs catch the ceiling panel from the back side. Minimum thickness of the ceiling panel is 5 mm. If minimum thickness  of the panel is less than 5 mm it must be reinforced from the reverse side. Maximum thickness of the ceiling panel must be no more than 25 mm.
  • Connect to the LED power supply unit.
  • Route the LED power supply unit through the installation housing and place it in the suspended ceiling.
  • Connect the 2-pin plug connector between luminaire and external LED power supply unit.

BEGA-50687-LED-Recessed-Ceiling-Downlight-for-Indoor-Use-
fig-2

  • Press together the two internal fixing sliders inside the luminaire housing.
  • Push the luminaire housing to the end of the installation housing and then release the fixing sliders.
  • This mechanism ensures that the luminaire housing sits securely inside the installation housing.
  • Please use the protective gloves provided for the installation to prevent finger prints on the reflector.
  • Place the reflector with silicone lens onto
  • the glass. Twist the glass with the attached reflector to the right to fix the assembly inside the luminaire housing.

Cleaning · Maintenance

  • Clean luminaire regularly with solvent-free cleansers from dirt.

Replacing the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
  • Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module.
  • Close the luminaire.

Accessories

  • Power supply units for LED luminaires 220-240 V · 0/50-60 Hz with strain relief and plug connector system.
  • 13 143 Power supply unit on/off
  • 13 168 Power supply unit DALI
  • The power supply units are only suitable for the operation of one LED luminaire.
  • For the accessories a separate instructions for use can be provided upon request.

Spares

  • Spare glass 11 003 452 10M RG
  • LED module 3000 K LED-0800/930
  • Reflector 75 002 722

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · [email protected] · www.bega.com