EATON Cooper Power Series 600 A 25 kV Class T-OP II Deadbreak Connector Instruction Manual

June 4, 2024
EATON

COOPER POWER SERIES
600 A 25 kV Class T-OP II deadbreak connector

Instruction Manual
EATON Cooper Power Series 600 A 25 kV Class T OP II Deadbreak
Connector

General

Eaton terminates high-voltage underground cable to transformers, switches, switchgear, and other apparatus with its Cooper PowerE series 600 A, 25 kV Class T-OPE II deadbreak connector. It is fully shielded and submersible and meets the requirements of IEEE Std 386E-2016— “Separable Insulated Connector Systems”. The 200 A three-phase rated load break interface provides a means for obtaining a live test, visible ground, and visible break using a clamp stick. It also provides a convenient location for an Eaton’s Cooper Power series metal oxide varistor elbow (M.O.V.E.) arrester or grounding elbow. Eaton offers an exclusive optional capacitive test point similar to 200 A elbow connectors. This allows the use of test point reset (TPR) faulted circuit indicators. T-OP II connectors are designed for use on solid dielectric cable (XLPE or EPR) with extruded semi-conducting shields and concentric neutral, with or without a jacket. Installation on the jacketed concentric neutral cable may require additional sealing material. Adapters are available for terminating tape shields and drain wire jacketed cable.

Installation

The T-body is assembled onto the prepared cable with a threaded coppertop compression connector or shear bolt and using a T-wrench, the load break- reducing tap plug is threaded into the connector. The short end of a special copper alloy stud, provided with the kit, is threaded into a de-energized 600 A bushing. The assembled housing is then connected to the ap pa ratus bushing using an O&T tool (with cap) and an installation torque tool. The T-OP II connector’s unique captured rotating nut provides ease of removal of the T-OP II connector system from the apparatus bushing. (See Table 6 for information on tools.) Refer to Service Information MN650048EN, 600 A 15/25 kV Class T-OP II Connector Assembly Installation Instructions for details.

Production tests

Tests are conducted in accordance with IEEE Std 386-2016:

  • ac 60 Hz 1-minute withstand
  • 40 kV
  • Minimum partial discharge extinction voltage
  • 19 kV

Tests are conducted in accordance with Eaton re quire ments:

  • Physical inspection
  • Periodic dissection
  • Periodic fluoroscopic analysis

Table 1. Voltage ratings and characteristics

Description kV
Standard voltage class 25
Maximum rating phase-to-phase (loadbreak-reducing tap plug only) 26.3
Maximum rating phase-to-ground 15.2
ac 60 Hz 1-minute withstand 40
dc 15-minute withstand 78
BIL and full wave crest 125
Minimum partial discharge extinction voltage 19

Note: N Voltage ratings and characteristics are in accordance with IEEE Std 386-2016.
Table 2. Current ratings and characteristics

Description Amperes

600 A Interface
Continuous| 600 A rms
24-hour overload| 1000 A rms
Short time| 40,000 A rms symmetrical for 0.20 s
27,000 A rms symmetrical for 4 s
200 A Interface a
Continuous| 200 A rms
Switching| 10 operations at 200 rms at 26.3 kV phase-to-phase
Fault closure| 10,000 A rms symmetrical at 26.3 kV phase-to-phase after 10 switching operations for 0.17 s
Short time| 10,000 A rms symmetrical for 0.17 s
3500 A rms symmetrical for 3 s

  1. System design and protection must recognize the ratings of the 200 A interface.
    Note: Current ratings and characteristics are in ac cor dance with IEEE Std 386-2016.

Features and benefits

EATON Cooper Power Series 600 A 25 kV Class T OP II Deadbreak Connector -
fig 1 Figure 1. T-OP II cutaway design features

Note: Dimensions are in inches (mm) and are for reference only.

Optional features

Protective cap
200 A insulated protective cap fits over a loadbreak-reducing tap plug for dead front shielding.
Capacitive test point
Capacitive test point on molded T-body, with snap-on cap, provides a place to mount STVT, STLO, and STHI series fault indicators.
Copper alloy stud
The copper alloy stud with its extended length allows for threading into the connector prior to mating the bushing and terminator interfaces. Blunt start threads on the stud help eliminate cross threading. Stud threads into an industry-standard 600 A bushing.
T-wrench
The T-wrench is used to install the load break-reducing tap plug into the compression connector and T-body.
EATON Cooper Power Series 600 A 25 kV Class T OP II Deadbreak Connector -
fig 3 Torque tool
The torque tool is required to check the torque of a 25 kV Class T-OP II deadbreak connector or bushing adapter when it is installed on a 600 A bushing interface. It is precision calibrated and hot stick operable.
EATON Cooper Power Series 600 A 25 kV Class T OP II Deadbreak Connector -
fig 4 Combination operating and test/torque tool
The combination operating and test/torque tool is used with a hot stick to test for circuit de-energization and to install and remove a 25 kV Class LRTP equipped connector from an apparatus tap. The standard tool is equipped with a molded EPDM rubber cap and torque limiter to allow proper tool seating and gripping of the T-OP II connector. It also ensures that the connector has been properly torqued into the mating bushing.
EATON Cooper Power Series 600 A 25 kV Class T OP II Deadbreak Connector -
fig 5 5/16-inch hex shaft
5/16-inch hex shaft with 3/8-inch socket drive tool.
EATON Cooper Power Series 600 A 25 kV Class T OP II Deadbreak Connector -
fig 6EATON Cooper
Power Series 600 A 25 kV Class T OP II Deadbreak Connector - fig
7 Figure 2. T-OP II connector profile and stacking dimensions in inches (mm)

Ordering information

Each T-OP II Connector kit contains:

  • Molded rubber T-body
  • Loadbreak-reducing tap plug
  • Cable adapter
  • Coppertop compression connector
  • Copper alloy stud
  • Silicone lubricant
  • Installation instruction sheet
    Use the following procedure to develop the correct part number for the desired T-OP II connector kit, based on cable size, conductor size, and desired options.

T-OP II connector kit—catalog numbering system
Build the 9- to 11-digit catalog number for a T-OP II kit by following the steps given below. The first 5 digits are “TP625”, so only digits 6 through 9 need to be selected. Digits 10 and 11 are optional.
EATON Cooper Power Series 600 A 25 kV Class T OP II Deadbreak Connector -
fig 9 Catalog number digits:
1 and 2 — “TP” = T-OP II connector system
3 — “6” = 600 A system
4 and 5 — “25” = 25 kV class
Step 1. Select digits 6 and 7 cable adapter range code Determine the cable’s diameter over the electrical insulation as shown in Figure 3 (including tolerances). Then identify a cable range from Table 3 that covers the minimum and maximum insulation diameters. Select the correct cable range code from Table 3.
Table 3. Cable diameter range

Inches mm range code
0.61–0.97 15.5–24.6 AB
0.75–1.08 19.1–2 7.4 CC
0.97–1.31 24.6–33.3 DD
1.09 –1.47 2 7.7– 3 7.3 EE
1.26–1.64 32.0 – 41.7 FF
1.36–1.71 34.5–43.4 GG
1.51–1.85 3 8.4 – 47.0 HH
1.70 –1.97 43.2–50.0 JJ

Step 2. Select digits 8 and 9 conductor code
Identify the conductor size and type in Table 4 (compression) or Table 5 (shear bolt) and select the conductor code from the appropriate column.
Table 4. Compression connector

Concentric or compressed Compact or solid
AWG or kcmil mm²
No connector
#2 35
#1
Jan-00 50
Feb-00 70
Mar-00
Apr-00 95
250 120
300
350
400 185
450
500 240
600 300
650
750
900
1000 500
1250 630

Table 5. Shear bolt connector
Cable conductor size
AWG or kcmil

Compact| Compressed| Concentric| mm² standard sizes| Conductor code| Catalog number
---|---|---|---|---|---
Jan-00| Jan-00| Jan-00| 50| S1| CDT630SB150T
Feb-00| Feb-00| Feb-00| 70|
Mar-00| Mar-00| Mar-00| —
Apr-00| Apr-00| Apr-00| 95
250| 250| 250| 120
350| —| —| 150
—| 350| 350| 185| S3| DT630SB300T
500| 500| 500| 240
600| 600| 600| 300
700| —| —| —
—| 700| 700| —| S4| CDT630SB400T
750| 750| 750| —
800| 800| —| 400
900| —| —| —
—| —| 800| —| S5| CDT900SB500T
—| 900| 900| —
1000| 1000| 1000| 500

EATON Cooper Power Series 600 A 25 kV Class T OP II Deadbreak Connector -
fig 8 Figure 3. Typical construction of the medium-voltage underground cable
Step 3. Select digit 10 and 11 (optional)
“TC” = T-OP II connector kit with a capacitive test point and protective cap
“C” = T-OP II connector kit with a protective cap (no capacitive test point)
Blank = T-OP II connector kit without capacitive test point or protective cap

Example

Select a T-OP II connector kit without a capacitive test point, with a protective cap for a 250 kcmil compressed cable with a nominal insulation diameter of 1.16 inches.
Step 1. Select digits 6 and 7
The nominal diameter over insulation is 1.160 ± 0.030 inches. Minimum diameter = 1.160 – 0.030 = 1.130 inches. Maximum diameter = 1.160 + 0.030 = 1.190 inches. From Table 3, identify the cable range that covers 1.130–1.190 inches and select the “EE” cable range code. Step
2. Select digits 8 and 9
The conductor size is 250 kcmil compressed. From Table 4, under the column “Concentric or compressed,” identify 250 kcmil and select the “17” conductor code.
Step 3. Select digit 10
A protective cap is needed. Use “C” for digit 10. The complete catalog number is: TP625EE17C.

Accessories

To order replacement parts and tools, refer to Table 6. To order replacement compression connectors, shear bolts, and cable adapters for a T-OP II Connector System, see section CA650007EN “Deadbreak Accessories, Tools and Replacement Parts.”
Table 6. Replacement parts

Description Catalog number
T-body without test point DT625
T-body with test point DT625T
Loadbreak-reducing tap plug (LRTP) LRTP625
Installation torque tool TQHD625
Operating and test tool OT625
Combination operating and test/torque tool OTTQ625
5/16-inch T-wrench TWRENCH
Copper alloy stud STUD-T
25 kV, 200 A insulated protective cap LPC225
5/16-inch Hex shaft with 3/8-inch socket drive tool HD625

Powering Business Worldwide
Eaton 1000 Eaton Boulevard
Cleveland, OH 44122 United States
Eaton.com
Eaton’s Power Systems Division 2300 Badger Drive
Waukesha, WI 53188 United States
Eaton.com/cooperpowerseries
© 2022 Eaton All Rights Reserved Printed in USA
Publication No. CA650059EN / Z26565 July 2022
Eaton is a registered trademark.
All other trademarks are property of their respective owners.

Documents / Resources

| EATON Cooper Power Series 600 A 25 kV Class T-OP II Deadbreak Connector [pdf] Instruction Manual