BEGA 24437K4 Wall Washer Light Instruction Manual

June 12, 2024
BEGA

BEGA logo Technical amendments reserved
Wall washer
24 437
Instruction Manual

24437K4 Wall Washer Light

BEGA 24437K4 Wall Washer Light

Instructions for use

Application
Wall washer with symmetrical light distribution for the illumination of façades and wall surfaces with the mounting surface being the reflection surface.
The luminaire can be installed with the light distribution opening upwards or downwards.

Product description

Luminaire made of aluminium alloy, aluminium and stainless steel
BEGA Unidure® coating technology
Clear safety glass
Reflector made of pure anodised aluminium 2 elongated fixing holes
Width 5.6 mm · 185 x 215 mm spacing 2 screw cable glands with strain relief for through-wiring power connecting cable ø 7–12 mm 1 screw cable gland closed at the factory with a dummy plug
Connecting terminal 2.5◽ with plug connection
Earth conductor connection
BEGA Ultimate Driver®
LED power supply unit
220-240 V ≂ 0/50-60 Hz
DC 176-264 V
DALI-controllable
Basic insulation is provided between the mains and control cables
BEGA Thermal Control®
Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
Safety class I
Protection class IP 65
Dust-tight and protection against water jets
Impact strength IK04
Protection against mechanical impacts < 0.5 joule
– Safety mark
****– Conformity mark
Weight: 3.8 kg
This product contains light sources of energy efficiency class(es) C

Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.

Safety

The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation.
If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Lamp

Module connected wattage 29.1 W
Luminaire connected wattage 32.5 W
Rated temperature ta = 25 °C
Ambient temperature ta max = 55 °C

24 437 K3

Module designation LED-1068/830
Colour temperature 3000 K
Colour rendering index CRI > 80
Module luminous flux 5640 lm
Luminaire luminous flux 4882 lm
Luminaire luminous efficiency 150,2 lm / W

24 437 K4

Module designation LED-1068/840
Colour temperature 4000 K
Colour rendering index CRI > 80
Module luminous flux 5800 lm
Luminaire luminous flux 5025 lm
Luminaire luminous efficiency 154,6 lm / W

Installation

LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during installation or relamping.
Undo hexagon socket head screws (wrench size 3 mm) through the opening in the luminaire housing up to the stop and lift luminaire top.
Lead the mains supply cable through the screw cable gland into the luminaire back housing.
Ensure correct directionality towards the area to be illuminated.
Fix luminaire base with enclosed or any other suitable fixing material onto the mounting surface.
The installed black gasket insert is intended for cables ø < 10 mm.
For cables ø 10-12 mm the enclosed grey gasket insert must be used.
In case of through-wiring replace the factory installed dummy plug with the enclosed corresponding gasket insert.BEGA 24437K4 Wall Washer Light - Thrust
screwAt the same time, use the enclosed synthetic cone-thrust collar between gasket insert and thrust screw (wrench size 22 mm) (see sketch).
Tighten screw cable gland.
Make the earth conductor connection and the electrical connection.
For digital control please use the connecting terminal DA, DA.
In case this terminal is not used the luminaire will be operated at full light output.
In order to guarantee the maximum service life of the electrical components, the enclosed desiccant pouch must be placed in the luminaire.
Remove the desiccant pouch from the foil packaging and place it in the position marked by the red information label immediately before finally closing the luminaire.
Push plug into coupler as far as it will go.
Make sure that gasket is positioned correctly.
Install the luminaire top, press-on and tighten screws evenly.

Cleaning · Maintenance

Clean luminaire regularly with solvent-free cleansers from dirt and deposits.
Do not use high pressure cleaners.

Replacing the LED module

The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.

Spares

Trim frame graphite with glass 25 000 033
Trim frame white with glass 25 000 034
Trim frame silver with glass 25 000 035
LED power supply unit DEV-0270/700i
LED module 3000 K LED-1068/830
LED module 4000 K LED-1068/840
Reflector 76 001 920
Gasket 83 001 983

BEGA Gantenbrink-Leuchten KG · Postfach 31 60
· 58689 Menden
· info@bega.com
· www.bega.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals