BEGA 50068.2 LED Wall Luminaire for Indoor Use Instruction Manual
- June 12, 2024
- BEGA
Table of Contents
BEGA 50068.2 LED Wall Luminaire for Indoor Use
Product Information
Safety| The installation and operation of this luminaire are subject to
national safety regulations. Installation and commissioning may
only be carried out by a qualified electrician. The manufacturer
accepts no liability for damage caused by improper use or
installation. If subsequent modifications are made to the
luminaire, the person responsible for these modifications shall be
considered the manufacturer.
---|---
Overvoltage protection| The electronic components installed in the luminaire
are
protected against overvoltage in accordance with DIN EN 61547. To
achieve an additional protection against e.g. transients, etc. we
recommend separate overvoltage protection components. You can find
them on our website at www.bega.com.
Replacement of the LED module| The designation of the LED module is noted on a
label in the
luminaire. The light colour and light output of BEGA replacement
modules correspond to those of the modules originally fitted. The
module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire. Please follow the
installation instructions for the LED module. Defective glass must
be replaced. Close the luminaire.
Product Usage Instructions
Modul-Anschlussleistung | 19.2 W |
---|---|
Leuchten-Anschlussleistung | 22.5 W |
Bemessungstemperatur | 25°C |
Umgebungstemperatur | 45°C |
Modul-Bezeichnung | 2x LED-0626/930 + 2x LED-0627/930 |
Farbtemperatur | 3000 K |
Farbwiedergabeindex | CRI > 90 |
Modul-Lichtstrom | 3210 lm |
Leuchten-Lichtstrom | 2286 lm |
Leuchten-Lichtausbeute | 101.6 lm/W |
Ersatzteile | Ersatzglas, LED-Netzteil, LED-Modul 3000 K, LED-Modul 3000 K, |
Dichtung Glas 2x
---|---
Spares| Spare glass, LED power supply unit, LED module 3000 K, LED
module 3000 K, Gasket glass 2x
Wall luminaire for indoor use
Instructions for use
Application
Free radiating wall luminaire · indoor luminaire with hand-blown three-ply
opal glass for a soft and uniform light distribution.
The elongated design of this wall luminaire particulary provides suitability
for installation on pillars, columns and for the front surface of walls, as
well as for recesses or profiles.
The luminaire may be installed horizontally or vertically.
Product Description
- Metal luminaire housing,finish Stainless steel
- Hand-blown opal glass
- The electrical equipment can be hinged 2 mounting holes ø 6 mm
- Distance apart 300 mm
- Jointing sleeve with cable entry for mains supply cable up to ø 14 mm, max. 5 x 1.5@
- Connecting terminals 2.5@
- Earth conductor terminal
- LED power supply unit 220-240 V x 0/50-60 Hz
- DC 176-276 V
- During DC operation the LED power is reduced to 15 %
- DALI-controllable
- Basic insulation is provided between the mains and control cables
- BEGA Thermal Control®
- Temporary thermal regulation to protect temperature-sensitive components without switching off the luminaire
- Safety class I
- Protection class IP 65
- Dust-tight and protection against water jets Impact strength IK03
- Protection against mechanical impacts < 0.35 joule
- – Safety mark
- – Conformity mark
- Weight: 3.0 kg
This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations. Installation and commissioning may only be carried out by
a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation. If subsequent modifications are made to the luminaire, the
person responsible for these modifications shall be considered the
manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.
Installation
- LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
- Undo hexagon socket (wrench size 5) in the locking cap and remove it.
- The opal glass can now be hinged together with the electrical equipment to the front. Remove opal glass.
- Note position of application of the luminaire arrow down«.
- Drill mounting holes into the mounting surface
- spacing 300 mm and turn in enclosed or suitable fixing screws.
- For the electrical connection undo the screw connection at the line connector and remove terminal block.
- Make earth conductor connection and electrical connection.
- Make connection of the phase with the L marked, the neutral wire at the N marked and earth conductor at the PE marked connecting terminal.
- For digital actuation please use the two connecting terminals DA. If these terminals are not assigned, the luminaire will work with full light output.
- Bolt together both screw cable glands firmly. Hook luminaire into the fixing screws and tighten.
- Slide opal glass over the lamp and fasten with the locking cap.
- Make sure that the gaskets are positioned correctly.
Lamp
- Module connected wattage 19.2 W
- Luminaire connected wattage 22.5 W
- Rated temperature ta = 25 °C
- Ambient temperature ta max = 45 °C
50 068.2 K3
- Module designation
- 2x LED-0626/930 + 2x LED-0627/930
- Colour temperature 3000 K
- Colour rendering index CRI > 90
- Module luminous flux 3210 lm
- Luminaire luminous flux 2286 lm
- Luminaire luminous efficiency 101,6 lm / W
Cleaning · Maintenance
- Clean luminaire regularly with solvent-free cleansers from dirt.
- Defective glass must be replaced.
Replacement of the LED module
- The designation of the LED module is noted on a label in the luminaire.
- The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
- The module can be replaced by qualified persons using standard tools.
- Disconnect the system and open the luminaire.
- Please follow the installation instructions for the LED module.
- Defective glass must be replaced.
- Close the luminaire.
Spares
- Spare glass 11 002 763 .1R G
- LED power supply unit DEV-0158/700i
- LED module 3000 K LED-0627/930
- LED module 3000 K LED-0626/930
- Gasket glass 2x 83 000 788
BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com