BEGA 50069.3 Wall luminaire For Indoors Instruction Manual
- June 12, 2024
- BEGA
Table of Contents
BEGA 50069.3 Wall luminaire For Indoors Instruction Manual
Wall luminaire for indoor use
Instructions for use
Application
Free radiating wall luminaire · indoor luminaire with hand-blown three-ply
opal glass for a soft and uniform light distribution. The elongated design of
this wall luminaire particulary provides suitability for installation on
pillars, columns and for the front surface of walls, as well as for recesses
or profiles. The luminaire may be installed horizontally or vertically Product
description Metal luminaire housing, finish Chrome Hand-blown opal glass The
electrical equipment can be hinged 2 mounting holes ø 6mm Distance apart 400mm
Jointing sleeve withcable entry for mains supply cable up toø 14 mm, max. 5 x
1.5@ Connecting terminals 2.5@ Earth conductor terminal LED power supply unit
220-240 V x 0/50-60 Hz DC 176-276 V During DC operation the LED power is
reduced to 15% DALI-controllable Basic insulation is provided between the
mains and control cables BEGA Thermal Control® Temporary thermal regulation to
protect temperature-sensitive components without switching off the luminaire
Safety class I Protection class IP 65 Dust-tight and protection against water
jets Impact strength IK04 Protection against mechanical impacts < 0.5 joule
Safety mark
Conformity mark
Weight: 3.3 kg
This product contains light sources of energy efficiency class(es) D
Safety
The installation and operation of this luminaire are subject to national
safety regulations. Installation and commissioning may only be carried out by
a qualified electrician. The manufacturer accepts no liability for damage
caused by improper use or installation. If subsequent modifications are made
to the luminaire, the person responsible for these modifications shall be
considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547. To achieve an additional
protection against e.g. transients, etc. we recommend separate overvoltage
protection components. You can find them on our website at
www.bega.com.
Lamp
Module connected wattage 23.2 W
Luminaire connected wattage 27 W
Rated temperature ta=25 °C
Ambient temperature ta max=45 °C
50 069.3K3
Module designation 4x LED-0627/930
Colour temperature 3000 K
Colour rendering index CRI > 90
Module luminous flux 3860 lm
Luminaire luminous flux 2840 lm
Luminaire luminous efficiency 105,2 lm/W
Installation
LED are high-quality electronic components! Please avoid touching the light
output opening of the LED directly during installation or relamping. Undo
hexagon socket (wrench size 5) in the locking cap and remove it. The opal
glass can now be hinged together with the electrical equipment to the front.
Remove opal glass. Note position of application of the luminaire »arrow down«.
Drill mounting holes into the mounting surface – spacing 400 mm and turn in
enclosed or suitable fixing screws. For the electrical connection undo the
screw connection at the line connector and remove terminal block. Make earth
conductor connection and electrical connection. Make connection of the phase
with the Lmarked, the neutral wire at the N marked and earth conductor at the
PE marked connecting terminal. For digital actuation please use the two
connecting terminals DA. If these terminals are not assigned, the luminaire
will work with full light output. Bolt together both screw cable glands
firmly. Hook luminaire into the fixing screws and tighten.
Side opal glass over the lamp and fasten with the locking cap. Make sure that the gaskets are positioned correctly.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt. Defective glass must be replaced.
Replacement of the LED module
The designation of the LED module is noted on a label in the luminaire. The
light colour and light output of BEGA replacement modules correspond to those
of the modules originally fitted. The module can be replaced by qualified
persons using standard tools. Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module. Defective
glass must be replaced. Close the luminaire.
Spares
Spare glass 11 002 764 .1RG
LED power supply unit DEV-0158/700i
LED module 3000 K LED-0627/930
Gasket glass 2x 83 000 788
BEGA Gantenbrink-Leuchten KG · Postfach 3160 · 58689 Menden ·
info@bega.com
www.bega.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>