velleman VTTEST23 Wall Socket Voltage and Earth Tester User Manual

August 2, 2024
Velleman

velleman VTTEST23 Wall Socket Voltage and Earth Tester

USER MANUAL

MODEL: VTTEST23

1. Introduction

To all residents of the European Union

Important environmental information about this product

This symbol on the device or the package indicates that disposal of the device after its lifecycle could harm the environment. Do not dispose of the unit (or batteries) as unsorted municipal waste; it should be taken to a specialized company for recycling. This device should be returned to your distributor or to a local recycling service. Respect the local environmental rules.

If in doubt, contact your local waste disposal authorities.

Thank you for choosing Velleman! Please read the manual thoroughly before bringing this device into service. If the device was damaged in transit, do not install or use it and contact your dealer.

2. Symbols

| AC (Alternating Current)
---|---
| Caution: risk of danger, the manual must be consulted in all cases where this symbol is marked.
Warning: a hazardous condition or action that may result in injury or death
Caution: condition or action that may result in damage to the meter or equipment under test
| Earth

3. General Guidelines

Refer to the Velleman® Service and Quality Warranty on the last pages of this manual.

| This symbol indicates: Read instructions
Not reading the instructions and manual can lead to damage, injury or death.
---|---
| This symbol indicates: Danger
A hazardous condition or action that may result in injury or death.
| This symbol indicates: Risk of danger/damage

| Risk of a hazardous condition or action that may result in damage, injury or death.
---|---
| This symbol indicates: Attention; important information Ignoring this information can lead to hazardous situations.
| WARNING: To avoid electrical shock always disconnect the test leads prior to opening the housing. To prevent fire hazards, only use fuses with the same ratings as specified in this manual. Remark: refer to the warning on the battery compartment.
| Avoid cold, heat and large temperature fluctuations. When the unit is moved from a cold to a warm location, leave it switched off until it has reached room temperature. This to avoid condensation and measuring errors.
| Protect this device from shocks and abuse. Avoid brute force when operating.
| Pollution degree 2-device. For indoor use only. Keep this device away from rain, moisture, splashing and dripping liquids. Not for industrial use. Refer to §8 Pollution degree.
| Keep the device away from children and unauthorised users.
| Risk of electric shock during operation. Be very careful when measuring live circuits.
| There are no user-serviceable parts inside the device.  Refer to an authorized dealer for service and/or spare parts.
| This is an installation category CAT II measuring instrument. Refer to §7 Overvoltage/installation category.
| Read this addendum and the manual thoroughly. Familiarise yourself with the functions of the device before actually using it.
IP30| Representing the level of protection from specified external conditions.
3: Protection against contact with a tool. Touch-protected only for measuring devices. Protected against penetration of solid objects larger than 2.5 mm.
0: No protection against moisture or water
| All modifications of the device are forbidden for safety reasons. Damage caused by user modifications to the device is not covered by the warranty.
| Only use the device for its intended purpose. Using the device in an unauthorized way will void the warranty. Damage caused by disregard of certain guidelines in this manual is not covered by the warranty and the dealer will not accept responsibility for any ensuing defects or problems.

4. Maintenance

There are no user-serviceable parts inside the device. Refer to an authorized dealer for service and/or spare parts.

Do not apply abrasives or solvents to the meter. Use a damp cloth and mild detergent for cleaning purposes.

5. During Use

Risk of electric shock during operation. Be very careful when measuring live circuits.

  • Read, understand and follow the Safety Rules and operating instructions in this manual before using this instrument.
  • The Voltage Tester is designed to be used by the skilled persons and in accordance with safe methods of work.
  • If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
  • Unauthorized persons are not to be allowed to disassemble the tester.
  •  Keep fingers away from the metal probe tips when taking measurements.
  • Comply with all safety codes. Use approved personal protective equipment when working near live electrical circuits.
  • Use caution on live circuits. Voltages above 30V AC RMS, 42V AC peak, or 60V DC pose a shock hazard.
  • Do not use the tester in wet or damp environments or during electrical storms.
  • Do not use the tester near explosive vapors, dust or gasses.
  • Do not use the tester if it operates incorrectly. Protection may be compromised.
  • Do not apply voltage that exceeds the tester’s maximum rated input limits.
  • Never use the meter with CAT II installations when measuring voltages that might exceed the safety margin of 230 V above earth ground.
  • The unit is only intended to be used for short periods, typically less than 2 minutes, and must not be left plugged in for extended periods.
  • Vent slots should not be covered or obstructed.
  • The unit is intended for use in the vertical orientation only.
  • The unit must always be checked for any sign of damage prior to use. lf there are visual signs of damage do not use. Return the unit to provider for analysis. Visual signs of damage include checking the case exterior, pins and label. lf any are damaged DO NOT USE.
  • To verify the tester is working correctly, always first plug it into a known good socket prior to use.
  • lf the unit has suffered a mechanica! shock such as a drop, have it checked out by provider first.
  • The product has no user serviceable parts.
  • The product is designed to comply with EN 61010 and is rated to IP30.
  • The product will not detect reverse earth neutral.
  • The Socket Tester is intended as a first level fault indication tool and only checks for correct polarity.

6. Overvoltage/Installation Category

Voltage testers are categorized depending on the risk and severity of transient overvoltage that might occur at the point of test. Transients are short-lived bursts of energy induced in a system, e.g. caused by lightning strike on a power line.

The existing categories according EN 61010-1 are:

CAT I| A CAT I-rated meter is suitable for measurements on protected electronic circuits that are not directly connected to mains power, e.g. electronics circuits, control signals…
---|---
CAT II| A CAT II-rated meter is suitable for measurements in CAT I-environments and mono-phase appliances that are connected to the mains by means of a plug and circuits in a normal domestic environment, provided that the circuit is at least 10 m apart from a CAT III- or 20 m apart from a CAT IV-environment. E.g. household appliances, portable tools…
CAT III| A CAT III-rated meter is suitable for measurements in CAT I- and CAT II-environments, as well as for measurements on (fixed) mono- or poly-phased appliances which are at least 10 m apart from of a
CAT IV| CAT IV-environment, and for measurements in or on distribution level equipment (fuse boxes, lighting circuits, electric ovens).
CAT IV| A CAT IV-rated meter is suitable for measuring in CAT I-, CAT II- and CAT III-environments as well as on the primary supply level. Note that for all measurements on equipment for which the supply cables run outdoors (either overhead or underground) a CAT IV meter must be used.

Warning:

This device was designed in accordance with EN 61010-1 installation category CAT II 230 V. This implies that certain restrictions in use apply that are related to voltages and voltage peaks which can occur within the environment of use. Refer to the table above.

This device is only suitable for measurements up to 230 V in CAT II

7. Pollution Degree

IEC 61010-1 specifies different types of pollution environments, for which different protective measures are necessary to ensure safety. Harsher environments require more protection, and the protection against the pollution which is to be found in a certain environment depends mainly on the insulation and the enclosure properties. The pollution degree rating of the DVM indicates in which environment the device may be used.

Pollution degree 1| No pollution or only dry, nonconductive pollution occurs. The pollution has no influence. (only to be found in hermetically sealed enclosures)
---|---
Pollution degree 2| Only nonconductive pollution occurs. Occasionally, temporary conductivity caused by condensation is to be expected. (home and office environments fall under this category)
Pollution degree 3| Conductive pollution occurs, or dry nonconductive pollution occurs that becomes conductive due to condensation that is to be expected.
(industrial environments and environments exposed to outside air – but not in contact with precipitation)
Pollution degree 4| The pollution generates persistent conductivity caused by conductive dust or by rain or snow. (exposed outdoor environments and environments where high humidity levels or high concentrations of fine particles occur)

Warning : This device was designed in accordance with EN 61010-1 pollution degree 2. This implies that certain restrictions in use apply that are related to pollution which can occur within the environment of use. Refer to the table above.

This device is only suitable for measurements in Pollution degree class 2 environments.

8. Specifications

This device is not calibrated when purchased!

Regulations concerning environment of use:
Use this meter only for measurements in CAT I, CAT II and CAT III environments (see §7).
Use this meter only in a pollution degree 2 environment (see §8).

AC voltage measurements 230 V – 50Hz – 11mA
Safety standard EN 61010
Safety rating CAT II / 230 V
Voltage tester type AC
Alarm sound type Buzzer, Optical
IP rating IP30
Number of poles 3
Mains plug type Type F (Germany – Schuko)
Altitude Max. 2000m
Temperature Max. 40°C
Mains supply voltage fluctuations ± 10%
Weight unit 60 g
Height unit 68 mm
Width unit 60 mm
Depth unit 56 mm
Humidity <80% relative humidity
Operating Temperature 0°C to 40°C
Storage Temperature -10°C to 50°C
Altitude < 2000m, indoor use only

9. Operation

Performing Tests and Measurements

The socket voltage tester is designed to assist users in determining the presence and level of electrical voltage in standard wall outlets and sockets.

This essential tool is intended for both professional electricians and homeowners to ensure the safety and functionality of electrical circuits and outlets.

With this socket tester you can check whether sockets, cable reels and extension cords are connected correctly. It detects whether the socket is connected with the correct polarity and shows wiring errors.

Warning:

This device only works on Live (L1) and Neutral (N) networks (TN network):

  • 230V between L1 and N connection. N connection is almost 0V

This device doesn’t work on Live (L1) and Live (L2) (IT network):

  • 230V between L1 and L2 connection. L1 and L2 gives 115V between Earth and L1 or L2

Visual Indicators:

The tool is equipped with a series of LED lights. The socket tester will light up GREEN, GREEN, OFF and the buzzer is continuously on for correct polarity. Any other combination indicates a fault.

Fault Combinations Chart:

  • N: Neutral
  • L: Live
  • E: Earth
Plug pins Status Display Result Buzzer Result
N E L LED1
N E L Correct GREEN
E N L E/N Swap GREEN
E L N LN
reverse OFF GREEN RED PULSE
L E N LN
reverse GREEN OFF RED PULSE
L N E LE
reverse GREEN OFF RED PULSE
X E L Missing N OFF
X L E Missing N OFF
X N L Missing N OFF
X L N Missing
N OFF GREEN OFF PULSE
N X L Missing Earth GREEN
L X N Missing Earth GREEN
E X L Missing
Earth GREEN OFF OFF PULSE
L X E Missing Earth GREEN
E L X L Fault GREEN
L E X L Fault GREEN
N L X L Fault GREEN
L N X L Fault GREEN
N L E LE
reverse OFF GREEN RED PULSE

X = No connection
Use this device with original accessories only. Velleman group nv cannot be held responsible in the event of damage or injury resulting from (incorrect) use of this device. For more info concerning this product and the latest version of this manual, please visit our website www.velleman.eu. The information in this manual is subject to change without prior notice.

© COPYRIGHT NOTICE

The copyright to this manual is owned by Velleman Group nv. All worldwide rights reserved. No part of this manual may be copied, reproduced, translated or reduced to any electronic medium or otherwise without the prior written consent of the copyright holder.

Specifications

  • Model: VTTEST23

  • Input Voltage: 230V

  • IP Rating: IP30

Frequently Asked Questions (FAQ)

Q: Can I modify the device for my specific needs?

A: No, all modifications are forbidden for safety reasons, and any damage resulting from user modifications is not covered by the warranty.

Q: How should I clean the device?

A: Use a damp cloth with mild detergent; do not use abrasives or solvents on the meter.

Q: What should I do if there is a risk of electric shock during

operation?

A: Always be careful when measuring live circuits and follow all safety guidelines provided in the manual.