Altronix AL175ULB Access Control Power Supply Instructions
- June 4, 2024
- Altronix
Table of Contents
- Altronix AL175ULB Access Control Power Supply Instructions
- Specifications:
- Power Supply Output Specifications:
- Stand-by Specifications:
- LED Diagnostics:
- Terminal Identification
- Maintenance:
- Typical Application Diagrams:
- Typical Application Diagrams
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Altronix AL175ULB Access Control Power Supply Instructions
AL175ULB
Access Control Power Supply/Charger
Overview:
AL175ULB is a power-limited power supply/charger that converts a 24VAC input into two (2) individual PTC pro-tected auto-resettable 12VDC or 24VDC outputs (see specifications). They are intended for use in applications re-quiring UL Listing for Access Control (UL 294) and applications requiring an interface with Fire Alarm Control Panels.
Specifications:
Agency Listings
-
UL Recognized component for Access Control Systems (UL 294).
Input: -
Input 24VAC, 40VA. Class 2 transformer.
-
Fire Alarm Panel or Access Control trigger input.
Output : -
12VDC or 24VDC selectable outputs.
-
12VDC @ 1.75A or 24VDC @ 0.9A supply current.
-
Two (2) Class 2 Rated power-limited outputs.
- Fail-Safe/Fail-Secure lock output (switched).
- Auxiliary power output (unswitched).
-
PTC protected outputs, rated @ 2.5A.
-
Filtered and electronically regulated output.
-
Short circuit and thermal overload protection
Battery Backup :
- Built-in charger for sealed lead acid or
gel type batteries.
• Automatic switch over to stand-by battery when
AC fails.
• Maximum charge current 0.4A.
Supervision:
- AC fail supervision (form “C” contacts).
- Supervised Fire Alarm Disconnect
(Latching w/reset or Non-Latching).
Visual Indicators:
- AC input and DC output LED indicators.
Board Dimensions
- (W x L x H approximate):3.1” x 5.8” x 1.5” (78.7mm x 147.3mm x 38.1mm).
Power Supply Output Specifications:
Output VDC| Switch Position| Max. Stand-by Load DC| Max. Alarm Load DC|
Battery (optional)
---|---|---|---|---
12VDC| SW1 OFF| 1.75A| 1.75A| 12VDC
24VDC| SW1 ON| 0.9A| 0.9A| 24VDC
Stand-by Specifications:
Output | 4 hr. of Stand-by & 5 Minutes of Alarm |
---|---|
12VDC / 7AH Battery | Stand-by = 1.25A Alarm = 1.25A |
24VDC / 7AH Battery
Installation Instructions:
AL175ULB should be installed in accordance with article 760 of The National
Electrical Code or NFPA 72 as well as all applicable Local Codes.
See Terminal Identification Chart on page 3 for a description of each terminal
function.
-
Mount AL175ULB in the desired location/enclosure (mounting hardware included).
-
Connect 28VAC, 56VA transformer to the terminals marked [AC AC]. Use 18 AWG or larger for all power connections (Battery, DC output). Use 22 AWG to 18 AWG for power-limited circuits (trigger inputs, dry outputs). Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input,
Battery Wires). Minimum 0.25” spacing must be provided. -
Set the AL175ULB to the desired DC output voltage by setting switch SW1 to the appropriate position (see Power Supply Output Specification Chart, pg. 1).
-
Measure output voltage before connecting devices. This helps avoiding potential damage.
-
Connect battery to the terminals marked [+ BAT -] on the unit (battery leads included).
Use two (2) 12VDC batteries connected in series for 24VDC operation.
Note: For Access Control applications batteries are optional.
When batteries are not used, a loss of AC will result in the loss of output voltage.
When the use of stand-by batteries is desired, they must be lead acid or gel type. -
Connect appropriate signaling notification devices to AC Fail supervisory relay outputs.
Note: To meet UL requirements, AC Supervisory outputs must be connected to the zone of Alarm Control Panel or to visual AC trouble indicator. -
For Access Control Device & Fire Alarm Interface connections see Application Diagrams, pg. 3 – 4. and Terminal Identification Chart, pg. 2.
LED Diagnostics:
Red (DC) | Green (AC) | Power Supply Status |
---|---|---|
ON | ON | Normal operating condition. |
ON | OFF | Battery backup is powering output. |
OFF | ON | No DC output. |
OFF | OFF | Loss of AC. Discharged or missing stand-by battery. No DC output. |
Terminal Identification
Terminal Legend | Function/Description |
---|---|
AC | Low voltage AC input. |
TRG1 & TRG2
| These input terminals are designed to connect to the normally closed outputs
of an access control or fire alarm relay. These terminals control [LOCK+], and
[STRIKE+], as well as AL175ULB output relay contacts [N.C., N.O., C]
LOCK +| This terminal provides DC output voltage when [TRG1] and [TRG2] are
shorted together and are typically used to power Mag Locks.
STRIKE+| This terminal provides DC output voltage when [TRG1] and [TRG2] are
unshorted and are typically used to power Electric Strikes.
N.C., N.O., C
| Isolated dry Form “C” contacts. Shorting [TRG1] and [TRG2] together causes these
contacts to switch. They are typically used for controlling multiple AL175ULBs with fire alarm tie-in ( Fig. 4, pg. 3 and Fig. 5, pg. 4 ).
AUX+| Continuous positive (+) DC power output voltage. It is not affected by
TRG1, TRG2 operation.
COM —| Common negative (-) output (ground).
FACP| Spare wiring terminal used for fire alarm tie-in application ( Fig. 3,
pg. 3 ).
+BAT —| Stand-by battery connections.
AC Fail
N.C., C, N.O.
| Used to notify loss of AC e.g connect audible device or alarm panel relay normally energized when AC power is present. Contact rating 1A @ 28VDC.
Maintenance:
Unit should be tested at least once a year for the proper operation as
follows:
Output Voltage Test : Under normal load conditions the DC output voltage
should be checked for proper
voltage leve l (Power Supply Output Specifications Chart).
Battery Test : Under normal load conditions check that the battery is
fully charged, check specified
voltage both at the battery terminal and at the board terminals marked [+ BAT
-] to ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharge is 400mA.
Note: Expected battery life is 5 years; however, it is recommended changing
batteries in 4 years or less if needed.
Typical Application Diagrams:
Fig. 2
Typical single mag lock or door strike installation with fire alarm tie-in
using trigger controlled output.
Fig. 3
Typical dual mag lock installation with fire alarm tie-in using trigger
controlled outputs:
Fig. 4 – Typical mag lock with fire alarm tie-in using aux output installation:
Typical Application Diagrams
Fig. 5 – Latching fire alarm tie-in with manual reset:
Fig. 6 – Multiple AL175ULB power supply connections:
Altronix is not responsible for any typographical errors. 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty IIAL175ULB – Rev. 081601 F29U
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>