HYTRONIK HBIR29/SV PIR Standalone Motion Sensor with Bluetooth Mesh Instruction Manual

June 12, 2024
HYTRONIK

HYTRONIK - logo

Installation and Instruction Manual
PIR Standalone Motion Sensor with Mesh
One DALI Channel Output

HBIR29/SV HBIR29/SV/R
HBIR29/SV/H HBIR29/SV/RH

Technical Specifications

Operation frequency 2.4 GHz – 2.483 GHz
Transmission power 4 dBm
Range (Typical indoor) 10~30m
Protocol Mesh
Operating voltage 220~240VAC 50/60Hz
Stand-by power <0.65W (Empty load)
Switched power Max. 40 devices, 80mA
Warming-up 5s
Sensor principle PIR detection
Detection range (Max.)* HBIR29/SV Installation Height : 6m Detection Range

(Ø) :9m
Detection range (Max.)
HBIR29/SV/R| Installation Height : 6m
Detection Range (Ø) :10m
Detection range (Max.)
HBIR29/SV/H| Installation height:15m (forklift) 12m (person) Detection range (Ø):24m
Detection range (Max.)* HBIR29/SV/RH| Installation height:20m (forklift) 12m (person) Detection range (Ø):40m
Detection angle| 360O
Operation temperature| Ta:-20OC~+50OC
IP rating| IP20
Standard compliance| EN300328, EN301489-1, EN301489-17, EN62479, EN55015, EN61547, EN60669-1, EN60669-2-1, EN62493
Certification| CB, CE , EMC, RED, RCM

Download the App

The access to Silvair apps mobile app: Silvair on the App Store web app: platform.silvair.com

Installation

Mechanical Structure & DimensionsHYTRONIK HBIR29 SV PIR Standalone Motion
Sensor with Bluetooth Mesh - Dimensions

  1. Ceiling (drill hole φ66~68mm)
  2. Carefully prise off the cable clamps.
  3. Make connections to the pluggable terminal blocks.
  4. Insert plug connectors and secure using the provided cable clamps, then clip terminal covers to the base.
  5. Fit detection blind (if required) and desired lens.
  6. Clip fascia to body.
  7. Bend back springs and insert into ceiling.

HYTRONIK HBIR29 SV PIR Standalone Motion Sensor with Bluetooth Mesh - Wire
Preparation

Mesh Factory Reset

The device HBIR29/SV can be reset by placing a strong magnet (e.g. N38 neodymium magnet, d=10mm*h=4mm) near the sensor lens for 5 seconds. Once the factory reset is done successfully, the luminaire flashes and then permanent on, then the device is being able to be re-commissioned by SILVAIR app.

To Reprovision

Place a strong magnet on the site of the Reset/Hall effect sensor (see diagram 4 below). To trigger the reset the magnet must be held in position for 5 seconds.![HYTRONIK HBIR29 SV PIR Standalone Motion Sensor with Bluetooth Mesh

Note: When change the lens part of HBIR29/SV, please kindly make sure that the lens fits the right location, where the “Reset dot” and “BLE dot”matches with the physical location on the PCB.

Status LED blinking Sequence

HBIR29/SV Unprovisioned| 30ms ON| 300ms OFF
HBIR29/SV Provisioned| 15ms ON| 2,000ms OFF
Factory reset| 500ms ON| 1,000ms OFF
Factory reset (initial burst)| 100ms ON| 1,000ms OFF
MESH package received| 30ms ON| 50ms OFF
Attention (from network)| 500ms ON| 500ms OFF

Detection Pattern & Optional Accessories

HBIR29/SV (Low-bay)
HBIR29/SV: Low-bay flat lens detection pattern for single person @ Ta = 20ºC (Recommended ceiling mount installation height 2.5m-6m)

Mount height Tangential (A) Radial (B)
2.5m max 50m2 (∅= 8m) max 13m2 (∅= 4m)
3m max 64m2 (∅= 9m) max 13m2 (∅= 4m)
4m max 38m2 (∅= 7m) max 13m2 (∅= 4m)
5m max 38m2 (∅= 7m) max 13m2 (∅= 4m)
6m max 38m2 (∅= 7m) max 13m2 (∅= 4m)

Optional Accessory — Ceiling/Surface Mount Box: HA03

HYTRONIK HBIR29 SV PIR Standalone Motion Sensor with Bluetooth Mesh - Mount
Box

Optional Accessory — Blind Insert for Blocking Certain Detection Angles

HYTRONIK HBIR29 SV PIR Standalone Motion Sensor with Bluetooth Mesh - Mount
Box1

HBIR29/SV/R (Reinforced Low-bay)
HBIR29/SV/R: Low-bay convex lens detection pattern for single person @ Ta = 20ºC (Recommended ceiling mount installation height 2.5m-6m)

Mount height Tangential (A) Radial (B)
2.5m max 79m2 (∅ = 10rn) max 20m2 (∅ = 5m)
3m max 79m2 (∅ = 10rn) max 20m2 (∅ = 5m)
4m max 64m2 (∅ = 9m) max 20m2 (∅ = 5m)
5m max 50m2 (∅ = 8m) max 20m2 (∅ = 5m)
6m max 50m2 (∅ = 8m) max 20m2 (∅ = 5m)

Optional Accessory — Ceiling/Surface Mount Box: HA03

HYTRONIK HBIR29 SV PIR Standalone Motion Sensor with Bluetooth Mesh - Mount
Box2

Optional Accessory — Blind Insert for Blocking Certain Detection Angles![HYTRONIK HBIR29 SV PIR Standalone Motion Sensor with Bluetooth Mesh

HBIR29/SV/H (High-bay)

HBIR29/SV/H: High-bay lens detection pattern for forklift @ Ta = 20ºC (Recommended ceiling mount installation height 10m-15m )

Mount height Tangential (A) Radial (B)
10m max 380m2 (Ø = 22m) max 201m2 (Ø = 16m)
11m max 452m2 (Ø = 24m) max 201m2 (Ø = 16m)
12m max 452m2 (Ø = 24m) max 201m2 (Ø = 16m)
13m max 452m2 (Ø = 24m) max 177m2 (Ø = 15m)
14m max 452m2 (Ø = 24m) max 133m2 (Ø = 13m)
15m max 452m2 (Ø = 24m) max 113m2 (Ø = 12m)

HBIR29/SV/H : High-bay lens detection pattern for single person @ Ta = 20ºC (Recommended ceiling mount installation height 2.5m-12m )

Mount height Tangential (A) Radial (B)
2.5m max 50m2 (Ø = 8m) max 7m2 (Ø = 3m)
6m max 104m2 (Ø = 11.5m) max 7m2 (Ø = 3m)
8m max 154m2 (Ø = 14m) max 7m2 (Ø = 3m)
10m max 227m2 (Ø = 17m) max 7m2 (Ø = 3m)
11m max 269m2 (Ø = 18.5m) max 7m² (Ø = 3m)
12m max 314m2 (Ø = 20m) max 7m² (Ø = 3m)

Optional Accessory — Ceiling/Surface Mount Box: HA03

HYTRONIK HBIR29 SV PIR Standalone Motion Sensor with Bluetooth Mesh -
Ceiling

Optional Accessory — Blind Insert for Blocking Certain Detection Angles![HYTRONIK HBIR29 SV PIR Standalone Motion Sensor with Bluetooth Mesh

HBIR29/SV/RH (Reinforced High-bay with 3-Pyro)

HBIR29/SV/RH: Reinforced high-bay lens detection pattern for forklift @ Ta = 20ºC (Recommended ceiling mount installation height 10m-15m)

Mount height Tangential (A) Radial (B)
10m max 346m2 (Ø = 21m) max 177m2 (Ø = 15m)
11m max 660m2 (Ø = 29m) max 177m2 (Ø = 15m)
12m max 907m2 (Ø = 34m) max 154m2 (Ø = 14m)
13m max 962m2 (Ø = 35m) max 154m2 (Ø = 14m)
14m max 1075m2 (Ø = 37m) max 113m2 (Ø = 12m)
15m max 1256m2 (Ø = 40m) max 113m2 (Ø = 12m)
20m max 707m2 (Ø = 30m) max 113m2 (Ø = 12m)

HBIR29/SV/RH : Reinforced high-bay lens detection pattern for single person @ Ta = 20OC (Recommended ceiling mount installation height 2.5m- 12m )

Mount height Tangential (A) Radial (B)
2.5m max 38m2 (Ø = 7m) max 7m2 (Ø = 3m)
6m max 154m2 (Ø = 14m) max 7m2 (Ø = 3m)
8m max 314m2 (Ø = 20m) max 7m2 (Ø = 3m)
10m max 531m2 (Ø = 26m) max 13m2 (Ø = 4m)
11m max 615m2 (Ø = 28m) max 13m2 (Ø = 4m)
12m max 707m2 (Ø = 30m) max 13m2 (Ø = 4m)

Optional Accessory — Ceiling/Surface Mount Box: HA03HYTRONIK HBIR29 SV PIR
Standalone Motion Sensor with Bluetooth Mesh - Tangential
3

Additional Information / Documents

  1. Regarding precautions for PIR Sensors installation and operation, please kindly refer to www.hytronik.com/download ->knowledge ->PIR Sensors – Precautions for Product Installation and Operation
  2. Data sheet is subject to change without notice. Please always refer to the most recent release on www.hytronik.com/products/bluetooth technology ->Partnership
  3. Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download ->knowledge ->Hytronik Standard Guarantee Policy

HYTRONIK - logo

WWW.HYTRONIK.COM
Subject to change without notice.
HBIR29/SV-20201012-A0

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

HYTRONIK User Manuals

Related Manuals