HYTRONIK HBIR29/SV PIR Standalone Motion Sensor with Bluetooth Mesh Instruction Manual
- June 12, 2024
- HYTRONIK
Table of Contents
Installation and Instruction Manual
PIR Standalone Motion Sensor with Mesh
One DALI Channel Output
HBIR29/SV HBIR29/SV/R
HBIR29/SV/H HBIR29/SV/RH
Technical Specifications
Operation frequency | 2.4 GHz – 2.483 GHz |
---|---|
Transmission power | 4 dBm |
Range (Typical indoor) | 10~30m |
Protocol | Mesh |
Operating voltage | 220~240VAC 50/60Hz |
Stand-by power | <0.65W (Empty load) |
Switched power | Max. 40 devices, 80mA |
Warming-up | 5s |
Sensor principle | PIR detection |
Detection range (Max.)* HBIR29/SV | Installation Height : 6m Detection Range |
(Ø) :9m
Detection range (Max.)
HBIR29/SV/R| Installation Height : 6m
Detection Range (Ø) :10m
Detection range (Max.) HBIR29/SV/H| Installation height:15m (forklift) 12m
(person) Detection range (Ø):24m
Detection range (Max.)* HBIR29/SV/RH| Installation height:20m (forklift) 12m
(person) Detection range (Ø):40m
Detection angle| 360O
Operation temperature| Ta:-20OC~+50OC
IP rating| IP20
Standard compliance| EN300328, EN301489-1, EN301489-17, EN62479, EN55015,
EN61547, EN60669-1, EN60669-2-1, EN62493
Certification| CB, CE , EMC, RED, RCM
Download the App
The access to Silvair apps mobile app: Silvair on the App Store web app: platform.silvair.com
Installation
Mechanical Structure & Dimensions
- Ceiling (drill hole φ66~68mm)
- Carefully prise off the cable clamps.
- Make connections to the pluggable terminal blocks.
- Insert plug connectors and secure using the provided cable clamps, then clip terminal covers to the base.
- Fit detection blind (if required) and desired lens.
- Clip fascia to body.
- Bend back springs and insert into ceiling.
Mesh Factory Reset
The device HBIR29/SV can be reset by placing a strong magnet (e.g. N38 neodymium magnet, d=10mm*h=4mm) near the sensor lens for 5 seconds. Once the factory reset is done successfully, the luminaire flashes and then permanent on, then the device is being able to be re-commissioned by SILVAIR app.
To Reprovision
Place a strong magnet on the site of the Reset/Hall effect sensor (see diagram 4 below). To trigger the reset the magnet must be held in position for 5 seconds.![HYTRONIK HBIR29 SV PIR Standalone Motion Sensor with Bluetooth Mesh
- Reprovision](https://manuals.plus/wp-content/uploads/2023/07/HYTRONIK-HBIR29 -SV-PIR-Standalone-Motion-Sensor-with-Bluetooth-Mesh-Reprovision.png)
Note: When change the lens part of HBIR29/SV, please kindly make sure that the lens fits the right location, where the “Reset dot” and “BLE dot”matches with the physical location on the PCB.
Status LED blinking Sequence
HBIR29/SV Unprovisioned| 30ms ON| 300ms OFF
HBIR29/SV Provisioned| 15ms ON| 2,000ms OFF
Factory reset| 500ms ON| 1,000ms OFF
Factory reset (initial burst)| 100ms ON| 1,000ms OFF
MESH package received| 30ms ON| 50ms OFF
Attention (from network)| 500ms ON| 500ms OFF
Detection Pattern & Optional Accessories
HBIR29/SV (Low-bay)
HBIR29/SV: Low-bay flat lens detection pattern for single person @ Ta = 20ºC
(Recommended ceiling mount installation height 2.5m-6m)
Mount height | Tangential (A) | Radial (B) |
---|---|---|
2.5m | max 50m2 (∅= 8m) | max 13m2 (∅= 4m) |
3m | max 64m2 (∅= 9m) | max 13m2 (∅= 4m) |
4m | max 38m2 (∅= 7m) | max 13m2 (∅= 4m) |
5m | max 38m2 (∅= 7m) | max 13m2 (∅= 4m) |
6m | max 38m2 (∅= 7m) | max 13m2 (∅= 4m) |
Optional Accessory — Ceiling/Surface Mount Box: HA03
Optional Accessory — Blind Insert for Blocking Certain Detection Angles
HBIR29/SV/R (Reinforced Low-bay)
HBIR29/SV/R: Low-bay convex lens detection pattern for single person @ Ta =
20ºC (Recommended ceiling mount installation height 2.5m-6m)
Mount height | Tangential (A) | Radial (B) |
---|---|---|
2.5m | max 79m2 (∅ = 10rn) | max 20m2 (∅ = 5m) |
3m | max 79m2 (∅ = 10rn) | max 20m2 (∅ = 5m) |
4m | max 64m2 (∅ = 9m) | max 20m2 (∅ = 5m) |
5m | max 50m2 (∅ = 8m) | max 20m2 (∅ = 5m) |
6m | max 50m2 (∅ = 8m) | max 20m2 (∅ = 5m) |
Optional Accessory — Ceiling/Surface Mount Box: HA03
Optional Accessory — Blind Insert for Blocking Certain Detection Angles![HYTRONIK HBIR29 SV PIR Standalone Motion Sensor with Bluetooth Mesh
- Blind Insert](https://manuals.plus/wp-content/uploads/2023/07/HYTRONIK- HBIR29-SV-PIR-Standalone-Motion-Sensor-with-Bluetooth-Mesh-Blind-Insert.png)
HBIR29/SV/H (High-bay)
HBIR29/SV/H: High-bay lens detection pattern for forklift @ Ta = 20ºC (Recommended ceiling mount installation height 10m-15m )
Mount height | Tangential (A) | Radial (B) |
---|---|---|
10m | max 380m2 (Ø = 22m) | max 201m2 (Ø = 16m) |
11m | max 452m2 (Ø = 24m) | max 201m2 (Ø = 16m) |
12m | max 452m2 (Ø = 24m) | max 201m2 (Ø = 16m) |
13m | max 452m2 (Ø = 24m) | max 177m2 (Ø = 15m) |
14m | max 452m2 (Ø = 24m) | max 133m2 (Ø = 13m) |
15m | max 452m2 (Ø = 24m) | max 113m2 (Ø = 12m) |
HBIR29/SV/H : High-bay lens detection pattern for single person @ Ta = 20ºC (Recommended ceiling mount installation height 2.5m-12m )
Mount height | Tangential (A) | Radial (B) |
---|---|---|
2.5m | max 50m2 (Ø = 8m) | max 7m2 (Ø = 3m) |
6m | max 104m2 (Ø = 11.5m) | max 7m2 (Ø = 3m) |
8m | max 154m2 (Ø = 14m) | max 7m2 (Ø = 3m) |
10m | max 227m2 (Ø = 17m) | max 7m2 (Ø = 3m) |
11m | max 269m2 (Ø = 18.5m) | max 7m² (Ø = 3m) |
12m | max 314m2 (Ø = 20m) | max 7m² (Ø = 3m) |
Optional Accessory — Ceiling/Surface Mount Box: HA03
Optional Accessory — Blind Insert for Blocking Certain Detection Angles![HYTRONIK HBIR29 SV PIR Standalone Motion Sensor with Bluetooth Mesh
- Blocking](https://manuals.plus/wp-content/uploads/2023/07/HYTRONIK-HBIR29 -SV-PIR-Standalone-Motion-Sensor-with-Bluetooth-Mesh-Blocking.png)
HBIR29/SV/RH (Reinforced High-bay with 3-Pyro)
HBIR29/SV/RH: Reinforced high-bay lens detection pattern for forklift @ Ta = 20ºC (Recommended ceiling mount installation height 10m-15m)
Mount height | Tangential (A) | Radial (B) |
---|---|---|
10m | max 346m2 (Ø = 21m) | max 177m2 (Ø = 15m) |
11m | max 660m2 (Ø = 29m) | max 177m2 (Ø = 15m) |
12m | max 907m2 (Ø = 34m) | max 154m2 (Ø = 14m) |
13m | max 962m2 (Ø = 35m) | max 154m2 (Ø = 14m) |
14m | max 1075m2 (Ø = 37m) | max 113m2 (Ø = 12m) |
15m | max 1256m2 (Ø = 40m) | max 113m2 (Ø = 12m) |
20m | max 707m2 (Ø = 30m) | max 113m2 (Ø = 12m) |
HBIR29/SV/RH : Reinforced high-bay lens detection pattern for single person @ Ta = 20OC (Recommended ceiling mount installation height 2.5m- 12m )
Mount height | Tangential (A) | Radial (B) |
---|---|---|
2.5m | max 38m2 (Ø = 7m) | max 7m2 (Ø = 3m) |
6m | max 154m2 (Ø = 14m) | max 7m2 (Ø = 3m) |
8m | max 314m2 (Ø = 20m) | max 7m2 (Ø = 3m) |
10m | max 531m2 (Ø = 26m) | max 13m2 (Ø = 4m) |
11m | max 615m2 (Ø = 28m) | max 13m2 (Ø = 4m) |
12m | max 707m2 (Ø = 30m) | max 13m2 (Ø = 4m) |
Optional Accessory — Ceiling/Surface Mount Box: HA03
Additional Information / Documents
- Regarding precautions for PIR Sensors installation and operation, please kindly refer to www.hytronik.com/download ->knowledge ->PIR Sensors – Precautions for Product Installation and Operation
- Data sheet is subject to change without notice. Please always refer to the most recent release on www.hytronik.com/products/bluetooth technology ->Partnership