Roth Touchline SL Reflermotor for Radiatorer Installation Guide
- June 12, 2024
- Roth
Table of Contents
Roth Touchline SL®
Installation
Living full of energy
Roth Touchline® SL radiator motor
Open the battery cover on the actuator and insert the AA batteries, beware of
the +/- poles. Once the batteries are inserted, the actuator starts to open
completely, making it easier to mount it on the valve. The openings can take
up to 1.5 minutes. The actuator is fully open, for mounting for approx. 30
minutes, after which it begins its calibration program – It is therefore
important that the actuator is mounted on the valve, within these 30 minutes,
as otherwise the actuator cannot perform its calibration program correct.
If you do not install the actuator within 30 minutes, remove one battery
again, press the registration button briefly and insert the battery again.
It is possible to initiate the calibration faster, to do this hold the pairing
button until the LED blinks 3 times. After this the actuator will calibrate on
the valve.
Registration of the actuator for the Touchline® SL master or the extension
module. Before you can register an actuator for a channel/zone, a thermostat
must be registered, see the instructions for the thermostat.
Registration of the actuator takes place in the same way on both control
units, using the same buttons. In the pictures, the panel from the Touchline®
SL Master control unit is shown.![Roth Touchline SL Reflermotor for Radiatorer
- control](https://manuals.plus/wp-content/uploads/2023/07/Roth-Touchline-SL- Reflermotor-for-Radiatorer-control.png)
Register an actuator for a channel on the control unit Follow steps 3 to 8 and
press the sign-up button (use the included tool) shown as step 9. Correct
short pressing of the registration button is signaled by a short blink of the
LED on the actuator, then, if the registration is successful, two short blinks
of the LED will occur. When the registration is unsuccessful, the LED will
light on for about two seconds.
Finish by pressinsg Menu and then press Exit repeatedly until default view.
Up to 6 actuators can be registered for each channel/zone.
Adapters for two types of Danfoss valves are included. Type RAN (click) or
type RTD-N. The adapters are easily mounted on the valve and the actuator is
screwed on.
The actuator can be used directly together with Roth’s own valves and floor
heating manifold without the use af adapters.
The actuator can also be used directly on valves from IMI/Heimeier TRV3 and
Honeywell radiator valves.
For mounting the radiator actuator on other types of valves, please contact
Roth.
If you want to remove all the actuators, press “Actuators removal”.
Information
If you select “Information”, you get an overview of the specic actuators connected to the zone: Software version, opening position, wireless signal and battery level. It is also possible to delete an specific actuator under “Information” by choosing the actuator and then choose “Delete”.
Settings
If you select “Settings”, you can view and change specific settings for the
actuator. Sigma, minimum and maximum opening time act as stabilizers for the
room temperature by proportional control of the actuator. In other words, it
helps prevent overheating and underheating of the zones and saves battery
life.
SIGMA
This function enables trouble-free control of the radiator actuator. In
addition, the user can define the minimum and maximum level for actuator
closing – so the level for opening/closing the actuator will then never exceed
these values. The values can be changed in the menu: “Zones” – “Zone”
-“Radiator actuators” – “Settings”.
We recommend to be very careful when changing these factory settings as it can
have a big impact on the function of the radiator actuator and the lifetime of
the battery.
Explanation of SIGMA function – example:
SET room temperature: 22°C.
Minimum opening: 1% (at reached SET = 22°C).
Maximum opening: 50%.
Sigma range: 1°C.
Protection range: 3°C.
Hysteresis: 0,2°C.
When the zone has been heated up to the set temperature of 22°C – the actuator
moves to 1%. When the temperature drops by the set hysteresis of 0.2°C -the
heating will turn on again. At a temperature of 21.8°C – the actuator moves to
10% (5% each 0,1°).
Area/Range
To adjust at which temperature the actuator starts to open/close, min.
0,00/max. 100 (factory set 10).
Min. opening/
Setting min. opening between 0 and 50% (factory set 1%).
Max. opening
Setting max. opening between 0 and 100% (factory set 50%).
Protection
When function is ENABLED (factory ON), the control unit monitors the
temperature. If the preset value is exceeded by the number of degrees
specified in the parameter “Protection range”, all actuators in a given zone
will close (0% opening). When temperature drops below preset value again
normal function is back. Function is only active when the SIGMA function is
activated (factory ON).
Emergency mode
To define the actuator opening which will be forced in the event of an alarm
in a given zone (communication error). There are two kind of communication:
between controller and sensor/thermostat and between controller and actuator.
Only the setting between controller and sensor can be changed, setting is
hardcoded into the actuator (factory set for both emergency modes are
10%).
Replacement of batteries
When the actuator runs out of battery it will remain in this exact position,
change batteries as soon as possible to prevent unnessary use of heat.
- Remove the battery cover
- Remove the batteries
- Press the registration button on the actuator
- Insert the new batteries and close the battery cover (Always replace both batteries with new ones).
Testing the connection
It is possible to check the connection between the actuator and the control
box by holding down the register button. If it flashes faintly green, the
connection is ok, if it flashes faintly red, there is no connection to the
control unit.
ROTH UK Ltd
1a Berkeley Business Park
Wainwright Road
Worcester WR4 9FA
Phone +44 (0) 1905 453424
E-Mail enquiries@roth-uk.com
technical@roth-uk.com
orders@roth-uk.com
accounts@roth-uk.com
roth-uk.com
ROTH DANMARK A/S
Centervej 5
3600 Frederikssund
Tlf. +45 4738 0121
E-mail: service@roth-danmark.dk
roth-danmark.dk