GOSSEN METRAWATT 210 Rogowski Flexible AC Current Probe Instruction Manual

June 12, 2024
GOSSEN METRAWATT

GOSSEN METRAWATT logo

Operating Instructions
MAVOWATT 210 ROGOWSKI
Flexible AC Current Probe
based on the Rogowski Principle
3-447-115-03
1/4.22
GOSSEN METRAWATT 210 Rogowski Flexible AC Current
Probe
MAVOWATT 210 Rogowski
Gossen Metrawatt GmbH

Safety Precautions

General

  • Carefully and completely read and adhere to these operating instructions.
    The document can be found at http://www.gossenmetrawatt.com. Retain this document for future reference.

  • Carefully and completely read and adhere to the product documentation of the combined products. Retain these documents for future reference.

  • Observe and comply with all safety regulations which are applicable for your work environment.

Handling

  • The probe may only be used as long as it is fully intact.
    Inspect all cables and the probe before use. Pay particular attention to damage, broken insulation or kinked cables.

  • If the probe doesn’t function flawlessly, remove it from operation and secure it against inadvertent use.

  • If the probe is damaged during use, e.g. through falling, remove it from operation and secure it against inadvertent use.

  • If the equipment is used in a manner not specified in this reference guide, the protection provided by the equipment may be impaired. These safety precautions are repeated where appropriate throughout this manual.

Operating conditions

  • Only use the probe in conjunction with the measuring device MAVOWATT 210.
  • Only use the probe in compliance with the specified technical data and under the specified conditions (ambient conditions, IP protection class, measuring category, etc.).
  • Do not use the probe after long periods of storage under unfavorable conditions (e.g. humidity, dust or extreme temperature).

Electricity

  • Installation, operation, and maintenance of this product must be performed by qualified personnel only.
  • Qualified personnel who work on or near exposed energized electrical conductors must follow  applicablesafety  related work practices and procedures including appropriate personal  protective equipment.
  • Wear proper personal protective equipment, including safety glasses and insulated gloves when making connections to power circuits.
  • Hands, shoes, and floor must be dry when making any connection to a power line.
  • Never apply the probe around bare conductors with hazardous voltages without having the appropriate permission to perform such work and without  wearing protective clothing and gloves as required.
  • Connections must be made to the measuring device first, then to the circuit to be monitored.
  • The probe may only be used within the limits of the specifications listed in this manual. Loads exceeding the specified values may destroy the probe and the electrical equipment connected to it.

Applications

Please read this important information!
2.1 Intended Use / Use for Intended Purpose
The MAVOWATT 210 Rogowski current probes are based upon the Rogowski principle. They can be used exclusively to measure AC current by being connected to MAVOWATT 210 Three-phase Power and Energy Logger.
The flexible probes allow current measurements on conductors that  are hard toreach.
Installation, operation, and maintenance of this product must be performed by qualified personnel only. Safety of the operator, as well as that of the product, is only assured when it’s used for its intended purpose.
2.2 Use for Other than Intended Purpose
Using the product for any purposes other than those described in the con- densed operating instructions or these product operating instructions is contrary to use  for intended purpose.
2.3 Liability and Guarantee
Gossen Metrawatt GmbH assumes no liability for property damage, personal injury or consequential damage resulting from improper or incorrect use of the product, in particular due to failure to observe the product documentation.
Furthermore, all guarantee claims are rendered null and void in such cases.
Nor does Gossen Metrawatt GmbH assume any liability for data loss.
2.4 Opening the Instrument / Repairs
Unauthorized modifications to the product are prohibited.

The Product

3.1 Scope of Application
This documentation applies to the following articles:

Product Product no. Description

MAVOWATT 210
Rogowski 500/40| Z840A| Flexible AC current probe based on the Rogowski principle, suitable for
MAVOWATT 210, 50 − 500 A, measuring head length 40 cm.
MAVOWATT 210
Rogowski 1500/40| Z840B| Flexible AC current probe based on the Rogowski principle, suitable for
MAVOWATT 210, 150 − 1500 A, measuring head length 40 cm.
MAVOWATT 210
Rogowski 3000/40| Z840C| Flexible AC current probe based on the Rogowski principle, suitable for
MAVOWATT 210, 300 − 3000 A, measuring head length 40 cm.

3.2 Product Overview

GOSSEN METRAWATT 210 Rogowski Flexible AC Current Probe - Probe
coupling

Figure 1: Flexible AC current probes based on the Rogowski principle
3.2.1 Symbols on the product and the included accessories:

| Warning concerning a point of danger (attention, observe documentation!)
---|---
| Double insulation (protection category II)
| Do not apply around or remove from hazardous live conductors without additional protective means.
| European conformity marking
| The device may not be disposed of with household trash a “Returns and Environmentally Sound Disposal” ****9.

3.3 Relevant Standards
The product has been manufactured and tested in accordance with the following safety regulations:

DIN EN 61326| Electrical Equipment for Measurement, Control and Laboratory Use − EMC Requirements
---|---
DIN EN 61010-1| Safety Requirements of Electrical Equipment for Measurement, Control, and Laboratory Use
− Part 1: General Requirements
DIN EN 61010-1-031| Safety Requirements of Electrical Equipment for Measurement, Control, and Laboratory Use − Part 031: Safety Requirements for Hand-held Probe Assemblies for Electrical Measurement and Test
DIN EN 61010-2-032| Safety Requirements of Electrical Equipment for Measurement, Control, and Laboratory Use − Part 2-032: Particular Requirements for Hand-held and Hand-manipulated Current Sensors for Electrical Test and Measurement

3.4 Technical Data

Rated Current Measurement range MAVOWATT 210 Rogowski 500/40 50 A — 500 A
MAVOWATT 210 Rogowski 1500/40 150 A — 1500 A
MAVOWATT 210 Hogowski 3000/40 300 A — 3000 A
Accuracy 0.5% per IEEE C57.13 class 0.6
Positioning error ±0.1 %
Ambient Conditions Operating temperature —20 … +70 °C
Relative humidity 5% to 95%,

no condensation allowed
Electrical| Phase orientation| Arrow points towards load
Frequency range| 45 Hz — 65 Hz
Frequency response| 10 Hz — 20 kHz
Safety| Working voltage| 1000 V CAT III, 600 V CAT IV
Dielectric strength| 7400 Vac at 50/60 Hz for 1 minute
Mechanical Design| Protection| IP61 per DIN EN 60529 / IEC 60529
Coil length| 40 cm
Coil diameter| 15.5 mm
Window size| 10.6 cm
Wire length| 2 m
Protection type| IP61

Installation

4.1 Unpacking the Product

  1. Carefully remove product and accessories from the packaging.
  2.  Check delivery for completeness and possible damage.
  3. In case of detected damages, hidden defects and short deliveries, document type and scope and contact the  manufacturer or supplier immediately.
  4.  Keep packing material for further transport.

4.2 Making Measurement Connections
To perform measurements, the Rogowski current probes are first connected to MAVOWATT 210. Subsequently, the Rogowski current probes are connected to the object to be measured.
Attention!
To avoid the risk of electric shock or burns, always connect the earth ground before making any other connections.
Attention!
Do not exceed the marked maximum ratings.
4.2.1 Connecting MAVOWATT 210 Rogowski Current Probes to MAVOWATT 210
√ MAVOWATT 210 is powered off.

  1. Plug the output cable of the current probe to the current input of MAVOWATT 210.

4.2.2 Connecting MAVOWATT 210 Rogowski Current Probes to the Circuit to be Measured
Attention!
DO NOT attempt to measure current in any circuit in which the circuit to ground voltage exceeds the insulation rating of the current probe.
Attention!
Make sure the current probes are tightly closed. Keep mating surfaces clean and free from foreign matter.
Note!
Do not locate the probe coupling close to other conductors carrying high current.
Note!
Be sure to connect the current probes with the arrow pointing towards the load or an erroneous power reading will result.
MAVOWATT 210 is powered off.

  1. Open the probe coupling and slip the measuring head over the conductor carrying the current to be measured.
  2. Close the probe coupling such that it visibly and audibly snaps into place.

The arrow marking on the current probe points in the direction of current flow and towards the load.
The conductor is centered within the measuring head.
The measuring head forms a perfect circle.GOSSEN METRAWATT 210 Rogowski
Flexible AC Current Probe - powered

Operation

For the different measurement configurations, refer to the Operating Instructions of MAVOWATT 210.

Maintenance

Cleaning
Keep the probe free of surface contamination. If necessary, clean the probe with isopropyl alcohol.

Contact, Support and Service

You can reach Gossen Metrawatt GmbH directly and uncomplicated, we have one number for everything!
Whether it’s a support question, or individual desire, we answer every request at:
+49-911-8602-0
Monday–Thursday:8:00 a.m. – 4:00 p.m.
Friday:  8:00 a.m. – 2:00 p.m.
You can also e-mail to: [email protected]

Do you prefer support via e-mail?

Measuring and test instruments: [email protected]
Industrial equipment: [email protected]

For repairs, replacement parts, and calibrations  1please contact GMC-I Ser- vice GmbH:

[email protected]
www.gmci-service.com
+49-911-817718-0

https://www.gmci-service.com/

Beuthener Str. 41
90471 Nürnberg
Germany

  1. DAkkS calibration laboratory per DIN EN ISO/IEC 17025.
    Accredited at the Deutsche Akkreditierungsstelle GmbH under registration no. D-K15080-01-01.

CE Declaration

The product fulfills all requirements of applicable EU directives and national regulations. We confirm this with the CE mark. The CE Declaration of Conformity is available upon request.

Returns and Environmentally Sound Disposal

This product is subject to directive 2012/19/EC on Waste Electrical and Electronic Equipment (WEEE) and its German national equivalent implemented as the Waste Electrical and Electronic Equipment Act (ElektroG) on the marketing, return and environmentally sound disposal of electrical and electronic equipment. The product is a category 9 product (monitoring and control instrument) in accordance with ElektroG (German Waste Electrical and Electronic Equipment Act).
The symbol at the left indicates that this device and its electronic accessories must be disposed of in accordance with applicable legal regulations, and not together with household waste. In order to dispose of the device, bring it to a designated collection point or contact our product support department ( ). Separate disposal and recycling conserves resources and protects our health and the environment.
Current and further information is available on our website at http://www.gossenmetrawatt.com under the search terms “WEEE” and “environmental pro- tection”.

© Gossen Metrawatt GmbH
Prepared in Germany • Subject to change, errors excepted • PDF version available on the Internet
All trademarks, registered trademarks, logos, product names, and company names are the property of their respective owners.

Gossen Metrawatt GmbH
Südwestpark 15
90449 Nürnberg • Germany
Phone +49 911 8602-0
Fax +49 911 8602-669
E-mail[email protected]
www.gossenmetrawatt.com

Documents / Resources

| GOSSEN METRAWATT 210 Rogowski Flexible AC Current Probe [pdf] Instruction Manual
210 Rogowski Flexible AC Current Probe, 210 Rogowski, Flexible AC Current Probe, AC Current Probe, Current Probe, Probe
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

GOSSEN METRAWATT User Manuals

Related Manuals