MYPV AC-THOR, AC ELWA-E Smart Energy Meter Instruction Manual
- October 30, 2023
- MYPV
Table of Contents
AC-THOR, AC ELWA-E Smart Energy Meter
with Kostal Piko IQ, Plenticore Plus or Smart Energy Meter (KSEM)
Instruction Manual
Default settings on AC•THOR or AC ELWA-E
Before commissioning, it is essential that you read the assembly instructions
that accompany the device, as well as the operating instructions available on
line.
Find the AC•THOR operation manual here.
Find the AC ELWA-E operation manual here.
Communication of AC•THOR or AC ELWA-E with Kostal
AC•THOR or AC ELWA-E are connected to Kostal in the network via a router.
Within this network, the unit receives information from Kostal about how much
excess PV power is available.
Do not connect the unit directly to the inverter or battery system!
When controlled by an inverter, a feed-in meter is required in the system.
Otherwise, the query of the inverter does not provide any data.
Settings on Kostal
With the “Kostal PIKO IQ Plenticore plus Manual” control, Modbus must be
activated on the inverter.
For the “Kostal Smart Energy Meter Manual” control, “Enable TCP Slave” must be
activated under Modbus Settings – Modbus TCP.
When communicating with Kostal, the IP address of the inverter must not change during operation (e.g. through a DHCP router), otherwise the AC•THOR or the AC ELWA-E will lose the control signal!
Settings on AC•THOR or AC ELWA-E
For the AC•THOR, select “Kostal PIKO IQ Plenticore plus Manual” or “Kostal Smart Energy Meter Manual” for the control type either on the display or in the web interface. The IP address of the signal source must then be statically specified on the display under “Ctrl IP”.
Alternatively, these settings can also be made on the AC•THOR via the web
interface. In the web setup, the parameters “Device ID” and “Device Port” can
also be set by Kostal.
For the “Kostal PIKO IQ Plenticore plus Manual” control, my-PV has preset
device ID 71 and device port 1502.
For the “Kostal Smart Energy Meter Manual” control, my-PV presets device ID 1
and device port 502.
With the AC ELWA-E, configuration is only possible in the web setup.
“Power timeout” is not to be changed.
If there is a battery storage unit in the system and it is to be charged with
priority, then the “target value of the control” should be set to -150 W.
Otherwise, we recommend leaving -50 W.
Subject to change. my-PV GmbH