MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device User Manual

October 30, 2023
MYPV

MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device

Product Information

The AC ELWA-E is a device that helps to optimize the usage of excess power generated by a photovoltaic system. The device can be configured with or without a router and has a temperature-adjusting knob, device number for 13A/16A fuse protection, LED operating mode displays, and a scanner program called my-PV Scanner 1.XX.exe.

Product Usage Instructions

Assembly

Before placing the AC ELWA-E into operation, it is essential to read the assembly instructions provided with the device.

Controls and Displays

The AC ELWA-E has a temperature-adjusting knob labeled 1-6, device number for 13A/16A fuse protection, and LED operating mode displays that indicate the following:

  • Green: Start-up

  • Yellow: Standby, Heating with excess power, Heating for hot
    water securing (Boost-mode), Heating finished, set-point
    temperature reached

  • Red: Setup mode, No control signal, Error

Putting into Operation

During the first commissioning, the AC ELWA-E is in the so-called Auto Detect mode. The device automatically searches for a signal source and adjusts itself accordingly. If the search is successful, NO further configuration via the Web-Interface of the AC ELWA-E is required for the use of excess power!

Configuration with Router (recommended)

The start-up with router only works if it is configured to DHCP. Follow the steps below:

  1. Connect your laptop with the router (LAN or WLAN).
  2. Connect the AC ELWA-E and router via a standard Rj45-cable (patch-cable).
  3. Plug in the AC ELWA-E power plug.
  4. The AC ELWA-E gets a dynamic IP-address from the router.

Using the program my-PV Scanner 1.XX.exe (contained in Software Package AC ELWA-E.zip at www.my-pv.com), the AC ELWA-E can be found. To do this, unpack the scanner program into a local directory.

Configuration without Router

To configure the AC ELWA-E without a router, follow the steps below:

  1. Connect your laptop with the AC ELWA-E via a standard Rj45-cable (patch-cable).
  2. Plug in the AC ELWA-E power plug.
  3. The AC ELWA-E starts up in DHCP mode and gets a dynamic IP-address from the laptop.
  4. Open a web browser and enter the IP-address of the AC ELWA-E into the address bar.
  5. You will be directed to the Web-Interface of the AC ELWA-E, where you can configure it further.

Web-Interface

The Web-Interface of the AC ELWA-E allows for further configuration of the device. To access it, enter the IP-address of the AC ELWA-E into a web browser. From there, you can adjust various settings such as fuse type, device number, and firmware updates.

Knob Adjustments

The temperature-adjusting knob on the AC ELWA-E can be adjusted to set the desired temperature for excess power usage. The device number knob can be adjusted to choose the appropriate fuse protection for either 13A or 16A.

Protocol Description of HTTP and Modbus TCP

The AC ELWA-E uses HTTP and Modbus TCP protocols for communication between devices. These protocols allow for seamless communication and data transfer between the AC ELWA-E and other devices.

Firmware Update Ethernet

The firmware of the AC ELWA-E can be updated via Ethernet. There are two ways to update the firmware:

  1. Update from Server (for SNr 160124180131XXXX and above).
  2. Update with USB cable (for SNr below 160124180131XXXX).

Fault Indication

The AC ELWA-E has a fault indication system that uses LED lights to indicate any errors or issues with the device. The LED lights can blink, turn off, or change colors to indicate the specific issue.

Assembly

Before placing into operation it is essential to read the assembly instructions provided with the
device.

Controls and displays

Operation displays

MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device-
FIG2

The display can change between „No control signal“ and „Standby“, if the device is triggered via Web-Interface or in cycles of one minute when data of temperature and power are recorded.

Putting into operation

During the first commissioning the AC ELWA-E is in the so-called “Auto Detect” mode. The device automatically searches for a signal source and adjusts itself accordingly. If the search is successful, NO further configuration via the Web-Interface of the AC ELWA-E is required for the use of excess power!

Configuration with router (recommended)

The start-up with router only works, if it is configured to DHCP.
The device must not be in Setup-Mode ( symbol on adjusting knob)

  1. Connect laptop with router (LAN or WLAN)

  2. Connect AC ELWA-E and router via standard Rj45-cable („patch-cable“)

  3. Plug in AC ELWA-E power plug

  4. AC ELWA-E gets a dynamic IP-address from router.
    Using the program „ my-PV Scanner 1.XX.exe“ (contained in „Software Package AC ELWA-E.zip“ at www.my-pv.com) the AC ELWA-E can be found.
    To do this, unpack the scanner program into a local directory.

  5.  Are there more AC ELWA-Es in the network, the desired device can be determined by the serial number (lateral on the case)!

  6. A double click on the particular device opens the Web-Interface of the AC ELWA-E.
    From firmware version 00200.00 onwards, the required HTML file is downloaded from the Internet and stored in the same directory as the scanner program Scanning is performed via UDP port 16124. Firewalls (or specific router settings) may prevent the AC ELWA-E from being found.
    In this case, it is advisable to look for the IP address of the AC ELWA-E in the DHCP list of the router and enter it manually into the address line of the web browser.
    Alternatively, the second scan program “Scan AC ELWA-E ARP.exe” can be used, which sends an ARP query to the router and displays the connected my-PV devices. Since the router takes some time to update the ARP table it may be that the ARP scan takes some time to show AC ELWA-E results.

TIP: Alternatively, the IP address of the device can also be determined via the DHCP client list of the router or via various IP scan programs!
From firmware version 00200.00 onwards, the Web-Interface of AC ELWA-E is outsourced to an external HTML file. If the device is accessed directly via the IP address in the web browser, this view appears.

MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device-
FIG6

Follow the download link and save the file locally, then open the file to access the Web- Interface.
my-PV does not recommend to connect the AC ELWA-E to the Internet via port forwarding access!

Configuration without router

From Ethernet firmware version 00200.00 this applies:
To be able to access the Web-Interface of AC ELWA-E in systems without internet access, please download the required HTML file in advance.
You will also find a corresponding note on the carton box:

Der Zugriff auf das Web-Interface dieses Gerätes ist nur durch eine HTML Datei möglich.

Download:
https://www.my-pv.com/download/currentversionget.php
Access to the web interface of this device is only possible through an HTML file.

Download:
https://www.my-pv.com/download/currentversionget.php

Procedure

  1. Set adjusting knob to the symbol (all three LEDs blinking)

  2. Plug in AC ELWA-E power plug

  3. All 3 LEDs of the AC ELWA-E are on for approx. 10 seconds (device boots), afterwards all 3
    LEDs are blinking. The device is now in Setup-Mode

  4. Disconnect existing Wi-Fi connections on the laptop to avoid possible network-conflicts

  5. Connect Laptop to AC ELWA-E via standard Rj45-cable („patch-cable“).
    Depending on the laptop, a cross-over network cable may be required!

  6. The Laptop gets a dynamic IP address

  7. The operating system might request you to choose a place of the network. At this step it is not necessary to do so. You can close the window.

  8. Insert address 192.168.0.1 in the web browser to select homepage of the AC-ELWA-E
    MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device-
FIG32

  9. Start the previously downloaded HTML file to get to the Web-Interface

  10.  Select Button „Settings“ and configure as described in chapter „Setup“

  11.  After all the settings have been made, disconnect the AC ELWA-E power plug

  12.  Turn the knob to the desired temperature

  13. Disconnect the data connection between AC ELWA-E and Laptop/PC

  14. Connect AC ELWA-E via standard Rj45-cable („patch-cable“) with router or via cross-over network cable directly with the my-PV Power Meter!
    Do not connect the device directly to the inverter or the battery system! 15. Plug in the AC ELWA-E power plug again

If the signal source for the AC ELWA-E is searched with the „Auto Detect“ – function, the process can take a few minutes!
If the set-up is done without a router, a connection between PC/Laptop – Router – AC ELWA-E can though be implemented afterwards. See next chapter!

Web-Interface

By means of the HTML file (required for Ethernet firmware version 00200.00 or higher) data of the AC ELWA-E can be retrieved and adjustments can be made.
If the Web-Interface is started via the scanner program, the connection to the device is established automatically.
From firmware version 00201.01onwards, the current Web-Interface allows the selection of
French or Spanish in addition to German and English.
If the Web-Interface is started by calling the HTML file, the IP address range of the network in which the device is located must be set once. The entry is saved by the web browser, but the address range can be redefined at any time using the “IP Search Range” button.

From the homepage further pages can be selected via the menu buttons.

MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device-
FIG8

A quick selection in the upper right corner allows direct access to the Web- Interface from other my-PV devices in the network. The button “Search Devices” scans the network for my-PV devices.
TIP: If the device search does not produce a result, the IP address can also be entered manually in the address line of the web browser.
URL: … /my-PV Websetup 00XXX.XX.html?ip=XXX. XXX. XXX. XXX

Consider that the appearance and the scope of options can change with updated software versions.

Home (homepage)

The graphic shows the current temperature in the boiler, the bar on the left visualises the power output of the device.
With device state “Off” the control of the AC ELWA-E can be switched off. The status page displays “Status 21, Device disabled”.
With the button „Single Boost“ the hot water backup can be started immediately once.
The dynamic web pages „Home“ and „Status“ are displayed without animation by
Microsoft Internet Explorer. Recommended browsers are Google Chrome or Mozilla Firefox in the latest versions!

MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device-
FIG33

Depending on which other measurements are queried in the system (see “Measurement Settings”), the status overview also provides information on these variables.

Data logger

A graphical information of the operating data is provided in the data platform my-PV.LIVE (see “Cloud Mode”).

MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device-
FIG11 Setup
On this page all adjustments of the device can be made.

Boost Settings
As an option, the AC ELWA-E can also ensure a minimum temperature in addition to the normal excess power operation. During backup operation the device is supplied with a power of 3kW.

MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device-
FIG34

Two boost timeframes can be defined per day. These frames may overlap.
Start hour and stop hour refer to the same calendar day. If a time window is defined over midnight, hot water backup will not start!
If the adjusted start-hour is after the stop-hour, hot water backup will not start!

Legionella Protection

To ensure drinking water hygiene, a period of time can be specified up to which an adjustable minimum temperature must be reached again after the last time this value has been reached.
The number of days of this period is adjustable between 1 and 14. A time at which the legionella program is to be started can be specified. The factory preset values of the days is 7, the start time is 8 pm, the temperature is 60 °C, the legionella program is “Off”.
The AC ELWA-E is then supplied with a power of 3kW.

Time

In case of an available internet connection via a router, AC ELWA-E gets its time setting automatically from the web but it doesn’t determine the particular time zone. That information can be transferred from the Laptop/PC by pressing the „Save/Speichern“ Button. The re-setting
of the ELWA-time to the new time zone can last a few minutes. Usually the time zone on the Laptop/PC shifts with the change from summer to wintertime. This shift can also be adopted with the „Save/Speichern“ Button. An automatic
time shift from summer to winter is not scheduled.
NTP-Timeserver-address: can be changed if necessary. (NTP = Network Time Protocol).
When there is no connection to the internet, the current time zone setting can be transferred
from the Laptop/PC by pressing „Set to PC Time / Auf PC Zeit stellen“.
If the device has no internet connection via router, the time setting is lost after a power outage.

Control Settings

  • In this section the choice of the signal source for the AC ELWA-E is made.
    A control type can only be selected if the AC ELWA-E has the factory preset device number See “Basic settings”.
    As a factory pre-set the control mode „Auto Detect“ is present. The device automatically searches for compatible sources. Some compatible manufacturers are not recognizable by the “Auto Detect” function!

  • The “Auto Detect” function can only be effective when just one signal source is present in the network. If there are more different sources (e.g. several inverters), a manual setting is essent ial for a correct functionality!
    For certain compatible sources the choice between „Auto“ (automatic IP-search of the device) or „Manual“ (manual entry of the IP address of the source) is possible. „Manual“ is necessary when there are several compatible sources in the network and a special one of them should be chosen as the control system.

  • The control mode “my-PV Power Meter direct” has to be selected when a direct data connection between the Power Meter and the AC ELWA-E is made (without network).
    For this type of connection a crossover patch cable has to be used!
    If the AC ELWA-E is also used for the optional hot water boost-backup, then the direct connection is not recommended since time and boost-backup settings are much easier to set via the network!
    It can take up to a minute before the direct connection is established!

Signalsource Comments
my-PV Power Meter Auto Connection to my-PV power meter in the network is set

up automatically. Setting up the connection may take up to a minute!
my-PV Power Meter Manual| Connection to my-PV power meter in the network is set up by entering the IP address manually.
my-PV Power Meter Direct| Connection to the my-PV Power Meter is established directly without a network. A crossover network cable must be used for this type of connection!
Adjustable Modbus TCP (Sunspec etc)| Explanation below.
Carlo Gavazzi Manual| Approved for meter type EM24 with Modbus TCP.
Fronius Auto / Manual

Fronius Gen24 Manual Fronius Sunspec Manual

| Smart Meter required.

For Modbus control Sunspec must be activated.

GoodWe Manual| Works with inverters that communicate via the GoodWe LAN module (not WIFI) using Modbus TCP.

For systems with battery storage, a value of 290W feed-in is preset as the target value of the control; without a battery, the value can also be reduced.

http| A description of this open protocol is available in a separate document, which will be provided on request.
Huawei (Modbus TCP) Manual| Works with Huawei devices that communicate via Modbus TCP, such as the Huawei Smart Dongle-WLAN-FE!

Note: From dongle firmware SPC124, TCP must be activated locally via the Huawei app!

KACO TL1 + TL3 Manual| Sunspec must be enabled on inverter.
Kostal PIKO IQ Plenticore plus Manual| Suitable electricity meters please refer to the Kostal descriptions. Modbus must be activated on the inverter.
Kostal Smart Energy Meter Manual| Device ID as set on the device.

Modbus Settings – Modbus TCP – set “Enable TCP Slave” active

MEC electronics Manual| Approved for meter type MECmeter.
Modbus TCP| A description of this open protocol is available in a separate document, which will be provided on request.
---|---
RCT Power Manual| –
Slave| Cannot be selected manually. See chapter “ Fehler! Verweisquelle konnte nicht gefunden werden.
SMA Direct meter communication Auto / Manual| This control type is available for the SMA Energy Meter and SMA Sunny Home Manager devices.

If this control type is carried out by the Sunny Home Manager, the superordinate energy planning for the my-PV device is then not given. There is also no visualization in the Load Balance. However, the power control is then carried out significantly faster than with the control type “SMA Home Manager”.

SMA Home Manager| The power signal which the SMA Sunny Home Manager gives the my-PV device depends not only on the feed-in, but also on the superordinate energy planning.
SolarEdge Manual| Modbus TCP must be enabled on SolarEdge.

The communication usually works either via port 502 or 1502.

According to the latest information from SolarEdge, this control only works when connected via LAN, not WLAN.

Steca Auto| –
Sungrow Manual| Works with Sungrow devices that communicate via Modbus TCP.
Varta Auto / Manual| –
Victron Energy 1ph / 3ph Manual| With Modbus control, the excess power control can be selected according to one or three phases.

TIP: For many of these and other manufacturers there are separate instructions for the required settings. More information about compatible manufacturers can be found here.

  • Not every control type is approved for hybrid systems with battery storage. If required, please contact the technical support of my-PV.

  • For some control types the IP address must be set manually. This must not change during

  • operation (e.g. by a DHCP router), otherwise the AC ELWA-E loses the control signal.

  • When controlled by an inverter, a feed-in meter is required in the system. The query of the inverter otherwise provides no data.

  • We ask for your understanding that we cannot do any binding support for third-party products.

  • For questions about third-party products, please contact the technical support of the respective company.
    Operation with battery may require additional control parameters. In this case, please contact the technical support of my-PV.

  • With the setting „Power Timeout“ the timeout of AC ELWA-E can be changed for the modes „http”, „Modbus TCP“ and „Adjustable Modbus TCP“.

  • The parameter “Control Target” specifies the set point of the power at the metering point. A negative value means feed-in. The factory pre-set of the set-point is -50 W. This parameter can be freely chosen in a range between -500 and +500 W.

  • The function „Block“ allows to define a time window within AC ELWA-E must not run. Unlike the two time frames for hot water securing the transition to the following day is possible (Start Hour is higher than Stop Hour). For example, this function can be used to give an existing battery time for charging and to do the water heating subordinate.

  • Changes of the time settings are effective within one minute.

  • With the “Adjustable Modbus TCP” control mode, the AC ELWA-E receives the power-value in the feed-in point from an inverter or Modbus counter. The required communication registers shall be set according to the manufacturer’s description.
    Device ID must be set to the Modbus ID of the external device.

  • This type of control is currently not approved for hybrid systems with battery storage.

  • With the settings “Adjustable Modbus TCP (Sunspec etc)”, the IP address of the signal source must not change during operation (eg by a DHCP router), otherwise the AC ELWA-E loses the control signal.

  • When controlled by an inverter, a feed-in meter is required in the system. The query of the inverter otherwise provides no data.

  • We ask for your understanding that we cannot do any binding support for third-party products. For questions about third-party products, please contact the technical support of the respective company.

  • Operation with battery may require additional control parameters. In this case, please contact the technical support of my-PV.

Measurement Settings

As an option, other measurements can be queried in the system in addition to PV excess measurement and visualise them on the my-PV.LIVE data platform. Available variables are PV power, Battery power, EV Charging station power and Heat pump power.
If you are using the my-PV Power Meter to detect these values, you must enter the ID (serial number) of the device. You will find this number on the device.

If the measured values come from an inverter or Modbus meter, the required communication registers shall be set according to the manufacturer’s description.
We ask for your understanding that we cannot do any binding support for third- party
products. For questions about third-party products, please contact the technical support of the respective company.

At the measuring point “Photovoltaic power” it is possible to block the my-PV device if the inverter does not produce any power. The operation for optional boost-backup is not affected by this.

EV Function
More information on compatible charging stations can be found here.

Multi Units
Several AC ELWA-E, AC•THOR or AC•THOR 9s can also be used in a network. Operation is based on the master/slave principle.

When using several devices the following things have to be considered:

  • All devices must be connected to the router via a network cable.
  • Only one master can be assigned to a signal source and vice versa.
  • A maximum of 10 slaves are possible per master.
  • All slaves in the network must have different device numbers, even if these are assigned to different masters.
  • All devices must be assigned by permanent IP addresses. This can be done in two ways:
    • In the Web-Interface of the respective device (see IP Settings) or via Cloud
    • By the router (recommended)

Settings on Slaves
For the slaves only the device numbers have to be specified (see Basic Settings). All other settings are only required on the master.

MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device-
FIG19

As soon as an assignment has been made, further control settings are no longer possible or required. The IP address field is disabled and “Slave” appears in the Control type field. After a device search in the quick selection at the top right, the slave with the set number appears. Switching between the devices is possible here.

Settings on Master
Only for devices with number 1 (= master) the following display appears in the setup:

MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device-
FIG21

To make the settings for several devices on the master, first choose between Synchron and Stratify. In the case of synchronous charging, the power is evenly distributed to the master and its slaves. In the case of stratified charge, the devices are controlled one after the other according to their numbers, in each case until the set target temperature is reached. After selection, please start the “Search for slaves” and activate the desired devices. Then save the setting.

MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device-
FIG22

Scanning is performed via UDP port 16124. Firewalls (or specific router settings) may prevent the AC ELWA-E from being found. (see Placing into operation with router)

IP Settings

MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device-
FIG23

DHCP: Selection of DHCP is standard, which means the device requests an IP address from the router to which it is connected.
This only works when the router is configured as a DHCP server.
Static IP: If there is no DHCP server active in the network or third-party control is desired, a static IP address is necessary.
The settings have to fit with the router, otherwise the device become invisible in the network!

Basic Settings

MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device-
FIG24

Number: Ex-factory each AC ELWA-E is assigned the number 1. If several devices are used, this setting must be adjusted for the “Slaves” (see Multiple devices). Fusetyp: If the device is connected to a 13 A plug socket, the 13 A setting restricts the maximum power to 2,500 W.

Cloud Mode
TIP: Inform yourself in advance on the Cloud Mode simply by watching our video explanation (activate English subtitles): https://youtu.be/tJtAvwM7-7Q

If your device has a device key, a connection to the data platform my-PV.LIVE possible. You will find it glued on the enclosed assembly instructions

MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device-
FIG25

Activate the cloud mode and save the settings.

MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device-
FIG26

Open the website www.my-pv.live and log in or register as a new user.

TIP: If you register for a new account you will receive an email with a confirmation link. If it does not appear in your inbox, it might be in your spam folder.

Choose a name that is as unique as possible and enter the serial number and the device key (without hyphens) of your device. Click on Save.
If the cloud mode has been activated, an overview of the operating data recorded from then on is available after connecting the device to the data platform.

MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device-
FIG27

Privacy
Information on the privacy regulations can be found at www.my-pv.com.

Debug-Mode
In order to simplify the analysis in the case of possible connection problems, a debug mode can
be activated in coordination with our technical support.

Firmware Version
In this section the current firmware versions can be retrieved (for service and Update purpose).

Details about the button “Update Firmware” can be found in the chapter “Firmware Update Ethernet”.
The button “Reboot Device” restarts the AC ELWA-E.
With the button „Factory Reset“ all settings of the device are set back to factory pre-set. After pressing the button a confirm message appears.
Consider that depending on the router settings the AC ELWA-E eventually is no longer visible in the network. To find it again restart the AC ELWA-E program „ my-PV Scanner 1.XX.exe”. For this reason, you cannot be automatically redirected to the AC ELWAE´s Web-Interface after reset.

Reset to factory settings

Pressing the “Factory Reset” button in the Web-interface is one way of resetting the AC ELWA-E to the factory settings.
As of Ethernet firmware 00202.XX, this can also be done by unplugging and plugging in the
Ethernet connector three times within 10 seconds. Before unplugging, always wait until the yellow and green LEDs on the RJ45 plug light up!

Knob adjustments

The following sections describe the possible settings with the knob.
The device parameterization is much more comfortable via the Web-Interface!
The target temperature for the regular operation mode has to be adjusted with the knob.
Target temperature cannot be set via the Web-Interface, only queried.

Adjust fuse type of the circuit (13A/ 16A)

With factory preset AC ELWA-E can perform up to 3.000 W (16 A). For circuits with 13 A fuses the power consumption can be limited to 2.500 W (setting on the AC ELWA-E or via Web-Interface possible).

Configure the device as follows:

  1. Disconnect power plug
  2. Set adjusting knob to the symbol
  3. Plug in the power plug
  4. All 3 LEDs blinking (Setup mode active)
  5. Turn the knob to the 13A marking  LEDs blinking from top to the bottom: green, yellow, red, green, etc.
  6. Value is automatically saved when the position of the knob is not changed for 5 seconds
  7. All 3 LEDs blinking fast for 2 seconds, setting saved.
  8.  Set the knob to the desired temperature value
    The setting can be reversed. For this purpose repeat procedure.

Adjust device number

  1. Disconnect power plug
  2.  Set adjusting knob to the symbol
  3. Plug in the power plug All 3 LEDs blinking (Setup mode active)
  4. Turn the knob to the desired device-number marking
    LEDs blinking to signal the number (see table)AC ELWA-E

number:

| LED green| LED yellow| LED red
---|---|---|---
1| blinking| off| off
2| off| blinking| off
3| blinking| blinking| off
4| off| off| blinking
5| blinking| off| blinking
6| off| blinking| blinking
5. Value is automatically saved when the position of the knob is not changed for 5 seconds
All 3 LEDs blinking fast for 2 seconds, setting saved.
6. Set the knob to the desired temperature value
The setting can be reversed. For this purpose repeat procedure.

Protocol description of http and Modbus TCP

These are described in a separate document which will be provided on request.

Firmware Update Ethernet

Before updating, please consider whether you really need an update! After the update, the view of the “day-chart” from Ethernet versions before 200.00 is no longer available locally.
For the graphic display of the operating data, my-PV.LIVE must then be used. A connection to my-PV.LIVE is only possible for devices from 160124171114XXXX!
From serial number 160124180131XXXX the update is no longer carried out with USB cable. The firmware is downloaded via the Internet instead.

For serial number older than 160124180131XXXX a remote firmware-update via Internet is not possible. It is instead done with a USB cable.

Update from Server (from SNr 160124180131XXXX)

Internet access is required!
With the “Update Firmware” button, the AC ELWA-E loads the latest firmware from the Internet.
After the update, the AC ELWA-E is automatically restarted.

Update with USB cable (for SNr below 160124180131XXXX)
The update of the firmware for the communication via Ethernet happens via the Micro USB interface and the provided USB cable at the bottom of the unit. A firmware update via the Ethernet interface is not possible because of security reasons.
Get the Firmware here.

Fault indication

MYPV AC ELWA E Electrical Photovoltaic Excess Hot Water Device-
FIG31

my-PV GmbH
Betriebsstrasse 12, 4523 Neuzeug
www.my-pv.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals