MYPV 9120095460051 AC ELWA-E Instructions

October 30, 2023
MYPV

MYPV 9120095460051 AC ELWA-E

According to the latest information from SolarEdge, this control only works when connected via LAN, not WLAN.

Default Settings On AC Thor Or Ac Elwa-e

Before commissioning, it is essential that you read the assembly instructions that accompany the device, as well as the operating instructions available on line.
Find the AC•THOR operation manual here.
Find the AC ELWA-E operation manual here.

Communication of AC•THOR or AC ELWA-E with SolarEdge

AC•THOR or AC ELWA-E are connected to SolarEdge in the network via a router. Within this network, the device receives information from SolarEdge about how much photovoltaic surplus is available.

Do not connect the unit directly to the inverter or battery system!
When controlled by an inverter, a feed-in meter is required in the system. Otherwise, the query of the inverter does not provide any data.

Settings on SolarEdge

  • ‘Sun Spec” must be set as the protocol.
  • If possible, set the unit ID to 1 (unit ID 1 is preset for my-PV).
  • Activate Modbus TCP
  • Note the port number. This is still required for the settings on the my-PV unit (port number 502 is preset for my-PV).

When communicating with SolarEdge, the IP address of the inverter must not change during operation (e.g. by a DHCP router), otherwise the AC-THOR or the AC ELWAE will lose the control signal!

TIP : If there are problems with data transmission, deactivating and then restarting the Sun spec data communication on the SolarEdge can help.

Settings on AC•THOR or AC ELWA-E

For the AC•THOR, select “SolarEdge Manual” for the control type either on the display or in the web interface.

TIP : For the AC ELWA-E from firmware 00205.00 and for the AC-THOR from firmware a0020800, the control types “SolarEdge Syn.2unit Manual” and “SolarEdge Syn.3unit Manual” are also available.

The IP address of the signal source must then be statically specified on the display under “Ctrl IP”.

Alternatively, these settings can also be made on the AC-THOR via the web interface. In the web setup, the parameters “Device ID” and “Device Port” can also be set by SolarEdge.
With the AC ELWA-E, configuration is only possible in the web setup.

“Power timeout” is not to be changed.
If there is a battery storage unit in the system and it is to be charged with priority, then the “Target value of the control” should be set to -150 W. Otherwise, we recommend leaving -50 W.