SENSOR 217E-02 Photo Electric Smoke Alarm User Manual
- October 30, 2023
- Sensor
Table of Contents
- SENSOR 217E-02 Photo Electric Smoke Alarm
- Product Information
- Specifications
- Overview
- Understanding Indicator and Alarm Signals
- Interconnected Units
- Installation Preparation
- Where Not to Install Your Alarm
- Installation
- What to do if the Alarm Sounds
- Warranty
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SENSOR 217E-02 Photo Electric Smoke Alarm
Product Information
The Photoelectric Smoke Alarm is a device that detects smoke andalerts occupants of a building to the potential danger of a fire.It has a Sensor 21E-02 and operates on both mains and battery power. The smoke alarm is capable of being interconnected with other devices and complies with safety standards.
Specifications:
- Sensor 21E-02
- Primary Power Source: Mains
- Secondary Power Source: Battery
- Mains supply current limit: 100mA
- Number of interconnected devices: Up to 40
- Operating temperature: -10°C to 55°C
- Operating humidity: 10% to 90% relative humidity (RH)
- Storage temperature: -20°C to 60°C
- Storage humidity: Up to 93% RH
- Complies with safety standards
Usage Instructions:
- Install the smoke alarm in a central location on the ceiling or high on a wall, away from corners, vents, and other obstructions.
- Connect the smoke alarm to the mains power supply.
- Insert a fresh battery into the smoke alarm.
- To test the smoke alarm, press and hold the test button until you hear a loud beep and the LED light flashes. If the smoke alarm does not sound, replace the battery and try again. If it still does not work, contact customer support.
- If the battery is low, the smoke alarm will beep three times every 40 seconds. Replace the battery immediately.
- If the smoke alarm detects smoke, it will sound an alarm with three long beeps followed by a pause, repeating until the smoke clears. The red LED light will flash, and the yellow LED light will flash once then three times in two cycles.
- To silence the alarm temporarily, press the hush button. The smoke alarm will beep every ten seconds for eight minutes.
- If there is a fault with the smoke chamber, the smoke alarm will beep three times every 40 seconds, and the yellow LED light will flash three times every 40 seconds. Contact customer support.
- The smoke alarm can be interconnected with up to 40 other devices. When connected, the green LED light will be continuously on, and the red LED light will flash every 40 seconds. If a device detects smoke, all connected devices will sound an alarm.
- To test interconnected devices, press and hold the test button on one device. All interconnected devices should sound an alarm.
- If a device enters alarm condition, the red LED light will flash every one second, and the yellow LED light will flash once every three seconds.
- Keep the smoke alarm clean by vacuuming it regularly. Do not paint or cover the smoke alarm.
- Replace the battery every year and replace the smoke alarm every ten years.
Specifications
Primary Power Source | AC(100 ~ 240)V |
---|---|
Secondary Power Source | DC 3V |
Mains supply current limit | 0.06A@230V, 0.12A@115V |
Number of interconnected devices | 20 |
Operating temperature | (0 ~ +55)˚C |
Operating humidity | (10 ~ 95) % RH, non-condensing |
Storage temperature | (-25 ~ +80) ˚C |
Storage humidity | (0 ~ 98) % RH, non-condensing |
Complies with | AS3786:2014 |
Sensor 21E-02
Caution
This product must only be used for the purpose described in these instructions and must be installed by a licensed electrician in accordance with the Building Code Australia (BCA) and local and state wiring rules and regulations.
Product Limitations
Caution! This device does not detect heat, gas or flame, and should not be
covered with a guard or similar obstructing item.
This device may not alert people who are hearing impaired. It is strongly
recommended that special-purpose smoke alarms using visual or vibrating
alerting devices be installed for occupants with a hearing impairment.
This device may not be effective in fires where smoke is prevented from
reaching the device (e.g., where intermediate doors are closed), where the
fire grows so rapidly that the egress path is blocked (even when correctly
located), and where the fire is intimate to a person (e.g., where a victim’s
clothes catch fire).
Sleeping Occupants
Studies have shown that smoke alarms may not awaken all sleeping occupants. It is the responsibility of individuals in the household who are capable of assisting others to provide assistance to those who may not be awakened by the alarm sound, or to those who may be incapable of safely evacuating the area unassisted.
Installation Limitations
This product is designed for use in a single residential unit, such as a family home or apartment. Smoke alarms located outside the dwelling may not provide adequate warning to occupants. This product is not designed for use in non-residential buildings. Non-residential buildings require special-purpose fire detection and alarm systems. This product alone is not a suitable substitute for a fire detection system installed in places of business or where people sleep on a temporary basis, such as hotels, motels, dormitories, hospitals, nursing homes, or group homes of any kind, even if they were once dwellings. Please refer to local and state regulations for fire detection and alarm system requirements for non-residential buildings and temporary accommodation settings
Overview
- SENSOR provides an online platform and ecosystem that allows 24/7 line of sight for real estate property managers to monitor the compliance of their properties.
- With round-the-clock monitoring without the need to physically visit the property, SENSOR mitigates the risk of the unknown.
- Using return pathway Internet of Things (IoT) devices installed at the property, SENSOR provides real-time device updates to meet legislative requirements and reduce the risk of property damage.
- Achieve legislative compliance and enhanced tenant safety with SENSOR’S range of smoke-detection sensors and alarms.
Introduction to the SENSOR 217E-02 Photoelectric Smoke Alarm
- The SENSOR 217E-02 Photoelectric Smoke Alarm works as an independent or interconnected photoelectric smoke alarm. When used in conjunction with the SENSOR Hub, an intuitive return pathway is created giving users access to monitoring, event logging, and remote testing via an IoT (Internet of Things) connection housed within the SENSOR Hub.
- Due to the advanced battery technology and low power consumption, each model of alarm in the 217E-02 series can be used to satisfy either the 230V or 10 year lithium requirement – depending on the applicable installation legislation or other local or state requirements.
- Each alarm connects to the SENSOR Hub independently of each other with a range of up to 200m line of sight.
- The 217E-02 model utilises a sealed lithium battery for both the operation of the alarm and the RF interconnect to the hub, ensuring no battery replacements are required over the life of the alarm.
The alarms are fitted with two test functions:
- The test button on the face of the alarm can be used to test the alarm if required.
- The alarm is also fitted with a software-based test which can be scheduled for a particular date and time or performed in real time via the portal.
The alarms are also fitted with several additional functions to ensure safety and compliance, including:
- Early low battery detection – designed to pre-empt a low battery alarm so it can be replaced prior to low battery beeping.
- Tamper detection – to ensure the alarms are always closed and operating correctly.
- RF disconnect warning – should an alarm become disconnected from the network a notification will be sent via the portal.
- 230V power outage – if power is lost to the alarm or hub a notification will be sent via the portal.
Disclaimers
All electrical installations must be carried out by a qualified electrician,
in accordance with local regulations and Australian Standards.
Connect and power the alarm with 220-240VAC only. The smoke alarm is suitable
for use with non-pure sinusoidal power sources. (e.g. Power derived from
square-wave inverters.)
It remains the duty of the installer to ensure that:
- All hardware is undamaged and in proper operating order,
- The correct number of alarms are being installed in compliant locations as per the local requirements.
This product must only be used for the purpose described in these instructions and must be installed by a licensed electrician in accordance with the Building Code Australia (BCA) and local and state wiring rules and regulations.
Understanding Indicator and Alarm Signals
Smoke alarms produce the following indicator and alarm signals, depending on their status condition
Specifications – Sensor 21E-02
Quiescent condition indication| Green LED continuously on, Red LED flashes
every 40s
Low battery indication| Short audible signal every 40 secs, synchronized with
a single flash of the yellow LED for 30 days
Low battery hush indication| Flashing yellow LED every 40 secs
Low Battery hush time| 10 hrs
Alarm Condition
Alarm condition audible indication output| ≥ 85 dB @ 3 mins three long beeps,
repeating
Alarm condition visual indication| Three blinks synchronized with audible
alarm
Alarm condition hush indicator| Device entering the alarm condition: Flashing
red LED every 1 sec
Alarm condition hush time| Smoke alarm: 8 mins
Test Condition
Test condition audible indication output| ≥ 85 dB @ 3 mins three long beeps,
repeating
Test condition visual indication| The yellow LED flashes once, then the red
LED flashes three times in two cycles
Fault Condition
Smoke chamber fault indication| Short audible signal every 40 secs,
synchronized with yelloe LED flashes three times
Smoke chamber fault hush indication| Three flashes of yellow LED every 40 secs
Smoke chamber fault hush time| 10 hours
Wireless Interconnection
Group mode connection indication on slave device(s)| Flashing yellow LED every
1 sec followed by a short audible signal
Interconnected Units
When configured as a group, interconnected units produce the following additional indicator and alarm signal when the primary unit is operated.
Alarm Condition
Alarm condition audible indication output| ≥ 85 dB @ 3 mins three long beeps,
repeating
Alarm condition visual indication| –
Test Condition
Test condition audible indication output| ≥ 85 dB @ 3 mins three long beeps,
repeating
Test condition visual indication| –
Fault Condition
Smoke chamber fault indication| Short audible signal every 40 secs
Installation Preparation
Equipment
Before commencing installation, ensure all equipment and tools to mount and
test the device are available, such as drills, mounting screws (supplied),
cables, and ladders.
Location Selection in Homes and Apartments
For complete coverage, alarms are to be installed in alignment with local,
state, and federal regulations. For enhanced coverage, alarms can be installed
in all rooms, halls, storage areas, basements, and attics in the dwelling.
Please use the following location guide.
Single Storey Dwellings
Install a smoke alarm in the hallway outside every separate bedroom area, as
shown in Fig. 1 a). Two smoke alarms should be installed in dwellings with two
bedroom areas, as shown in Fig. 1 b).
Multi-Storey Dwellings
Install a smoke alarm on every floor of a multi-floor dwelling, as shown in
Fig. 2.
Recommended Enhanced Safety
To improve early detection performance and safe evacuation, ensure that a
minimum of two alarms are installed per dwelling. Consider installing
additional alarms as follows:
- Inside every bedroom
- At both ends of a bedroom hallway if the hallway is more than 12 m
- Inside every room where one sleeps with the door partly or completely closed, since smoke could be blocked by the closed door, and a hallway alarm may not wake up the sleeper if the door is closed
- At the bottom of the basement stairwell
- On the second floor, at the top of the first-to-second floor stairwell
- In the living room, dining room, family room, attic, utility room, and storage rooms.
Installation Location
- Installation must adhere to all relevant local and state regulations. However, as a base guideline, alarms should be installed as close to the centre of the ceiling as possible, away from light fittings and air-conditioning ducts. If this is not practical, mount the alarm on the ceiling, no closer than 50 cm from any wall or corner:
- If some of your rooms have sloped, peaked, or gabled ceilings, try to mount alarms 0.9 m from the highest point of the ceiling measured horizontally. (see Fig. 3).
Where Not to Install Your Alarm
Nuisance alarms occur when alarms are installed where they will not work properly. To avoid nuisance alarms, do not install alarms in the following situations.
- In or near areas where combustion particles are present, such as kitchens with few windows or poor ventilation, garages where there may be vehicle exhaust, near furnaces, combustion heaters, and space heaters. Combustion particles are the by-products of something that is burning, which the alarm may detect. As a guide, aim to avoid installing an alarm within 6 m of kitchens where combustion particles are normally present. If a 6 m distance is not possible (e.g. in a mobile home), try to install the alarm as far away from the combustion particles as possible, preferably on the wall. Ensure the area is well ventilated.
- In dead air ceiling or wall spaces, which are often at the top of a peaked roof or in apex of ceilings and walls. Dead air may prevent smoke from reaching the alarm. See Fig. 3 for the recommended installation location in such situations.
Where Not to Install Your Alarm (ctd)
-
In other dead-air areas, where ventilation systems cause airflow that would not pass through the smoke sensing chamber. Also avoid airflow from areas where normal combustion articles are expected, such as kitchens. Refer to Fig. 4, which indicates the correct and incorrect alarm locations.
-
In damp or very humid areas, or within 3 m of bathrooms with showers. Moisture in humid air can enter the sensing chamber then condense into droplets upon cooling, which can cause nuisance alarms.
-
In very cold or very hot areas, including unheated buildings or outdoor rooms.
If the temperature rises above or falls below the operating range of the alarm, it may not function properly. The temperature range for your alarm is (0 – 55) 0 C. -
In very dusty or dirty areas. Dirt and dust can build up on the smoke sensing chamber, causing it to become overly sensitive. Additionally, dust or dirt can block openings to the sensing chamber and prevent the alarm from sensing smoke.
-
Near fresh air vents or high draft areas like air conditioners, heaters or fans, fresh air vents and drafts, which can drive smoke away from alarms.
-
In insect-infested areas. If insects enter the smoke sensing chamber, they may cause a nuisance alarm. Where insects are a problem, ensure that pest control measures have been undertaken before installing the alarm.
-
Near fluorescent lights. Electrical “noise” from fluorescent lights may cause nuisance alarms. Do not install alarms within 1.5 m of such lights.
Installation
This product must only be used for the purpose described in these instructions
and must be installed by a licensed electrician in accordance with the
Building Code Australia (BCA) and local and state wiring rules and
regulations. In the event of a mains powered installation this must be
completed by a licenced electrician and the power should be turned off prior
to commencing any installation or maintenance to avoid electric shock or
electrocution.
The following steps are for the purpose of installation of the SMOKE Alarm
ONLY. For full product suite installation including interconnectivity, please
refer to the SENSOR HUB Installation Guide
- Step 1. Identify a suitable location for the installation of the alarm.
- Step 2. Remove all packaging from the alarm (including the labelled tab in the clip of the alarm)
- Step 3. Using the hardware included affix the alarm in its desired location. Mains power must be used if required by legislation, otherwise the alarm can be used via battery power.
- Step 4. Close the alarm until it clicks.
- Step 5. Repeat this process with each alarm required.
What to do if the Alarm Sounds
-
Alert every person in the premises, paying particular care to alert any small children and elderly persons.
-
Leave immediately by your plan of escape. Every second counts, so don’t waste time getting dressed or picking up valuables.
-
When leaving, don’t open any inside door without first feeling its surface.
If the door feels hot or if you see smoke seeping through the cracks, don’t open that door! Instead, use your alternate exit. If inside door is cool, place your shoulder against it, open it slightly and be ready to slam it shut if heat and smoke rush in. -
Stay close to the floor if air is smoky. Breathe shallowly through a wet cloth if possible.
-
Once outside, go to your selected meeting place and make sure everyone is there.
-
Call the Fire Brigade on 000.
-
Don’t return to your home until officials say that it is safe to do so. For further information on fire safety contact your local Fire Brigade.
Testing
Regularly testing the alarm is imperative to ensure the proper function of the
alarm and the safety of all occupants. The testing of the 217E-02 alarm can be
by one of the following methods.
- A test will begin after pushing the test button for three seconds. This test will include the sounding of the alarm, and will trigger a test on all other alarms that are part of the RF network.
- A more in-depth test can also be triggered via the SENSOR portal. The additional tested functions tested via the portal include battery percentage, RF interconnection, and alarm volume.
- It is recommended that testing be completed at least once every twelve months
Good Practice – DEVELOP AN ESCAPE PLAN
Every family should formulate and regularly practice a fire escape plan.
Ensure that the plan is updated whenever a change is made to the structure of
the home, including the acquisition or repositioning of furniture or the
repurposing of rooms. A comprehensive fire escape plan should include:
-
The two quickest ways out of each room.
-
How to exit from upstairs, for homes with a second story. A rope or chain may be required.
-
An agreed upon meeting place outside, such as the letterbox.
-
Familiarity with the sound of the alarm, including a sense of urgency to leave the home
when the alarm is sounded. -
A fire drill at least every six months including drills at nights.
Practice allows you to test your plan before an emergency. Remember that you may not be able to reach your children. It is important that they know what to do in the event of a fire emergency.
Care and Maintenance of your SENSOR 217E-02 Photoelectric Smoke Alarm
To ensure the optimal performance of your SENSOR smoke alarms, please familiarise yourself with the following care and maintenance instructions.
Cleaning your SENSOR Smoke Alarm
- Cobwebs on or near the alarm can cause nuisance false positive alarm sounds.
- Ensure your alarm is always free from cobwebs by regularly vacuuming the smoke vent on the face of the alarm.
- Clean the alarm housing by wiping the alarm gently with a damp cloth to remove any dust, then dry the alarm thoroughly.
- The alarm housing must remain closed during cleaning.
- An open alarm is an electrocution risk.
- When your alarm is properly paired with a SENSOR Hub, you will be notified by the SENSOR platform when cleaning is required.
Disposal of product
This product is designed to work reliably for ten years after the installation
date. Smoke alarms and replaceable batteries should not be disposed of as
land-fill.
Please dispose in an environmentally friendly manner, for example at your
local authority recycling center.
Warning:
This is an important document. Retain it for the life of the device
Warranty
In order to protect your rights, please retain the original purchase receipt
for the proof of purchase. No warranty can be offered without the original
purchase receipt. Sensor Pty Ltd(“Sensor”), warrants the enclosed product to
be free from defects in materials and workmanship under normal use and service
for a period of five years from date of purchase. This LIMITED WARRANTY is the
sole and exclusive warranty, express or implied for Sensor products. No
employee, agent, dealer or other person is authorized to alter, modify, expand
or reduce the terms of this warranty or to make any other warranty on behalf
of Sensor. Sensor’s obligation of this Warranty shall be limited to the repair
or replacement of any part of the product which is found to be defective in
materials or workmanship under normal use and service during the Warranty
Period. Products in need of repair should be returned, shipping prepaid, to
the point of purchase.
Sensor shall not be obligated to repair or replace units that are found to be
in need of repair because of damage, unreasonable use, modifications, or
alterations occurring after the date of purchase. The duration of any implied
Warranty, including that of merchantability or fitness for any particular
purpose, shall be limited to the period of five years commencing from the date
of purchase. In no case shall Sensor be liable for any consequential or
incidental damages for breach of this or any other Warranty expressed or
implied whatsoever, even if the loss or damage is caused by Sensor’s
negligence or fault. Some jurisdictions do not allow the exclusion or
limitation of incidental or consequential damages, so the above limitation or
exclusion may not apply to you. This Warranty gives you specific legal rights,
and you may also have other rights which vary from jurisdiction to
jurisdiction.
Due to Sensors continual product development, we reserve the right to alter
product details and specifications without prior notice.
© Sensor Global (Wholesale) Pty Ltd 2023
SENSORGLOBAL.COM
ABN 50 642 017 767
7/3 Koala Crescent, West Gosford, NSW 2250, AUSTRALIA
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>