GIRA 5061 00 One Switching Actuator 1-gang 16 A Instruction Manual

June 10, 2024
GIRA

GIRA 5061 00 One Switching Actuator 1-gang 16 A Instruction Manual
GIRA 5061 00 One Switching Actuator 1-gang 16 A

Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons.

  • Serious injuries, fire or property damage possible.
    Please read and follow manual fully.

  • Danger of electric shock.
    Device is not suitable for disconnection from supply voltage.

  • Danger of electric shock.
    Make sure during the installation that there is always sufficient insulation between the mains voltage and the bus.
    A minimum distance of at least 4 mm must be maintained between bus conductors and mains voltage cores.
    Danger of electric shock on the installation.
    Do not connect any external voltage to the inputs.
    The device might be damaged, and the SELV potential on the bus line will no longer be available.

  • This manual is an integral part of the product, and must remain with the end customer.

Device components

  1. Programming LED
  2. Programming button
  3. Control cable (bus connection and extension inputs)
  4. Load connection (relay output)
    **Image 1: Device components

**

Image 2: Connection assignment of control cable (example)
Device Components

  • red (RD): KNX / One +
  • black (BK): KNX / One –
  • green (GN): Input 1 (push-button, switch, contact, condensation/leakage sensor)
  • yellow (YE): Input 2 (push-button, switch, contact, condensation/leakage sensor)
  • white (WH): Input 3 (push-button, switch, contact, condensation/leakage sensor, NTC temperature sensor)
  • brown (BN): COM inputs 1…3

Function

System information
This device is a product for the Gira One Smart Home system.
The Gira One system is commissioned easily and in a time-saving manner using the Gira Project Assistant.
The Gira One Smart Home system enables the control and automation of lighting, heating and shading, as well as connection to various third-party systems and much more.
It can be operated via Gira One switches, by app from home or securely from a remote location.
Electrically skilled persons can maintain the Gira One project remotely free of charge.
Data transmission between the Gira One devices is encrypted.
This provides protection against third-party access and manipulation.
Commissioning is carried out with the free Gira Project Assistant (GPA), version 5 or higher.
Free function and security updates are also transferred to the Gira One devices with the GPA.
The Gira One system is based on the globally proven KNX smart home standard.

Intended use

  • Operation in Gira One system
  • Switching of electrical consumers via relay contact
  • Reading in switching states of installation switches or push-buttons and other potential-free contacts at inputs 1…3
  • Signal evaluation of condensation and leakage sensors at inputs 1…3 (see accessory).
  • Acquisition of temperature values via NTC temperature sensor at input 3 (see accessories)
  • Mounting in appliance box with dimensions according to DIN 49073

Product characteristics

  • Output can be operated via the Gira One system or extension inputs

  • Three extension inputs for connecting potential-free contacts or dew/leakage sensors.
    NTC temperature sensor can be connected to input 3.

  • Supply via the bus, no additional supply voltage necessary

  • Programming and commissioning with the Gira Project Assistant (GPA), version 5 or higher

  • Updating via the Gira Project Assistant (GPA)

  • Encrypted data transmission between the Gira One devices

Characteristics switch operation

  • Operation as NO or NC contacts
  • Setting of a switch-on or switch-off delay
  • Staircase function for which a pre-warning time can additionally be set.
  • Configuration as a switching function, e.g. for a light or sockets, as a garage door function or door opener function, and as a switching contact for transmission of the heat requirement to a heat pump.
  • Garage door function: The time for closing the relay can be configured.
  • Door opener function: The time for closing the relay can be configured.

Extension input characteristics

  • Single or dual-area operation can be configured for rockers.
  • Connection of rockers that are configured with the function for switching, dimming, shading and ventilation, scene recall, staircase (motion detector), floor call with Gira G1, garage door and door opener.
  • Connection of motion and presence detectors with potential-free relay outputs.
  • Convenient group control of switching, dimming, shading and ventilation loads.
  • Switching contact evaluation of wind, frost, brightness or rain sensors with potential-free relay outputs possible in order to protect shading and ventilation loads against environmental influences.
  • Window contact polling and visualization in the Smart Home app: An open window leads to the frost protection heating mode after a configured time has elapsed.
  • Door contact polling and visualization in the Smart Home app: An open door leads to the Venetian blind or shutters being raised and locked.
  • Polling of a switch-over between heating/cooling at a heat pump in order to be able to forward the current operating mode (heating or cooling) to a heating controller.
  • Switching contact indicator for displaying a contact state in the Smart Home app.
  • Configurable switching inputs that can be parameterized independently.
  • Acquisition and calibration of temperature values via remote sensors (see accessories) at input 3.

Information for electrically skilled persons

DANGER!
Electric shock when live parts are touched.
Electric shocks can be fatal.
Always disconnect device before working on it.
For this, switch off all corresponding circuit breakers, secure against being switched on again and check that there is no voltage.
Cover up adjacent live parts

Mounting and electrical connection

DANGER!
When connecting the bus/extensions and mains voltage wires in a shared appliance box, the bus line may come into contact with the mains voltage.
This endangers the safety of the entire installation.
People at remote devices may also receive an electric shock.
Do not place bus/extensions and mains voltage terminals in a shared connection compartment.
Use an appliance box with a fixed partition wall or separate appliance boxes.

Connecting and fitting the device

  • Enter or scan the device certificate and add it to the project. A high resolution camera should be used to scan the QR code.
  • The device certificate should be removed from the device during mounting.
  • Document all passwords and keep them safe.
    Mounting in suitable appliance box (recommendation: electronic device box with partition).
    Observe cable routing and spacing (see figure 3)!
    **Image 3: Mounting example in electronic appliance box with partition wall, series push-button and NTC temperature sensor

(5) Appliance box
(6) Partition
(7) potential-free contacts (e.g. series push-button)
(8) NTC temperature sensor (optional)
Image 4: Cable spacing
Cable Spacing
Minimum spacing between the mains voltage and bus/extension wires: 4 mm (see figure 4)
Image 5: Connection of load

**

Observe ambient temperature. Ensure adequate cooling.

  • Connect bus line, observing the correct polarity.
  • Connect load as shown in the connection example (see figure 5).
  • If required, connect potential-free contacts or condensation/leakage sensors to inputs 1…3, or NTC temperature sensors to input 3 (see figure 2).
  • Install the device in the appliance box.
    The COM reference potential must not be connected together with COM connections of other devices!
Commissioning

Commissioning the device

NOTICE!
Incorrect load control due to undefined relay state at delivery.
Unexpected control of connected loads.
During commissioning, before switching on the load, ensure that all relay contacts are open by applying the bus voltage.
Observe commissioning sequence!

  • Switch on the bus voltage.
  • Wait about 10 s.
  • Connect the load circuit.
    Delivery state: Operation of the output via switch at input 1 (ON / OFF) possible.
    Inputs 2 and 3 have no function.

Function of Inputs in the as-delivered state

Input Switch Function
1 closed ON
1 open OFF
2
3

The device is commissioned with the Gira Project Assistant (GPA) version 5 or higher.

Safe-state mode
The safe-state mode stops the execution of the program.
Only the system software of the device is still functional.
Diagnosis functions and programming of the device are possible.

Activating safe-state mode

  • Switch off the bus voltage or disconnect the device from the bus.
  • Wait about 10 s.
  • Press and hold down the programming button.
  • Switch on the bus voltage or connect the bus again at the device.
    Release the programming button only after the programming LED starts flashing slowly.
    The safe-state mode is activated

Deactivating safe-state mode

  • Switch off the bus voltage (wait approx. 10 s) or carry out programming

Master reset
The master reset restores the basic device settings (firmware remains in place).
The device must then be recommissioned with the GPA.

Performing a master reset
Precondition: The safe-state mode is activated.

  • Press and hold down the programming button for > 5 s.
    The programming LED flashes quickly.
    The device performs a master reset, restarts and is ready for operation again after approx. 5 s.

Technical data

Rated voltage DC 21 … 32 V SELV
Current consumption 5 … 18 mA
Connection mode Device connection terminal on control cable

Outputs
Connection mode| Screw terminals
Switching voltage| AC 250 V ~
Switching current| 16 AX
Switch-on current 200 μs| max. 800 A
Switch-on current 20 ms| max. 165 A
Connected load
Ohmic load| 2500 W
Capacitive load| max. 16 A (140 μF)
Motors| 1380 VA
Incandescent lamps| 2300 W
HV halogen lamps| 2300 W
HV-LED lamps| max. 400 W
LV halogen lamps with electronic transformers| 1500 W
LV halogen lamps with inductive transformer| 1200 VA
Compact fluorescent lamps uncompensated| 1000 W
Compact fluorescent lamps parallel compensated| 1160 W (140 μF)
Reduction of connected load
per 5 °C in excess of 35 °C| -10%
when installed in wooden or dry construction walls| -15%
when installed in multiple combinations| -20%
Clampable conductor cross-section
Single stranded| 0.5 … 4 mm²
Finely stranded without conductor sleeve| 0.5 … 4 mm²
Finely stranded with conductor sleeve| 0.5 … 2.5 mm²
Connection torque, screw terminals| max. 0.8 Nm
Ambient conditions
Ambient temperature| -5 … +45 °C
Storage/transport temperature| -25 … +70 °C
Dimensions (W × H × D)| 48 x 50 x 28 mm
Inputs
Control cable (pregerminated| YY6x0.6
Input type| Potential-free
Number| 3
Total length of extension device cable| max. 10 m
Cable type (preferably)| J-Y(St)Y
Poll voltage, extension inputs| approx. 5 V

Accessories

  • Remote sensor (NTC temperature sensor): 1493 00
  • Condensation sensor: 5069 00
  • Leakage sensor: 5068 00

Parameter list

Parameters that can be set via the GPA:

Output

Function of the switching output| NO contact
NC contact
---|---
NO contact
The relay works as an NO contact. The logical switching state of the switching out- put is not forwarded to the relay in inverted form.
Switching state = OFF (“0”) -> relay contact open, Switching state = ON (“1”) -> relay contact closed. NC contact
The relay works as an NC contact. The logical switching state of the switching output is forwarded to the relay in inverted form.
Switching state = OFF (“0”) -> relay contact closed,
Switching state = ON (“1”) -> relay contact open.
Switch-on delay| 0 … 3599 s (0 … 59:59 min)
---|---
This parameter is used for setting the duration of the switch-on delay.
After receipt of an ON-telegram, the time that can be configured here is started.
The lamp is switched on after the set time has elapsed.
A further ON-telegram during the switch-on delay time re-triggers the time, i.e. the time set here is started again.
An OFF-telegram received during the ON-delay will end the delay and sets the switching status to “OFF”.
Switch-off delay| 0 … 3599 s (0 … 59:59 min)
---|---
This parameter is used for setting the duration of the switch-off delay.
After receipt of an OFF-telegram, the time that can be configured here is started.
The lamp is switched off after the set time has elapsed.
A further OFF-telegram during the switch-off delay time re-triggers the time, i.e. the time set here is started again.
An ON-telegram received during the OFF-delay will end the delay and sets the switching status to “ON”.
Staircase switch Switch-off delay| 0 … 3599 s (0 … 59:59 min)
---|---
The duration of the switch-on time for the staircase function is configured here.
Once the time set here has elapsed, the lighting is switched off or (if configured) the pre-warning time is started.
The staircase function is only active if the function “Staircase” has been selected for the push-button of this dimming channel.
Pre-warning time| 0 … 3599 s (0 … 59:59 min)
---|---
In accordance with DIN 18015-2, the pre-warning is intended to warn persons still on the staircase that the light will soon be switched off automatically.
The pre-warning time set here is added to the time set in the parameter “Staircase switch switch-off delay”.
Switching time| 0 … 65535 s (0….. 18.20 h)
---|---
The switching time in seconds can be specified here.

Input

Debounce time 10 … 255 ms

This parameter sets the denouncing time individually for the input.
According to the time set here, the input signal at the input is evaluated with a delay.
Contact type| NO contact

NC contact

---|---
The contact type of the connected contact is defined here.
When closing the contact| No reaction Switch on Switch off Toggle
---|---
This parameter determines the reaction when the contact connected to the input is closed.
When opening the contact| No reaction Switch on Switch off Toggle
---|---
This parameter determines the reaction when the contact connected to the input is opened.
Temperature calibration| – 12.8….. 12.7 K
---|---
The value for the temperature calibration can be entered here if the temperature measured by the connected sensor differs from the actual room temperature.
To determine the temperature deviation, the actual room temperature should be de- tected with a reference measurement using a calibrated temperature measuring device.
The measured value must be raised if the value measured by the sensor is below the actual temperature. The measured value must be lowered if the value measured by the sensor is above the actual temperature.

Warranty

The warranty is provided in accordance with statutory requirements via the specialist trade.
Please submit or send faulty devices postage paid together with an error description to your responsible salesperson (specialist trade/installation company/electrical specialist trade).
They will forward the devices to the Gira Service Center.

Gira
Giersiepen GmbH & Co. KG
Elektro-InstallationsSysteme
Industriegebiet Mermbach Dahlienstraße
42477 Radevormwald
Postfach 12 20
42461 Radevormwald

CUSTOMER SUPPORT

Deutschland
Tel +49(0)21 95 – 602-0
Fax +49(0)21 95 – 602-191
www.gira.de
info@gira.de