For your safety
Installation and mounting of electrical devices may only be carried out by qualified electricians. Serious injury (e.g. caused by an electric shock), fire, or material damage are possible in case of improper mounting.
Configuration and installation may only be performed by an expert.
As per EN 14676, the configuration and installation of the smoke alarm device
may only be performed by a qualified expert. For this purpose, Gira offers the
“Certified expert for smoke alarm devices in accordance with DIN EN 14676”
online course, complete with certificate. Additional information can be found
under “akademie.gira.de”.
Briefing and transfer of the instructions
Explain all the functions of the product to the end user or their
representative. These instructions are part of the product and must be
transferred to the end user or their representative for safekeeping.
Inadmissible installation locations
The Basic Q smoke alarm device is not suitable for installation in caravans,
campers, boats etc.
Product features
The smoke alarm device Basic Q is a battery operated smoke alarm device for private residential units or similarly inhabited areas as per DIN 14676. The smoke alarm device detects the development of smoke in a timely manner and warns occupants before the smoke gas concentration becomes dangerous. The warning comes in the form of an acoustic signal.
Product features
- Loud, pulsating alarm signal (min. 85 dB (A))
- Smoke detection using the photoelectric scattered-light principle
- Integrated function button for function test
- Soiling/fault display
- Permanently installed, non-removable battery
- Q-Label
Scope of supply
- 1x smoke alarm device Basic Q
- 1x set of mounting hardware
- 1x installation and operating instructions
Device description
- Mounting plate
- Activation slider
- Smoke alarm device
- Smoke penetration openings
Selecting installation site
When selecting the installation site for the smoke alarm device, the
specifications of DIN EN 14676 apply. The most important specifications are as
follows:
- Attach as close as possible to the centre of the ceiling (min. distance of 50 cm from walls, lights and other obstructions)
- One smoke alarm device per room (max. 60 m2 area)
- do not install in direct proximity of heat sources
System description of smoke alarm devices
More detailed information with regard to installation as per DIN EN 14676 can be found in the “System description of smoke alarm devices”, which is available in the Gira download area ( www.gira.de/service/download ).
Minimum protection/optimum protection
The following applies for flats and houses:
Minimum protection
- One smoke alarm device in every bedroom, every child’s room and in the hallway/staircase (escape route).
- In the case of open space across two levels, a smoke alarm device is to be installed on the highest level.
- In the case of buildings spanning several storeys, a smoke alarm device is to be installed on each storey.
Optimum protection
- One smoke alarm device per room and floor
- In the case of larger buildings, use networked smoke alarm devices
- Use specialised alarm devices (e.g. heat detectors) in sensitive areas.
Deceptive alarm
Some sites are unsuitable for the installation of a smoke alarm device as
deceptive alarms are repeatedly triggered due to local conditions (e.g.
welding/soldering work, very heavy water/cooking vapour and similar fumes).
More detailed information with regard to unsuitable installation sites can be
found in the “System description of smoke alarm devices”.
Installing smoke alarm device
Install the smoke alarm device as described in the following.
- Install the mounting plate.
- Activate the smoke alarm device.
Activation/deactivation
The activation slider is protected against being pushed in inadvertently at
the factory. Remove the guard and slide the activation slider (grey) into the
guide completely. The smoke alarm device is now activated. Deactivation is
carried out in the reverse order.
Place the activated smoke alarm device onto the mounting plate and lock it there (turn clockwise). Removal is carried out in the reverse order. Perform the function test (see “Function test”).
Installation position
The smoke alarm device can only be installed in a certain position. A locking
pin is found on the mounting plate for this purpose. It ensures that the smoke
alarm device is locked properly. Before locking, you must slide the activation
slider into the smoke alarm device. Disregarding this could cause the smoke
alarm device to tilt on the mounting plate. At that point, an extreme exertion
of force would be required for its removal.
Function button
The smoke alarm device Basic Q features an easy-access function button (grey).
The following actions can be initiated:
Function test.
Function test
The function test should be conducted:
- After the initial installation
- After every alarm, maintenance session and fault message
Risk of permanent hearing loss due to the loud signal tone
The loud signal tone (min. 85 dB (A)) emitted during the function test can lead to a permanent loss of hearing (e.g. tinnitus). Maintain a distance of at least 50 cm from the smoke alarm device during the function test.
Performing function test
Perform the function test as follows:
- Press and hold the function button for approx. 4 s. A loud signal tone is emitted, and the ring indicator flashes.
- Release the function button. The signal tone is muted and the ring indicator goes out.
Function test failure
Replace the smoke alarm device immediately if it fails the function test two
times in a row. Non-operational smoke alarm devices may not be installed.
Smoke alarm devices save lives
Observe the following when using smoke alarm devices:
- Use only smoke alarm devices which are compliant with DIN EN 14604.
- Never cover smoke alarm devices continuously, block them with objects or paint them.
- Never install smoke alarm devices if they are defective or not fully operational.
Operating and alarm signals
Problem | Solution |
---|---|
No signal can be heard during the function test | Check activation slider |
Frequent deceptive alarms | Check installation |
site for interference sources
Clean smoke alarm
device
Acknowledging alarm/deceptive alarm
If the smoke alarm device has triggered an alarm and a deceptive alarm has been identified as the culprit, you can acknowledge the alarm message by pressing the function button. Then ensure that the cause of the deceptive alarm has been eliminated.
Care and maintenance
Maintain and care for the smoke alarm device on a regular basis to ensure full
operability.
Care
Wipe the smoke alarm device with a moist (not wet!) cloth on a regular basis.
You can also carefully remove dust from the smoke alarm device with a vacuum
cleaner (lowest setting).
Maintenance
Maintenance and duty to maintain
As per DIN EN 14676, you are required to have smoke alarm devices maintained
by a qualified expert. Observe the following: If this required maintenance is
not carried out, insurance coverage may be nullified in case of fire.
Maintenance book for smoke alarm devices
Gira offers the “Maintenance book for smoke alarm devices” in the download area. All the important data for the initial installation and subsequent maintenance can be entered here.
Renovation work
If possible, do not install the smoke alarm device until all renovation work has been completed. Should this not be possible, you can remove the smoke alarm device for the period of work as an alternate option. After completing all the work, carry out a function test.
Disposal
Dispose of the smoke alarm device by the date indicated on the device’s label
or when the battery is flat.
DANGER
There is a risk of explosion if the battery is removed forcibly! The
battery in the smoke alarm device cannot be replaced.
An explosion can occur if damage is caused by forcibly removing the battery
from the device. The entire smoke alarm device must always be disposed of. The
Gira smoke alarm device is an electric and electronic device in the sense of
EU guideline 2002/96/EC.
High-quality materials and components were used in developing and manufacturing the device. These materials and components can be reused and recycled. Please consult the regulations governing the separate collection of electric/electronic waste valid for your country. These devices may not be disposed of with household waste. The correct disposal of waste can prevent possible negative consequences to the environment and humans.
Technical data
- Power supply: Via smoke alarm device battery
- Battery life: Up to 10 years (after activation)
- Acoustic alarm signal: Min. 85 dB (A)
- Optical display: Ring indicator (red LED)
- Operating temperature: -5 °C to +55 °C
- Storage temperature: -20 °C to +65 °C
- Installation height: Max. 6 m
- Protection type: IP 42
- Housing dimensions: 110 x 40 mm (dia. x h)
- Weight: Approx. 250 g
- Area of application: As per DIN 14676
Declaration of performance
The Declaration of performance according to Directive (EC) No. 765/2008,
Directive (EU) No. 305/2011 can be found either in the download area
(gira.de/Konformitaet) or directly via the online catalogue at the product (
katalog.gira.de ).
Warranty
The warranty is provided in accordance with statutory requirements via the
specialist trade. Please submit or send faulty devices postage paid together
with an error description to your responsible salesperson (specialist
trade/installation company/ specialist electrical trade). They will forward
the devices to the Gira Service Center.
Q-Label and warranty
The Q-label has no effect on the legal warranty.
Gira
Giersiepen GmbH & Co KG
Electrical installation systems
P.O. Box 1220
42461 Radevormwald
Phone +49 (0) 2195 602 – 0
Fax +49 (0) 2195 602 – 191
info@gira.de
www.gira.de
Documents / Resources
| GIRA
1149 02 Smoke Alarm Device Basic
Q
[pdf] Instruction Manual
1149 02 Smoke Alarm Device Basic Q, 1149 02, Smoke Alarm Device Basic Q, Alarm
Device Basic Q, Device Basic Q, Basic Q
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>