GIRA 1493 00 Remote Sensor Instruction Manual

June 4, 2024
GIRA

GIRA 1493 00 Remote Sensor

Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons.

The danger of electric shock. Depending on the room temperature controller, the sensor cable is connected to the mains voltage potential. If the sensor cable is damaged, disconnect the device immediately and replace the sensor cable.
Serious injuries, fire or property damage are possible. Please read and follow the manual fully.

Intended use

  • External sensor for measuring ambient temperature
  • Connection to a suitable room temperature controller

Mounting and electrical connection

DANGER!
Mortal danger of electric shock.
Before working on the device or performing an installation, disconnect all the corresponding circuit breakers. Cover up live parts!

The remote sensor must be mounted in an empty tube so that the sensor is mechanically protected and can be exchanged if necessary.

Technical data

  • Dimensions Ø×H 7.8 × 27 mm
  • Sensor cable S03VV-F 2 x 0.5 mm²
  • Length connecting cable 4 m
  • Degree of protection IP 67

Remote sensor resistance values

Temperature

(°C)

| Resistance

(kΩ)

|  | Temperature

(°C)

| Resistance

(kΩ)

---|---|---|---|---
5| 89.5|  | 30| 26.2
10| 68.8|  | 35| 20.9
15| 53.5|  | 40| 16.7
20| 41.9|  | 45| 13.5
25| 33.0|  | 50| 11.0

The resistance values can only be measured if the sensor is disconnected.

Gira
Giersiepen GmbH & Co. KG Elektro-Installations-Systeme
Tel +49(0)21 95 – 602-0 Fax +49(0)21 95 – 602-191
www.gira.de [email protected] 

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

GIRA User Manuals

Related Manuals