GIRA 1493 00 Remote Sensor Instruction Manual
- June 4, 2024
- GIRA
Table of Contents
GIRA 1493 00 Remote Sensor
Safety instructions
Electrical devices may only be mounted and connected by electrically skilled persons.
The danger of electric shock. Depending on the room temperature controller,
the sensor cable is connected to the mains voltage potential. If the sensor
cable is damaged, disconnect the device immediately and replace the sensor
cable.
Serious injuries, fire or property damage are possible. Please read and follow
the manual fully.
Intended use
- External sensor for measuring ambient temperature
- Connection to a suitable room temperature controller
Mounting and electrical connection
DANGER!
Mortal danger of electric shock.
Before working on the device or performing an installation, disconnect all the
corresponding circuit breakers. Cover up live parts!
The remote sensor must be mounted in an empty tube so that the sensor is mechanically protected and can be exchanged if necessary.
Technical data
- Dimensions Ø×H 7.8 × 27 mm
- Sensor cable S03VV-F 2 x 0.5 mm²
- Length connecting cable 4 m
- Degree of protection IP 67
Remote sensor resistance values
Temperature
(°C)
| Resistance
(kΩ)
| | Temperature
(°C)
| Resistance
(kΩ)
---|---|---|---|---
5| 89.5| | 30| 26.2
10| 68.8| | 35| 20.9
15| 53.5| | 40| 16.7
20| 41.9| | 45| 13.5
25| 33.0| | 50| 11.0
The resistance values can only be measured if the sensor is disconnected.