GIRA 234700 Radio Module for Smoke Alarm Device Dual Instruction Manual

June 5, 2024
GIRA

GIRA 234700 Radio Module for Smoke Alarm Device Dual

GIRA-234700-Radio-
Modulefor-Smoke-Alarm-Device-Dual-PRODUCT

For your safety

Improper electrical installations can result in serious material damage or injuries, e.g. due to fire or an electric shock. The safe electrical installation can only be guaranteed when performed b individuals who can verify their basic knowledge in the following areas:

  • Connecting to installation networks
  • Combining more than one electrical device
  • Laying electrical cable In general, only qualified professionals in the field of electrical installation technology possess this knowledge and experience.

If these minimum requirements are not fulfilled or disregarded, there is a risk o personal liability for material damage and injury.

Configuration and installation may only be performed by an expert

As per DIN EN 14676, configuration, installation, and maintenance of the smoke alar device may only be performed by a qualified expert. For this purpose, Gira offers the “Certified expert for smoke alarm devices in accordance with DIN EN 14676” online course, complete with certificate. More detailed information can be found under “akademie.gira.de”.

These instructions are part of the product and must remain with the end customer.

Product features

The radio module for smoke alarm device Dual (hereinafter referred to as the “radio module”) enables the wireless network of smoke alarm devices Dual Q in the Gira radio bus system.

  • The networking terminals of the smoke alarm device Dual can still be used when the radio module is attached. This allows combined wired-radio networking to be established.
  • In case of alarm: It is possible to mute a local smoke detection alarm using a radio remote control or radio wall transmitter.
  • The radio range can be extended with repeater mode in the radio module.
  • Up to 40 smoke alarm devices can be networked.
  • The radio module is downward compatible, which means it can also be used for the smoke alarm device Dual/VdS.

Device description

  1. Battery compartment with battery
  2. Radio module
  3. Programming button with LED
Inserting the radio module

Smoke alarm device Dual Q

  • Please see the installation and operating instructions of the smoke alarm device
  • Dual Q for all the information on the smoke alarm device Dual Q (e.g. installation, signals, etc.)

The radio module is inserted as follows:

  1. Insert the radio module with the connection pins into the module interface (1) of the smoke alarm device until the module engages.

Assigning the radio module

Radio modules have to be assigned in order to communicate with one another (a transmitter or receiver).

The following assignments are possible:

  • Setting up a radio-networked group\ (initial setup)
  • Assigning the radio module to a radionetworked group of smoke alarm devices Dual Q (expansion)
  • Assigning the radio module to a radionetworked group of smoke alarm device Dual/VdS (replacing obsolete systems)
  • Deleting all assignments

Activating and exiting programming mode

The following describes how to activate and exit the programming mode on the radio module.

Activating programming mode

  • Press the Prog. button (for approx. 4 s) until the programming LED flashes.
  • The programming model is activated for approx 1 min.

Exiting programming mode

  • The programming mode ends automatically when 1 min has elapsed.
  • Alternatively, you can briefly press the Prog. button.

Radio-networked group

  • Radio modules can only communicate with each other within a group. A radionetworked group must be set up for this purpose.

Radio-networked group

The following smoke alarm devices can b set up as radio-networked groups:

Dual Q <-> Dual Q

  • Dual Q <-> Dual/VdS

Observe the maximum distance in programming mode

Radio transmitters and receivers must be positioned at a maximum distance of 5 m from each other in programming mode.

Setting up a radio-networked group (initial setup)

  1. Insert the radio modules in all smoke alarm devices Dual Q that should belong to a group.
  2. Activate programming mode on all radio modules.
  3. Repress the Prog. button (approx. 4 s) on any smoke alarm device Dual Q in the group until a signal tone is emitted.
  4. All LEDs light up continuously: the group has been set up.
  5. Exit programming mode.

As soon as one smoke alarm device in the group detects smoke or increased temperature and triggers an alarm, all other smoke alarm devices in the group are also triggered.

Assigning the radio module to a radionetworked group of smoke alarm devices Dual Q (expansion)

A radio-networked group of smoke alarm devices Dual Q can be expanded until reaching the maximum number (40 units).

  1. Lay out a smoke alarm device Dual Q (#1) which has already been assigned.
  2. Insert the radio module in the smoke alarm device Dual Q (#2) which has not yet been assigned.
  3. Activate programming mode on the two radio modules.
  4. Repress the Prog. button (approx. 4 s) of the radio module on smoke alarm device #1 until a signal tone is emitted. The LEDs of both radio modules light up continuously, and an additional radio module has been added to the group.
  5. Exit programming mode.

Assigning the radio module to a radio networked group of smoke alarm devices Dual/VdS (replacing obsolete systems)

You can assign a smoke alarm device Dual Q with radio module to an existing group of smoke alarm devices Dual/VdS with radio modules (e.g. replacing an obsolete device).

  1. Activate programming mode on the radio module of any smoke alarm device Dual/VdS.
  2. Activate programming mode on the radio module of the smoke alarm device Dual Q.
  3. Press the function button of the smoke alarm device Dual/VdS.
  4. All LEDs light up and the new radio module is assigned to the existing group of smoke alarm devices Dual/VdS.
  5. Exit programming mode.

Radio module in repeater mode

  • In the state of delivery, repeater mode is deactivated in the radio module.
  • Repeater mode is activated whenever one or more smoke alarm devices no longer receive signals via radio (or reception is poor).

Radio module as a repeater

  • Only one radio module may be activated as a repeater per group.
  • All networked smoke alarm devices must be reachable via the radio range. As a repeater, the radio module also receives weaker radio telegrams and forwards them with maximum output.

Activating repeater mode

  1. Select one of the group’s centrally installed smoke alarm devices.
  2. Press the Prog. the button of the radio module on the selected smoke alarm device for 10 s.
  3. After approx. 4 s the LED flashes.
  4. After approx. 10 s the LED flashes faster.
  5. Repeater mode is now activated.
  6. Exit programming mode.

Deactivating repeater mode

Activated repeater mode can be deactivated at any time.

  1. Select the smoke alarm device with activated repeater mode.
  2. Press the Prog. the button of the radio module for 10 s.
  3. After approx. 4 s the LED flashes. After approx. 10 s the LED flashes more slowly. Repeater mode is deactivated.
  4. Exit programming mode.

Deleting all assignments

To reset radio modules to factory settings, all assignments (to groups, as repeaters, etc.) must be deleted.

  1. Activate programming mode.
  2. Release the Prog. button.
  3. Repress the Prog. the button of the radio module (approx. 10 s).
  4. A brief signal tone is emitted after approx. 4 s.
  5. After approx. 10 s, a longer signal tone is emitted and the programming LED lights up continuously.
  6. All assignments have been deleted.
  7. Exit programming mode.

Checking the networking of the smoke alarm device

The radio networking of the smoke alarm device can be checked prior to installation.

  1. Manually activate the smoke alarm: Press and hold the internal activation button (initialization phase approx. 30 s). Do not release the activation button during the test!

The signal transmitter of the smoke alarm device was muted in the test mod

  1. When the test function is active, the signal transmitter of the smoke alarm device is muted.
  2. Trigger the test alarm on the smoke alarm device
  3. When the alarm message is received, the programming LED of the radio module continuously lights up. The radio module is correctly assigned.
  4. Briefly press the Prog. button: test mode is exited..

Performing function test

  • The function test is a manual test of the smoke alarm device.

Function test of the smoke alarm device

  • Observe all notes for performing a function test of the smoke alarm device Dual Q in the installation and operating instructions of the smoke alarm device Dual Q.

Delayed signaling of the radio module

  1. The radio module checks the reception of alarm messages every 60 s. Therefore, it may take up to 60 s until the radio module acknowledges reception.
  2. Initiate the function test on the smoke alarm device. After 5 s the signal tone is emitted and the ring indicator flashes.
  3. All other radio-networked smoke alarm devices only emit an acoustic alarm (after 60 s at the most).

Radio transmission

Radio transmission occurs on a nonexclusive transmission path so interference cannot be excluded. Radio transmission is not suitable for security purposes (e.g. emergency stop, emergency call). The range of the radio system depends on transmitter power, the reception characteristic of the receiver, humidity, installation height, and the building itself Examples for material penetration:

Dry material Penetration

Wood, plaster,

sheetrock

|

approx. 90%

Brick, pressboard| approx. 70%
Reinforced concrete| approx. 30%
Metal, metal grids,

aluminum cladding

|

approx. 10%

Rain, snow| approx. 0-40%

Replacing the batter

The “low battery” signal is indicated by three beeps every 30 s.

  1. Remove the smoke alarm device from the mounting plate or 230 V base.
  2. Open the battery cover of the radio module and remove the battery.
  3. Replace the empty battery with a new one at the same time (see technical data) and close the battery cover again.
  4. Remount the smoke alarm device. Wait for the initialization phase (approx. 30 s) to finish. The wireless module continues to signal “low battery”.
  5. Perform a test alarm on the Dual Q smok alarm device After completion of the test alarm, the wireless module transmits “Battery OK status for 30 s. The networked smoke alarms receive the new signal and adopt it.

For “weak battery”, the signaling (without alarm) behaves as follows:

  • 3 short beeps every 30 s from the smoke alarm trigger the “weak battery”.
  • 2 short beeps every 10 mins from the networked smoke alarm.

Wirelessly networked smoke alarm signals incorrectly

Under certain conditions (e. g. bad wireless signal) a wirelessly networked Dual Q smoke alarm may continue to signal “low battery” even after the battery in the wireless module of the triggering Dual Q smoke alarm has been replaced and the status was changed. Activate the mute function of the incorrectly signaling Dual Q smoke alarm. After unmuting (manually or automatically after 15 min), the previous “Low battery” signal has been reset and the Dual Q smoke alar no longer signals “Low battery”.

Remove empty batteries immediately and dispose of them in an environmentally- friendly way. Do not dispose of batteries with household waste. Local authorities provide information about environmentally-sound disposal. The end consumer is legally required to return used batteries in accordance with legislative requirements.

Technical data

  • Power supply: from a battery of the radio module
  • Batter Type: 2/3 AA lithium
  • Capacity: 3 V
  • Transmission frequency: 433.42 MHz, ASK
  • Transmission range: 100 m (free field)
  • Transmission capacity: max. 10 mW
  • Ambient temperature: -5 °C to +50 °C
  • Protection class: IP 20

Warranty

The warranty is provided in accordance with statutory requirements via the specialist trade. Please submit or send faulty devices postage paid together with an error description to your responsible salesperson (specialist trade/installation company specialist electrical trade). The salesperson will forward the devices to the Gira Service Center.

Gira

Giersiepen GmbH & Co. KG
Electrical installation systems

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

GIRA User Manuals

Related Manuals