This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net
OPERATOR PAGE AND PARAMETERS
Parameters | Settings (Default Value) |
---|---|
Alarm Acknowledge | No |
Yes
(Default : No)
Maximum PV| View Only
(Default : NA)
Minimum PV| View Only
(Default : NA)
Reset Command| No
Yes
(Default : No)
Reset Password| 0 to 250
(Default : 0)
Alarm-1 Setpoint | Min to max Range specified for the selected Input Type
(Default: Min or Max Range)
Alarm-2 Setpoint | Min to max Range specified for the selected Input Type
(Default : Min or Max Range)
ALARM PARAMETERS
Parameters | Settings (Default Value) |
---|---|
Alarm-1 Type | None |
Process Low
Process High
(Default : None)
Alarm-1 Setpoint| Min to max Range specified for the selected Input Type
(Default : Min or Max Range)
Alarm-1 Hysteresis | 1 to 999 or 0.1 to 999.9
(Default : 2.0)
Alarm-1 Inhibit | No
Yes
(Default : Yes)
Alarm-1 Logic| Normal
Reverse
(Default : Normal)
Alarm Latch| No
Yes
(Default : No)
Alarm-2 Type | None
Process Low
Process High
(Default : None)
Alarm-2 Setpoint | Min to max Range specified for the selected Input Type
(Default : Min or Max Range)
Alarm-2 Hysteresis | 1 to 999 or 0.1 to 999.9
(Default : 2.0)
Alarm-2 Inhibit | No
Yes
(Default : Yes)
Alarm-2 Logic | Normal
Reverse
(Default : Normal)
Alarm Latch | No
Yes
(Default : No)
RE TRANSMISSION PARAMETERS
Parameters | Settings (Default Value) |
---|---|
Recorder Output Type | 0 to 20mA |
4 to 20mA
0 to 5 Volts
0 to 10 Volts
(Default : 0 to 20mA)
Recorder Low| Min. to Max. Range specified for the selected Input Type
(Default : -200)
Recorder High | Min. to Max. Range specified for the selected Input Type
(Default : 1376)
INPUT CONFIGURATION PARAMETERS
Parameters | Settings (Default Value) |
---|---|
Input Type | Refer Table 2 |
(Default : Type K)
Units | Refer Table 1
(Default : ºC)
Signal Range Low | | Input Type| Settings|
Default
---|---|---
0 to 20 mA| 0.00 to Signal High| 0.00
4 to 20 mA| 4.00 to Signal High| 4.00
Reserved| 0.0 to Signal High| 0.0
0 to 80 mV| 0.00 to Signal High| 0.00
0 to 1.25 V| 0.000 to Signal High| 0.000
0 to 5 V| 0.000 to Signal High| 0.000
0 to 10 V| 0.00 to Signal High| 0.00
1 to 5 V| 1.000 to Signal High| 1.000
Signal Range High| | Input Type| Settings| Default
---|---|---
0 to 20 mA| Signal Low to 20.00| 20
4 to 20 mA| Signal Low to 20.00| 20
Reserved| Signal Low to 80.00| 80
0 to 80 mV| Signal Low to 80.00| 80
0 to 1.25 V| Signal Low to 1.250| 1.25
0 to 5 V| Signal Low to 5.000| 5
0 to 10 V| Signal Low to 10.00| 10
1 to 5 V| Signal Low to 5.000| 5
Resolution| Refer Table 2
(Default : 1)
DC Range Low| -1999 to 9999
(Default : 0.0)
DC Range High| -1999 to 9999
(Default : 100.0)
Offset| -1999 to 9999 or
-199.9 to 999.9
(Default : 0)
Filter| 0.5 to 60.0 Seconds
(in steps of 0.5 Seconds)
(Default : 2.0 sec.)
SUPERVISORY PARAMETERS
Parameters | Settings (Default Value) |
---|---|
Alarm SP Adjustment on Operator Page | Disable |
Enable
(Default : Disable)
Process Value High-Low Monitoring| No
Yes
(Default : No)
Password for Resetting PV High-Low | 0 to 250
(Default : 0)
Serial ID Number| 1 to 127
(Default : 1)
Baud Rate| 4800
9600
19200
(Default : 9.6)
Parity | None
Even
Odd
(Default : Even)
Serial Write Permission | No
Yes
(Default : Yes)
USER LINEARISATION PARAMETERS
Parameters | Settings (Default Value) |
---|---|
User Linearization Setting Code | 0 to 9999 |
(Default : 0)
User Linearization | No
Yes
(Default : No)
Total Break Points | 2 to 32
(Default : 2)
Break Point Number | 1 to 32
(Default : 1)
Actual Value for Break Point (X co-ord)| -1999 to 9999
(Default : Undefined)
Derived Value for Break Point (Y co-ord) | -1999 to 9999
(Default : Undefined)
TABLE- 1
Lower Readout| Units|
---|---|---
| °C| Temperature
| °F
| Kelvin
| Engineering Units|
| Percentage|
| Pascals| Pressure
| Mpascals
| Kpascals
| Bar
| Milli bar
| PSI
| kg/sq cm
| mm water gauge| Pressure
| Inches water gauge
| mm mercury
| Torr
| Litres per hour| Flow
| Litres per minute
| % Relative Humidity|
| % O2|
| % CO2|
| % Carbon Potential|
| volts| Electricity
| Amps
| Milli amps
| Milli Volts
| Ohms
| Parts per million|
| Revolutions per pinute|
| Milli seconds| Time
| Seconds
| Minutes
| Hours
| PH|
| %PH|
| Miles per hour|
| Milli grams| Weight
| Grams
| Kilo grams
Lower Readout| Units|
---|---|---
| mm (Millimeter)| Length/Height/Distance
| cm (Centimeter)
| Meter
| Kilometre
| Foot
| Inch
| Mile
Table 2
Option | What it means | Range (Min. to Max.) | Resolution |
---|---|---|---|
Type J Thermocouple | 0 to +960°C / +32 to +1760°F | Fixed 1°C/1°F | |
Type K Thermocouple | -200 to +1376°C / -328 to +2508°F | ||
Type T Thermocouple | -200 to +385°C / -328 to +725°F | ||
Type R Thermocouple | 0 to +1770°C / +32 to +3218°F | ||
Type S Thermocouple | 0 to +1765°C / +32 to +3209°F | ||
Type B Thermocouple | 0 to +1825°C / +32 to +3092°F | ||
Type N Thermocouple | 0 to +1300°C / +32 to +2372°F | ||
Reserved for customer specific Thermocouple type not listed above. The type |
shall be specified in accordance with the ordered (optional on request)
Thermocouple type.
| 3-wire, RTD Pt100| -199 to +600°C/-328 to +1112°F
or
-199.9 to 600.0°C/-199.9 to 999.9°F| User settable
1°C/1°F
or
0.1°C/0.1°F
| 0 to 20mA DC current| -1999 to +9999 units| User settable
1 / 0.1 / 0.01/
0.001 units
| 4 to 20mA DC current
| Reserved
| 0 to 80 mV DC voltage
| 0 to 1.25V DC voltage
| 0 to 5.0V DC voltage
| 0 to 10.0V DC voltage
| 1 to 5.0V DC voltage
FRONT PANEL LAYOUT
Keys Operation
Symbol | Key | Function |
---|---|---|
PAGE | Press to enter or exit set-up mode. | |
DOWN | Press to decrease the parameter value. Pressing once decreases the |
value by one count; keeping pressed speeds up the change.
| UP| Press to increase the parameter value. Pressing once increases the value
by one count; keeping pressed speeds up the change.
| ENTER/ACK| Set up Mode: Press to store the set parameter value and to scroll
to the next parameter on the PAGE.
Run Mode: Press to acknowledge any pending Alarm(s). This also turns off the
Alarm relay.
PV Error Indications
Message | PV Error Type |
---|---|
Over-range |
(PV above Max. Range)
| Under-range
(PV below Min. Range)
| Open
(Sensor open/broken)
ELECTRICAL CONNECTIONS
101, Diamond Industrial Estate, Navghar,
Vasai Road (E), Dist. Palghar – 401 210.
Sales: 8208199048/8208141446
Support: 07498799226/08767395333
E: sales@ppiindia.net
support@ppiindia.net
Dec 2021
Documents / Resources
| PPI
Neuro 200 Advanced Universal Process
Indicator
[pdf] Instruction Manual
Neuro 200 Advanced Universal Process Indicator, Neuro 200, Advanced Universal
Process Indicator, Universal Process Indicator, Process Indicator, Indicator
---|---
| PPI
neuro 200 Advanced Universal Process
Indicator
[pdf] User Manual
neuro 200 Advanced Universal Process Indicator, neuro 200, Advanced Universal
Process Indicator, Universal Process Indicator, Process Indicator
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>