PPI Neuro 200 Advanced Universal Process Indicator Instruction Manual

June 11, 2024
PPI

Neuro 200 Advanced Universal Process Indicator
Instruction Manual

This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net

OPERATOR PAGE AND PARAMETERS

Parameters Settings (Default Value)
Alarm Acknowledge No

Yes
(Default : No)
Maximum PV| View Only
(Default : NA)
Minimum PV| View Only
(Default : NA)
Reset Command| No
Yes
(Default : No)
Reset Password| 0 to 250
(Default : 0)
Alarm-1 Setpoint | Min to max Range specified for the selected Input Type
(Default: Min or Max Range)
Alarm-2 Setpoint | Min to max Range specified for the selected Input Type
(Default : Min or Max Range)

ALARM PARAMETERS

Parameters Settings (Default Value)
Alarm-1 Type None

Process Low
Process High
(Default : None)
Alarm-1 Setpoint| Min to max Range specified for the selected Input Type
(Default : Min or Max Range)
Alarm-1 Hysteresis | 1 to 999 or 0.1 to 999.9
(Default : 2.0)
Alarm-1 Inhibit | No
Yes
(Default : Yes)
Alarm-1 Logic| Normal
Reverse
(Default : Normal)
Alarm Latch| No
Yes
(Default : No)
Alarm-2 Type | None
Process Low
Process High
(Default : None)
Alarm-2 Setpoint | Min to max Range specified for the selected Input Type
(Default : Min or Max Range)
Alarm-2 Hysteresis | 1 to 999 or 0.1 to 999.9
(Default : 2.0)
Alarm-2 Inhibit | No
Yes
(Default : Yes)
Alarm-2 Logic | Normal
Reverse
(Default : Normal)
Alarm Latch | No
Yes
(Default : No)

RE TRANSMISSION PARAMETERS

Parameters Settings (Default Value)
Recorder Output Type 0 to 20mA

4 to 20mA
0 to 5 Volts
PPI Neuro 200 Advanced Universal Process Indicator - Icon
27 0 to 10 Volts
(Default : 0 to 20mA)
Recorder Low| Min. to Max. Range specified for the selected Input Type
(Default : -200)
Recorder High | Min. to Max. Range specified for the selected Input Type
(Default : 1376)

INPUT CONFIGURATION PARAMETERS

Parameters Settings (Default Value)
Input Type Refer Table 2

(Default : Type K)
Units | Refer Table 1
(Default : ºC)
Signal Range Low PPI Neuro 200 Advanced Universal Process Indicator - Icon
32| | Input Type| Settings| Default
---|---|---
0 to 20 mA| 0.00 to Signal High| 0.00
4 to 20 mA| 4.00 to Signal High| 4.00
Reserved| 0.0 to Signal High| 0.0
0 to 80 mV| 0.00 to Signal High| 0.00
0 to 1.25 V| 0.000 to Signal High| 0.000
0 to 5 V| 0.000 to Signal High| 0.000
0 to 10 V| 0.00 to Signal High| 0.00
1 to 5 V| 1.000 to Signal High| 1.000
Signal Range High| | Input Type| Settings| Default
---|---|---
0 to 20 mA| Signal Low to 20.00| 20
4 to 20 mA| Signal Low to 20.00| 20
Reserved| Signal Low to 80.00| 80
0 to 80 mV| Signal Low to 80.00| 80
0 to 1.25 V| Signal Low to 1.250| 1.25
0 to 5 V| Signal Low to 5.000| 5
0 to 10 V| Signal Low to 10.00| 10
1 to 5 V| Signal Low to 5.000| 5
Resolution| Refer Table 2
(Default : 1)
DC Range Low| -1999 to 9999
(Default : 0.0)
DC Range High| -1999 to 9999
(Default : 100.0)
Offset| -1999 to 9999 or
-199.9 to 999.9
(Default : 0)
Filter| 0.5 to 60.0 Seconds
(in steps of 0.5 Seconds)
(Default : 2.0 sec.)

SUPERVISORY PARAMETERS

Parameters Settings (Default Value)
Alarm SP Adjustment on Operator Page Disable

Enable
(Default : Disable)
Process Value High-Low Monitoring| No
Yes
(Default : No)
Password for Resetting PV High-Low | 0 to 250
(Default : 0)
Serial ID Number| 1 to 127
(Default : 1)
Baud Rate| 4800
9600
19200
(Default : 9.6)
Parity | None
Even
Odd
(Default : Even)
Serial Write Permission | No
Yes
(Default : Yes)

USER LINEARISATION PARAMETERS

Parameters Settings (Default Value)
User Linearization Setting Code  0 to 9999

(Default : 0)
User Linearization | No
Yes
(Default : No)
Total Break Points | 2 to 32
(Default : 2)
Break Point Number | 1 to 32
(Default : 1)
Actual Value for Break Point (X co-ord)| -1999 to 9999
(Default : Undefined)
Derived Value for Break Point (Y co-ord) | -1999 to 9999
(Default : Undefined)

TABLE- 1

Lower Readout| Units|
---|---|---
| °C| Temperature
| °F
| Kelvin
| Engineering Units|
| Percentage|
| Pascals| Pressure
| Mpascals
| Kpascals
| Bar
| Milli bar
| PSI
| kg/sq cm
| mm water gauge| Pressure
| Inches water gauge
| mm mercury
| Torr
| Litres per hour| Flow
| Litres per minute
| % Relative Humidity|
| % O2|
| % CO2|
| % Carbon Potential|
| volts| Electricity
| Amps
| Milli amps
| Milli Volts
| Ohms
| Parts per million|
| Revolutions per pinute|
| Milli seconds| Time
| Seconds
| Minutes
| Hours
| PH|
| %PH|
| Miles per hour|
| Milli grams| Weight
| Grams
| Kilo grams
Lower Readout| Units|
---|---|---
| mm (Millimeter)| Length/Height/Distance
| cm (Centimeter)
| Meter
| Kilometre
| Foot
| Inch
| Mile

Table 2

Option What it means Range (Min. to Max.) Resolution
Type J Thermocouple 0 to +960°C / +32 to +1760°F Fixed 1°C/1°F
Type K Thermocouple -200 to +1376°C / -328 to +2508°F
Type T Thermocouple -200 to +385°C / -328 to +725°F
Type R Thermocouple 0 to +1770°C / +32 to +3218°F
Type S Thermocouple 0 to +1765°C / +32 to +3209°F
Type B Thermocouple 0 to +1825°C / +32 to +3092°F
Type N Thermocouple 0 to +1300°C / +32 to +2372°F
Reserved for customer specific Thermocouple type not listed above. The type

shall be specified in accordance with the ordered (optional on request) Thermocouple type.
| 3-wire, RTD Pt100| -199 to +600°C/-328 to +1112°F
or
-199.9 to 600.0°C/-199.9 to 999.9°F| User settable
1°C/1°F
or
0.1°C/0.1°F
| 0 to 20mA DC current| -1999 to +9999 units| User settable
1 / 0.1 / 0.01/
0.001 units
| 4 to 20mA DC current
| Reserved
| 0 to 80 mV DC voltage
| 0 to 1.25V DC voltage
| 0 to 5.0V DC voltage
| 0 to 10.0V DC voltage
| 1 to 5.0V DC voltage

FRONT PANEL LAYOUT

PPI Neuro 200 Advanced Universal Process Indicator - FRONT PANEL
LAYOUT

Keys Operation

Symbol Key Function
PAGE Press to enter or exit set-up mode.
DOWN Press to decrease the parameter value. Pressing once decreases the

value by one count; keeping pressed speeds up the change.
| UP| Press to increase the parameter value. Pressing once increases the value by one count; keeping pressed speeds up the change.
| ENTER/ACK| Set up Mode: Press to store the set parameter value and to scroll to the next parameter on the PAGE.
Run Mode: Press to acknowledge any pending Alarm(s). This also turns off the Alarm relay.

PV Error Indications

Message PV Error Type
Over-range

(PV above Max. Range)
| Under-range
(PV below Min. Range)
| Open
(Sensor open/broken)

ELECTRICAL CONNECTIONS

PPI Neuro 200 Advanced Universal Process Indicator - ELECTRICAL
CONNECTIONS

101, Diamond Industrial Estate, Navghar,
Vasai Road (E), Dist. Palghar – 401 210.
Sales: 8208199048/8208141446
Support: 07498799226/08767395333
E: sales@ppiindia.net
support@ppiindia.net
Dec 2021

Documents / Resources

| PPI Neuro 200 Advanced Universal Process Indicator [pdf] Instruction Manual
Neuro 200 Advanced Universal Process Indicator, Neuro 200, Advanced Universal Process Indicator, Universal Process Indicator, Process Indicator, Indicator
---|---
| PPI neuro 200 Advanced Universal Process Indicator [pdf] User Manual
neuro 200 Advanced Universal Process Indicator, neuro 200, Advanced Universal Process Indicator, Universal Process Indicator, Process Indicator

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals