PPI HumiTherm-c Pro Enhanced Temperature Humidity PID Controller User Manual
- June 11, 2024
- PPI
Table of Contents
PPI Hum iTherm-c Pro Enhanced Temperature Humidity PID Controller User
Manual
UTILITY PARAMETERS : PAGE-33
Parameters | Settings (Default Value) |
---|---|
Compressor Control Strategy | Dry Bulb SP Dry Bulb PV (Default : Dry Bulb SP) |
Input Type For Temperature
| Refer Table 1 (Default : RTD)
Signal Low For Temperature
|
Signal High For Temperature
|
DC Range Low For Temperature
| 199.9 to 999.9 (Default : 100.0)
DC Range High For Temperature| 25.0 to +25.0°C (Default : 0.0)
Input Type For %RH
| The above parameters are for %RH input and the descriptions are the same as
their temperature counterparts.
Notes
- RTD Pt100 input selection is not available for %RH.
- The factory default input type is 0 -5 VDC with corresponding signal low, signal high, range low & range high default values.
Signal High For %RH
DC Range Low For %RH
DC Range High For %RH
Offset For %RH
TEMPERATURE PARAMETERS : PAGE-10
Parameters | Settings (Default Value) |
---|
Temperature Alarm Band
| 0.3 to 25.0°C (Default : 0.5 °C)
Temperature Alarm Hysteresis
| 0.2 to 10.0°C (Default : 0.2 °C)
Temperature Proportional Band
| 0.1 to 999.9°C (Default : 5.0 °C)
Temperature Integral Time
| 0 to 1000 Seconds (Default : 100)
Temperature Derivative Time
| 0 to 250 Seconds (Default : 25)
Temperature Cycle Time
| 0.5 to 25.0 Seconds (in steps of 0.5 secs.)
RELATIVE HUMIDITY (% RH) PARAMETERS : PAGE-11
Parameters | Settings (Default Value) |
---|
%RH Alarm Band
| 0.3 to 25.0% (Default : 2.0)
%RH Alarm Hysteresis
| 0.2 to 10.0% (Default : 2.0)
%RH Proportional Band
| 0.1 to 999.9% (Default : 10.0)
%RH Integral Time
| 0 to 1000 Seconds (Default : 100
%RH Derivative Time
| 0 to 250 Seconds (Default : 25)
%RH Cycle Time
| 0.5 to 25.0 Seconds (in steps of 0.5 secs.)
OP3 FUNCTION PARAMETERS : PAGE-13
Parameters | Settings (Default Value) |
---|
Compressor Output Type
Alarm Output Type
| Default : For Compressor O/P Type : SSR For Alarm O/P type : None)
Compressor Setpoint
| 0.0 to 50.0°C or 0.0 to 25.0°C
Compressor Hysteresis
| 0.1 to 25.0°C (Default : 0.2)
Compressor Time Delay
| 0.00 to 10.00 Min. Sec (in steps of 5 Seconds) (Default : 00.00)
SUPERVISORY PARAMETERS : PAGE-12
Parameters | Settings (Default Value) |
---|
SP Adjustment on PAGE-0
| (Default : Enable)
Self-Tune Command
| (Default : No)
Water Level-low Detection Logic
| (Default : Open)
Slave Id
| 1 to 127 (Default : 1)
Baud Rate
| 4800 9600 19200 (Default : 9600)
Parity
| None Even Odd (Default : Even)
COMPRESSOR OPERATION & POWER INDICATION : PAGE-1
Parameters | Settings (Default Value) |
---|
Compressor Operation Mode
| (Default : Auto)
Output Power for Temperature Loop
| 0 to 100.0% (View Only – Non editable)
Output Power for %RH Loop
| 0 to 100.0% (View Only – Non editable)
Table 1
Option | What it means | Range (Min. to Max.) |
---|---|---|
3-wire, RTD Pt100 | -199.9 to 600.0°C / -199.9 to 999.9°F | |
0 to 20mA DC current | Refer Parameters Signal Low Signal High Range Low |
Range High
| 4 to 20mA DC current
| Reserved (Don’t Select)
| 0 to 1.25V DC voltage
| 0 to 5.0V DC voltage
| 0 to 10.0V DC voltage
| 1 to 5.0V DC voltage
FRONT PANEL LAYOUT ELECTRICAL CONNECTIONS
Front Panel
Keys Operation
Symbol | Key | Function |
---|---|---|
PAGE | Press to enter or exit set-up mode. | |
DOWN | Press to decrease the parameter value. Pressing once decreases |
the value by one count; keeping pressed speeds up the change.
| UP| Press to increase the parameter value. Pressing once increases the
value by one count; keeping pressed speeds up the change.
| ENTER| Press to store the set parameter value and to scroll to the
next parameter on the PAGE.
PV Error Indications
Message | PV Error Type |
---|---|
**** | Over-range(Dry-Bulb Temp. above Max. Range) |
**** | Under-range(Dry-Bulb Temp. below Min. Range) |
**** | Open(Sensor open / broken) |
ELECTRICAL CONNECTIONS
WIRING CONNECTION
RH SENSORS
R= Red
G= Green
B= Black
-
(Humirel RH sensor)
-
(IST RH sensor)
-
(Capacitance RH sensor)
Enhanced ‘Temperature + Humidity’ PID Controller
This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net