PPI ScanLog 4-8 Channel Recorder with Printer Interface Instruction Manual

June 11, 2024
PPI

PPI ScanLog 4-8 Channel Recorder with Printer Interface

SPECIFICATIONS

OPERATOR PARAMETERS

Parameters| Settings (Default Value)
Stop Printing| No Yes
Select Option| 1. None

2. Print (New)

3. Re-print (Old)

4. Resume

5. Recover

6. Print Info Page

(Default : None)

Batch Start Batch Stop| No Yes
Balance Slot Time| Read Only
Line Per Page| 25 to 100

(Default : 65)

Top Margine| 1 to 5

(Default : 2)

Bottom Margine| 1 to 5

(Default : 2)

Offset Records| 10 to 1000

(Default : 10)

Print Page Header >>| No

On First Page Every Page

(Default : Every Page)

Delete Page Header >>| No Yes
Delete Page Footer >>| No Yes
READ USB PARAMETERS

Parameters| Settings (Default Value)
Select Option| 1. None

2. Read Set.txt File

3. Read Hdr.dat File

4. Read Ftr.dat File

(Default : None)

ALARM SETTINGS

Parameters| Settings (Default Value)
Select Channel| Channel-1 to

Channel-4

(for 4C Printer Version) Channel-1 to Channel-8

(for 8C Printer Version)

Select Alarm| AL1, AL2, AL3, AL4

(The actual available options depends on the numbers of Alarms

set per channel on Alarm configuration page)

AL1 Type| None Process Low Process High

(Default : None)

AL1 Setpoint| Min. to Max. of selected input type range

(Default : 0)

Parameters Settings (Default Value)
AL1 Hysteresis 1 to 30000

(Default : 20)

AL1 Inhibit| No Yes

(Default : No)

DEVICE CONFIGURATION

Parameters| Settings (Default Value)
Delete Records| No Yes

(Default : No)

CHANNEL CONFIGURATION

Parameters| Settings (Default Value)
All Chan Common| No Yes

(Default : No)

Select Channel| Channel-1 to

Channel-4

(for 4C Printer Version)

Channel-1 to

Channel-8

(for 8C Printer Version)

Input Type| Refer Table 1

(Default : 0 to 10 V)

Resolution| Refer Table 1
Signal Low|
Signal High|
Parameters| Settings (Default Value)
---|---
Range Low| -30000 to +30000

(Default : 0)

Range High| -30000 to +30000

(Default : 1000)

Low Clipping| Disable Enable

(Default : Disable)

Low Clip Val| -30000 to High Clip Val (Default : 0)
High Clipping| Disable Enable

(Default : Disable)

High Clip Val| Low Clip Val to 30000 (Default : 1000)
Zero Offset| -30000 to +30000

(Default : 0)

ALARM CONFIGURATION

Parameters| Settings (Default Value)
Alarms/Chan| 1 to 4

(Default : 4)

RECORDER CONFIGURATION

Parameters| Settings (Default Value)
Normal Interval| 0:00:00 (H:MM:SS) to

2:30:00 (H:MM:SS)

(Default : 0:00:30)

Zoom Interval| 0:00:00 (H:MM:SS) to

2:30:00 (H:MM:SS)

(Default : 0:00:10)

Alrm Toggl Rec| Disable Enable

(Default : Enable)

Recording Mode| Continuous Batch

(Default : Continuous)

Batch Time| 0:01 (HH:MM) to

250:00 (HHH:MM)

(Default : 1:00)

Batch Start Batch Stop| No Yes
RTC SETTING

Parameters| Settings
Time (HH:MM)| 0.0 to 23:59
Date| 1 to 31
Month| 1 to 12
Year| 2000 to 2099
UTILITIES

Parameters| Settings (Default Value)
Lock Unlock| No Yes

(Default : No)

Factory Default| No Yes

(Default : No)

TABLE 1

Option| Range (Min. to Max.)| Resolution & Unit
Type J (Fe-K)| 0.0 to +960.0°C| ****






1 °C

or

0.1 °C

Type K (Cr-Al)| -200.0 to +1376.0°C
Type T (Cu-Con)| -200.0 to +387.0°C
Type R (Rh-13%)| 0.0 to +1771.0°C
Type S (Rh-10%)| 0.0 to +1768.0°C
Type B| 0.0 to +1826.0°C
Type N| 0.0 to +1314.0°C
Reserved for customer specific Thermocouple type not listed above. The type shall be specified in accordance with the ordered (optional on request) Thermocouple type.
RTD Pt100| -199.9 to +600.0°C| 1°C or 0.1 °C
0 to 20 mA| ****


-30000 to 30000 units

| ****



1

0.1

0.01

0.001

units

4 to 20 mA
0 to 80 mV
Reserved
0 to 1.25 V| ****



-30000 to 30000 units

0 to 5 V
0 to 10 V
1 to 5 V

FRONT PANEL KEYS

SCROLLING THROUGH VARIOUS SCREENS

The screen shown below are for 4 Channel Version. The sequence is the same for 8 Channel Version.

PPI-ScanLog-4-8-Channel-Recorder-with-Printer-Interface-
FIG-2

VIEWING ALARM STATUS SCREEN

PPI-ScanLog-4-8-Channel-Recorder-with-Printer-Interface-
FIG-3

ELECTRICAL CONNECTIONS

4 Channel Without Alarm Relay Outputs

4 Channel With Alarm Relay Outputs

8 Channel Without Alarm Relay Outputs

8 Channel With Alarm Relay Outputs

This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application please log on to www.ppiindia.net

101, Diamond Industrial Estate, Navghar, Vasai Road (E), Dist. Palghar – 401 210.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals