OPERATOR PAGE PARAMETERS

OPERATOR PAGE PARAMETERS

Parameters| Settings (Default Value)
Select

Prnt Option >>

| None   Print (New)

Re-Print (Old) Print Info Page

(Default : None)

Temp.

Set Value >>

| SP Low Limit to SP High Limit

(Default : 25.0)

%RH

Set Value >>

| SP Low Limit to SP High Limit

(Default : 60.0)

Temp.

Lo Deviation >>

| 0.2 to 99.9

(Default : 2.0)

Temp.

Hi Deviation >>

| 0.2 to 99.9

(Default : 2.0)

%RH

Lo Deviation >>

| 0.2 to 99.9

(Default : 2.0)

%RH

Hi Deviation >>

| 0.2 to 99.9

(Default : 2.0)

Change Password >>| 1 to 100

(Default : 0)

SUPERVISORY

SUPERVISORY > SENSOR INPUT

Parameters| Settings (Default Value)
Temp.

Zero Offset >>

| -50.0 to 50.0

(Default : 0.0)

%RH

Zero Offset >>

| -50.0 to 50.0

(Default : 0.0)

SUPERVISORY > RECORDING

Parameters| Settings (Default Value)
Recording Interval (min) >>| 0 to 250 Min (Default : 5 Min)
Alarm

Toggle Records >>

| Enable Disable

(Default : Enable)

Delete

PC Records >>

| Yes No

(Default : No)

RTC Time >>| 0 to 23 for Hour

0 to 59 for Min

(Default : NA)

RTC Date >>| 1 to 31 (Default : NA)
RTC Month >>| 1 to 12 (Default : NA)
RTC Year >>| 2000 to 2099

(Default : NA)

SUPERVISORY > PRINTER SETTING

Parameters| Settings (Default Value)
Line Per Page >>| 25 to 100

(Default : 65)

Top Margine >>| 1 to 5

(Default : 2)

Bottom Margine >>| 1 to 5

(Default : 2)

Header & Footer >>| No

On First Page Every Page (Default : No)

Enable >>| Yes No

(Default : No)

SUPERVISORY > PRINT EVENT

Parameters| Settings (Default Value)
Alarm Toggle >>|
RTC Modify >> Interval Modify >>

Power  Up >> Door Open >> Mains Fail >> Setpoint Modify >>

| Yes No

(Default : Yes)

SUPERVISORY > PASSWORD

Parameters| Settings (Default Value)
Change Password >>| 1000 to 1999

(Default : 123)

SUPERVISORY > EXIT

Parameters| Settings (Default Value)
Exit

Setup Mode >>

| Yes No

(Default : No)

FACTORY

FACTORY > TEMPERATURE > ALARM

FACTORY > HUMIDITY (%RH) > ALARM


Parameters| Settings

(Default Value)

Hysteresis >>| 0.1 to 99.9

(Default : 0.2)

Inhibit >>| Yes No

(Default : Yes)

FACTORY > TEMPERATURE > CONTROL FACTORY > HUMIDITY (%RH) > CONTROL

Parameters| Settings (Default Value)
Tune >>| Yes No

(Default : No)

Setpoint LO Limit >>| -99.9 to   SETPOINT HI LIMIT

(Default : 10.0)

Setpoint HI Limit >>| For RTD: Setpoint Lo Limit to 600.0

For mA/V: Setpoint Lo Limit

to 999.9

(Default : 60.0)

FACTORY > TEMPERATURE > CONTROL

FACTORY > HUMIDITY (%RH) > CONTROL


CONTROL ZONES : DUAL
Parameters| Settings (Default Value)
CZ Prop Band >>| 0.1 to 999.9

(Default : 50.0)

CZ

Integral Time >>

| 0 to 3600 Sec (Default : 100 Sec)
CZ

Derivative Time >>

| 0 to 600 Sec (Default : 16 Sec)
HZ Prop Band >>| 0.1 to 999.9

(Default : 50.0)

HZ

Integral Time >>

| 0 to 3600 Sec (Default : 100 Sec)
HZ

Derivative Time >>

| 0 to 600 Sec (Default : 16 Sec)
Cycle Time >>| 0.5 to 100.0 Sec (Default : 10.0 Sec)
CONTROL ZONES : SINGLE
Parameters| Settings (Default Value)
Proportional Band >>| 0.1 to 999.9

(Default : 50.0)

Integral Time >>| 0 to 3600 Sec (Default : 100 Sec)
Derivative Time >>| 0 to 600 Sec (Default : 16 Sec)
Cycle Time >>| 0.5 to 100.0 Sec (Default : 10.0 Sec)
FACTORY > TEMPERATURE > SENSOR INPUT

FACTORY > HUMIDITY (%RH) > SENSOR INPUT


Parameters| Settings (Default Value)
Input Type >>| * RTD Pt100 0-20mA

4-20mA

0-5V

0-10V

1-5V

(Default :

For Temp. Input : RTD Pt100 For %RH Input : 0-5V)

*Available for Temp. Input only

PPI-HumiTherm-Plus-Recording-Plus-Printer-Interface-fig
3

FACTORY > COMPRESSOR

Control Strategy : Heat + Cool
COMPRESSOR STRATEGY >>| CONT. OFF CONT. ON SP BASED PV BASED

(Default : CONT. ON)

CONT. ON| SP BASED| PV BASED
Time Delay (sec) >>

0 to 1000 Sec (Default : 200 Sec)

| Boundary Set Value >>

0.0 to 100.0

(Default : 45.0)

| Compressor SP >>

0.0 to 100.0

(Default : 45.0)

 | Control Zones >>

SINGLE DUAL

(Default : SINGLE)

| Hysteresis >>

0.1 to 99.9

(Default : 2.0)

Time Delay (sec) >>

0 to 1000 Sec

(Default : 200 Sec)

| Time Delay (sec) >>

0 to 1000 Sec

(Default : 200 Sec)

FACTORY > COMPRESSOR

Control Strategy : Heat + Cool
COMPRESSOR STRATEGY >>| CONT. OFF CONT. ON SP BASED PV BASED

(Default : CONT. ON)

CONT. ON| SP BASED| PV BASED
Time Delay (sec) >>

0 to 1000 Sec (Default : 200 Sec)

| Boundary Set Value >>

0.0 to 100.0

(Default : 45.0)

| Compressor SP >>

0.0 to 100.0

(Default : 45.0)

 | Control Zones >>

SINGLE DUAL

(Default : SINGLE)

| Hysteresis >>

0.1 to 99.9

(Default : 2.0)

Time Delay (sec) >>

0 to 1000 Sec

(Default : 200 Sec)

| Time Delay (sec) >>

0 to 1000 Sec

(Default : 200 Sec)

FACTORY > BOILER WATER LEVEL

Parameters| Settings (Default Value)
Enable >>| Yes No

(Default : No)

Water

Level Startegy >>

| Single Switch Dual Switch Lo-hi Dual Switch Lo-vlo

(Default : Single Switch)

Switch-1 Logic >>| Close : Water Lo Open : Water Lo

(Default : Close : Water Lo)

Switch-2 Logic >>| Close : Water HI Open : Water HI

(Default : Close : Water HI)

OR

Close : Water VLO Open : Water VLO

(Default : Close : Water VLO)

FACTORY > DOOR OPEN

Parameters| Settings (Default Value)
Enable >>| Yes No

(Default : No)

Switch Logic >>| Close : Door Open Open : Door Open

(Default : Close : Door Open)

Door

Alrm Dly (sec) >>

| 0 to 1000 Sec

(Default : 60 Sec)

FACTORY > MAINS FAILURE

Parameters| Settings (Default Value)
Enable >>| Yes No

(Default : No)

Switch Logic >>| Close : Mains Fail Open : Mains Fail

(Default : Close : Mains Fail)

FACTORY > FACTORY DEFAULT

Parameters| Settings (Default Value)
Set To Default >>| Yes No

(Default : No)

FACTORY > PASSWORD

Parameters| Settings (Default Value)
Change Password >>| 2000 to 2999

(Default : 321)

FACTORY > EXIT

Parameters| Settings (Default Value)
Exit Setup Mode >>| Yes No

(Default : No)

FRONT PANEL KEYS

PPI-HumiTherm-Plus-Recording-Plus-Printer-Interface-fig
1

PV ERROR INDICATIONS

PPI-HumiTherm-Plus-Recording-Plus-Printer-
Interface-fig 4

ELECTRICAL CONNECTIONS

PPI-HumiTherm-Plus-Recording-Plus-Printer-
Interface-fig 2

This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net

101, Diamond Industrial Estate, Navghar, Vasai Road (E), Dist. Palghar – 401 210.