PPI HumiTherm Plus Recording Plus Printer Interface Instruction Manual
- June 11, 2024
- PPI
Table of Contents
PPI HumiTherm Plus Recording Plus Printer Interface
OPERATOR PAGE PARAMETERS
OPERATOR PAGE PARAMETERS
Parameters| Settings (Default Value)
Select
Prnt Option >>
| None Print (New)
Re-Print (Old) Print Info Page
(Default : None)
Temp.
Set Value >>
| SP Low Limit to SP High Limit
(Default : 25.0)
%RH
Set Value >>
| SP Low Limit to SP High Limit
(Default : 60.0)
Temp.
Lo Deviation >>
| 0.2 to 99.9
(Default : 2.0)
Temp.
Hi Deviation >>
| 0.2 to 99.9
(Default : 2.0)
%RH
Lo Deviation >>
| 0.2 to 99.9
(Default : 2.0)
%RH
Hi Deviation >>
| 0.2 to 99.9
(Default : 2.0)
Change Password >>| 1 to 100
(Default : 0)
SUPERVISORY
SUPERVISORY > SENSOR INPUT
Parameters| Settings (Default Value)
Temp.
Zero Offset >>
| -50.0 to 50.0
(Default : 0.0)
%RH
Zero Offset >>
| -50.0 to 50.0
(Default : 0.0)
SUPERVISORY > RECORDING
Parameters| Settings (Default Value)
Recording Interval (min) >>| 0 to 250 Min (Default : 5 Min)
Alarm
Toggle Records >>
| Enable Disable
(Default : Enable)
Delete
PC Records >>
| Yes No
(Default : No)
RTC Time >>| 0 to 23 for Hour
0 to 59 for Min
(Default : NA)
RTC Date >>| 1 to 31 (Default : NA)
RTC Month >>| 1 to 12 (Default : NA)
RTC Year >>| 2000 to 2099
(Default : NA)
SUPERVISORY > PRINTER SETTING
Parameters| Settings (Default Value)
Line Per Page >>| 25 to 100
(Default : 65)
Top Margine >>| 1 to 5
(Default : 2)
Bottom Margine >>| 1 to 5
(Default : 2)
Header & Footer >>| No
On First Page Every Page (Default : No)
Enable >>| Yes No
(Default : No)
SUPERVISORY > PRINT EVENT
Parameters| Settings (Default Value)
Alarm Toggle >>|
RTC Modify >> Interval Modify >>
Power Up >> Door Open >> Mains Fail >> Setpoint Modify >>
| Yes No
(Default : Yes)
SUPERVISORY > PASSWORD
Parameters| Settings (Default Value)
Change Password >>| 1000 to 1999
(Default : 123)
SUPERVISORY > EXIT
Parameters| Settings (Default Value)
Exit
Setup Mode >>
| Yes No
(Default : No)
FACTORY
FACTORY > TEMPERATURE > ALARM
FACTORY > HUMIDITY (%RH) > ALARM
Parameters| Settings
(Default Value)
Hysteresis >>| 0.1 to 99.9
(Default : 0.2)
Inhibit >>| Yes No
(Default : Yes)
FACTORY > TEMPERATURE > CONTROL FACTORY > HUMIDITY (%RH) > CONTROL
Parameters| Settings (Default Value)
Tune >>| Yes No
(Default : No)
Setpoint LO Limit >>| -99.9 to SETPOINT HI LIMIT
(Default : 10.0)
Setpoint HI Limit >>| For RTD: Setpoint Lo Limit to 600.0
For mA/V: Setpoint Lo Limit
to 999.9
(Default : 60.0)
FACTORY > TEMPERATURE > CONTROL
FACTORY > HUMIDITY (%RH) > CONTROL
CONTROL ZONES : DUAL
Parameters| Settings (Default Value)
CZ Prop Band >>| 0.1 to 999.9
(Default : 50.0)
CZ
Integral Time >>
| 0 to 3600 Sec (Default : 100 Sec)
CZ
Derivative Time >>
| 0 to 600 Sec (Default : 16 Sec)
HZ Prop Band >>| 0.1 to 999.9
(Default : 50.0)
HZ
Integral Time >>
| 0 to 3600 Sec (Default : 100 Sec)
HZ
Derivative Time >>
| 0 to 600 Sec (Default : 16 Sec)
Cycle Time >>| 0.5 to 100.0 Sec (Default : 10.0 Sec)
CONTROL ZONES : SINGLE
Parameters| Settings (Default Value)
Proportional Band >>| 0.1 to 999.9
(Default : 50.0)
Integral Time >>| 0 to 3600 Sec (Default : 100 Sec)
Derivative Time >>| 0 to 600 Sec (Default : 16 Sec)
Cycle Time >>| 0.5 to 100.0 Sec (Default : 10.0 Sec)
FACTORY > TEMPERATURE > SENSOR INPUT
FACTORY > HUMIDITY (%RH) > SENSOR INPUT
Parameters| Settings (Default Value)
Input Type >>| * RTD Pt100 0-20mA
4-20mA
0-5V
0-10V
1-5V
(Default :
For Temp. Input : RTD Pt100 For %RH Input : 0-5V)
*Available for Temp. Input only
FACTORY > COMPRESSOR
Control Strategy : Heat + Cool
COMPRESSOR STRATEGY >>| CONT. OFF CONT. ON SP BASED PV BASED
(Default : CONT. ON)
CONT. ON| SP BASED| PV BASED
Time Delay (sec) >>
0 to 1000 Sec (Default : 200 Sec)
| Boundary Set Value >>
0.0 to 100.0
(Default : 45.0)
| Compressor SP >>
0.0 to 100.0
(Default : 45.0)
| Control Zones >>
SINGLE DUAL
(Default : SINGLE)
| Hysteresis >>
0.1 to 99.9
(Default : 2.0)
Time Delay (sec) >>
0 to 1000 Sec
(Default : 200 Sec)
| Time Delay (sec) >>
0 to 1000 Sec
(Default : 200 Sec)
FACTORY > COMPRESSOR
Control Strategy : Heat + Cool
COMPRESSOR STRATEGY >>| CONT. OFF CONT. ON SP BASED PV BASED
(Default : CONT. ON)
CONT. ON| SP BASED| PV BASED
Time Delay (sec) >>
0 to 1000 Sec (Default : 200 Sec)
| Boundary Set Value >>
0.0 to 100.0
(Default : 45.0)
| Compressor SP >>
0.0 to 100.0
(Default : 45.0)
| Control Zones >>
SINGLE DUAL
(Default : SINGLE)
| Hysteresis >>
0.1 to 99.9
(Default : 2.0)
Time Delay (sec) >>
0 to 1000 Sec
(Default : 200 Sec)
| Time Delay (sec) >>
0 to 1000 Sec
(Default : 200 Sec)
FACTORY > BOILER WATER LEVEL
Parameters| Settings (Default Value)
Enable >>| Yes No
(Default : No)
Water
Level Startegy >>
| Single Switch Dual Switch Lo-hi Dual Switch Lo-vlo
(Default : Single Switch)
Switch-1 Logic >>| Close : Water Lo Open : Water Lo
(Default : Close : Water Lo)
Switch-2 Logic >>| Close : Water HI Open : Water HI
(Default : Close : Water HI)
OR
Close : Water VLO Open : Water VLO
(Default : Close : Water VLO)
FACTORY > DOOR OPEN
Parameters| Settings (Default Value)
Enable >>| Yes No
(Default : No)
Switch Logic >>| Close : Door Open Open : Door Open
(Default : Close : Door Open)
Door
Alrm Dly (sec) >>
| 0 to 1000 Sec
(Default : 60 Sec)
FACTORY > MAINS FAILURE
Parameters| Settings (Default Value)
Enable >>| Yes No
(Default : No)
Switch Logic >>| Close : Mains Fail Open : Mains Fail
(Default : Close : Mains Fail)
FACTORY > FACTORY DEFAULT
Parameters| Settings (Default Value)
Set To Default >>| Yes No
(Default : No)
FACTORY > PASSWORD
Parameters| Settings (Default Value)
Change Password >>| 2000 to 2999
(Default : 321)
FACTORY > EXIT
Parameters| Settings (Default Value)
Exit Setup Mode >>| Yes No
(Default : No)
FRONT PANEL KEYS
PV ERROR INDICATIONS
ELECTRICAL CONNECTIONS
This brief manual is primarily meant for quick reference to wiring connections and parameter searching. For more details on operation and application; please log on to www.ppiindia.net