PPI ProceX48 Process Indicator with Alarms User Manual
- June 11, 2024
- PPI
Table of Contents
Proce X
Process Indicator with Alarms
User Manual
PANEL MOUNTING & ELECTRICAL CONNECTIONS
PANEL CUTOUTS
ELECTRICAL CONNECTIONS
FRONT PANEL AND OPERATION
PROCEX48 / PROCEX72 / PROCEX96
PROCEX48H
Table 2.1
KEY DEFINITIONS
Symbol | Key | Function |
---|---|---|
PROGRAM MODE | Keep pressed for approximately 5 seconds to enter / exit Set- |
up mode.
| **** DOWN| Press to decrease the parameter value. Pressing once decreases the value by one count; holding the key pressed speeds up the change.
| **** UP| Press to increase the parameter value. Pressing once increases the value by one count; holding the key pressed speeds up the change.
MAIN MODE DISPLAY
Upon switching on the power to the Indicator, all displays and indicators are
lit on for approximately 3 seconds. This is followed by the indication of the
Indicator model name for approximately 1 second. The Indicator now enters MAIN
Mode wherein the display shows the PV proportional to the Input DC signal
within user set Range Low and Range High Limits.
PV ERROR INDICATION
In case of PV Error the following messages are flashed.
Table 2.2
Message | PV Error Type |
---|
__
| Over-range (PV above Max. Range)
__
| __ Under-range (PV below Min. Range)
PARAMETER SETTINGS
The Indicator offers various parameters for setting-up the configuration and
operation modes. Each parameter has a unique name and a settable value. For
example, the parameter ‘Input Type’ is identified by its name and has the
settable values ‘0-20mA / 4-20mA / 0-5V / 0-10V’.
Further, the parameters are organized under different groups. Each group of
parameters is called PAGE. Each page is assigned a unique number for its
identification and access. The various pages along with their parameters are
described later. Follow the steps below for setting / changing any parameter
value.
Follow the steps below for setting / changing any parameter value.
- Keep PRG key pressed (approximately 5 seconds) until display shows PAGE ( ). Release the key.
- Press PRG key again. Display shows page number 0.
- Press PRG key if page 0 is the desired page number (operator page) or use UP / DOWN keys to set the desired page number and then press PRG key. The display now shows the name for the first parameter in the page.
- Use UP / DOWN keys to select the desired parameter name.
- Press PRG key. The display now shows the value for the selected parameter.
- Use UP / DOWN keys to change the parameter value.
- Press PRG key to save the new value. The display shows the name for the next parameter in the list.
- Repeat steps 4 to 7 for any other parameter settings, if required.
- For returning to Main Mode, keep PRG key pressed (approximately 3 seconds) until the display starts showing PV.
The following figures step-wise show an example of changing the value for the parameter ‘Resolution’ from ‘1’ to ‘0.1’. The parameter ‘Resolution’ is available on PAGE-12 and is second in the list. Notice that from MAIN Mode the appropriate page number is selected first and then the desired parameter name is selected for changing the value. Finally, PRG key is used to return back to MAIN Mode.
Table 3.1
PAGE – 0 : OPERATOR PARAMETERS
Parameter Description | Settings |
---|
ALARM-1 SETPOINT
Available only if selected ‘Alarm-1 type’ is either ‘Process High’ or
‘Process Low’. This parameter value sets the Upper (Process High) or Lower
(Process Low) Alarm Limit.| ** -1999 to 9999
(with selected Resolution)
ALARM-2 SETPOINT
Available only if selected ‘Alarm-2 type’ is either ‘Process High’ or
‘Process Low’. This parameter value sets the Upper (Process High) or Lower
(Process Low) Alarm Limit.| ** -1999 to 9999
(with selected Resolution)
Table 3.2
PAGE – 1 : PV MIN / MAX PARAMETERS
Parameter Description | Settings |
---|
MAXIMUM PROCESS VALUE
This gives the maximum PV recorded since Power-up or last reset| ** View
Only
MINIMUM PROCESS VALUE
This gives the minimum PV recorded since Power-up or last reset.| **
View Only
RESET PV MONITOR
This command resets Maximum value and Minimum value to the instantaneous
Process Value.|
Table 3.3
PAGE – 12 : INPUT CONFIGURATION PARAMETERS
Parameter Description | Settings |
---|
INPUT TYPE
The Indicator is factory calibrated for DC Voltage (0-5V / 0-10V) and DC
Current (0-20mA / 4-20mA). Select the appropriate input type as per the type
of Input Signal.
Note : _
_For DC Voltage Input, keep Terminals 2 & 3 open.
For DC Current Input, keep terminals 2 & 3 shorted.| ****
Controller Version :
RESOLUTION
Decimal Point for the displayed value.|
Parameter Description| Settings
---|---
DC RANGE LOW AND
DC RANGE HIGH
Set Range High as the value corresponding to Maximum input signal level and
Range Low as the value corresponding to Minimum input signal level.| ****
-1999 to 9999
(with selected Resolution)
OFFSET FOR PV
Zero offset for measured PV. Displayed PV = Actual PV + Offset| **** -1999
to 9999
(with selected Resolution)
Table 3.4
PAGE – 11 : ALARM PARAMETERS
Parameter Description | Settings |
---|
ALARM-1 TYPE
Type for Alarm-1.|
ALARM-1 HYSTERESIS
Differential (dead) band between the ON and OFF alarm states. Keep it large
enough to avoid frequent switching.| 1 to 999 (with selected Resolution)
ALARM-1 LOGIC
Normal : The alarm-1 output remains ON under alarm conditions; OFF
otherwise.
Reverse : The alarm-1 output remains OFF under alarm conditions; ON
otherwise.|
ALARM-1 INHIBIT
Yes : The alarm-1 is suppressed during start-up alarm conditions.
No : The alarm-1 is not suppressed during start-up alarm conditions.|
ALARM-2 TYPE
Type for Alarm-2.|
ALARM-2 HYSTERESIS
Same as Alarm-1 Hysteresis.| 1 to 999 (with selected Resolution)
ALARM-2 LOGIC
Same as Alarm-1 Logic.|
ALARM-2 INHIBIT
Same as Alarm-1 Inhibit.|
Process Precision Instruments
101, Diamond Industrial Estate, Navghar, Vasai Road (E),
Dist. Palghar – 401 210.Maharashtra, India
Sales : 8208199048 / 8208141446
Support : 07498799226 / 08767395333
sales@ppiindia.net,
support@ppiindia.net
www.ppiindia.net
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>