TELETEK SensoMAG F10B Conventional Fire Alarm Fixed Temperature Detector Instruction Manual

June 10, 2024
Teletek

TELETEK SensoMAG F10B Conventional Fire Alarm Fixed Temperature Detector

TELETEK-SensoMAG-F10B-Conventional-Fire-Alarm-Fixed-Temperature-Detector-
product

The SensoMAG F10B is a fixed temperature detector used for fire alarm systems in commercial and residential buildings. It has been tested and certified according to EN 54-5:2017+A1:2018 Detector Class B/S standards. It can be installed with any conventional fire panel with fire alarm threshold between 10mA and 15mA (between 10mA and 30mA with B24RD fire base).

Product SensoMAG Bases

The SensoMAG F10B can be used with 4 base types:

  • B12L/U – Base with relay output (not covered by EN 54-5)
  • B24 – Standard base, low profile
  • B24-HP – Standard base, high profile
  • B24D – Standard base with Schottky diode
  • EB24RD – Standard base with Schottky diode and increased alarm state current.

Product Usage Instructions

  1. Choose the proper place for installation of the fire detector. Refer to the given installation instructions. Note: Do not installthe detector near to natural heat sources, e.g. above cookers, ovens or fireplaces.
  2. If you want to lock the detector to the base, remove the little tooth (with the triangle shape) and break the plastic key off the base. Keep the plastic key in a safe place to be able to open the detector later.
  3. Mount the fire base on the ceiling of the protected premises using fixings according to the mounting surface.
  4. Connect the detector base to the fire panel using the wiring diagram.
    • ATTENTION: Disconnect the line power before installing the detector!
  5. Insert the detector into the base and rotate clockwise until it drops into place. Continue to rotate the detector until it locks to the base – a click is heard.
  6. If the detector has been locked to the base, when opening it for a scheduled maintenance service and cleaning you have to usethe plastic key. Lightly press with the plastic key into the baseopening and at the same time rotate the detector head counter-clockwise.
  7. In case of removing the detector’s PCB for service maintenance, when mounting it back, find the colored dot sticker on the PCB and align it to the mark on the plastic body (visible from the outside). The hole next to the colored dot has to align with the pin on the plastic body. Gently press downwards to fix the PCB in place.
  8. Test the detector for proper operation and LED indication.

Note: Follow all safety precautions and refer to the installation instructions carefully before beginning installation. Always test the detector for proper operation after installation and during scheduled maintenance services.

SensoMAG Bases

ATTENTION: Read carefully these installation Instructions before installing the device! The detector SensoMAG F10B is compatible with any conventional Fire Panel with fire alarm threshold between 10mA and 15mA (between 10mA and 30mA with B24RD firebase). The detector SensoMAG F10B can be used with 4 base types:

TELETEK-SensoMAG-F10B-Conventional-Fire-Alarm-Fixed-Temperature-Detector-
fig-1

  1. B12L/U:  Base with relay output (not covered by EN 54-5);
  2. B24:  Standard base, low profile; B24-HP – Standard base, high profile;
  3. B24D: Standard base with Schottky diode;
  4. B24RD:  Standard base with Schottky diode and increased alarm state current.

INSTALLATION

TELETEK-SensoMAG-F10B-Conventional-Fire-Alarm-Fixed-Temperature-Detector-
fig-2

  1. Choose the proper place for installation of the fire detector. Refer to the given installation instructions.
    • Note: Do not install the detector near to natural heat sources, e.g. above cookers, ovens or fire places.
  2. If you want to “lock” the detector to the base remove the little “tooth” (with the triangle shape) and break the plastic key off the base. Keep the plastic key in safe place to be able to open the detector later.
  3. Mount the fire base on the ceiling of the protected premises using fixings according the mounting surface.
  4. Connect the detector base to the fire panel using the wiring diagram.
    • ATTENTION: Disconnect the line power before installing the detector!
  5. Insert the detector into the base and rotate clockwise until it drops into place. Continue to rotate the detector until it locks to the base – a click is heard.
  6. If the detector has been locked to the base, when opening it for scheduled maintenance service and cleaning you have to use the plastic key. Lightly press with the plastic key into the base opening and at the same time rotate the detector head counter-clockwise.
    • ATTENTION: In case of removing the detector’s PCB for service maintenance, when mounting it back, find the colored dot sticker on the PCB and align it to the mark on the plastic body (visible from the outside). The hole next to the colored dot have to align with the pin on the plastic body. Gently press downwards to fix the PCB in place.
  7. Test the detector for proper operation and LED indication.

WIRING DIAGRAM

TELETEK-SensoMAG-F10B-Conventional-Fire-Alarm-Fixed-Temperature-Detector-
fig-3

TELETEK-SensoMAG-F10B-Conventional-Fire-Alarm-Fixed-Temperature-Detector-
fig-5

ATTENTION: When the EOL-module is only a capacitor, IT IS OBLIGATORY TO CONNECT a 100K resistor in parallel at the beginning of the line!

LED Indication

  • Blinking
  • Light on
  • Light off

TEST AND MAINTENANCE

  1. Apply power to the detector.
  2. Wait for 30 sec.
  3. Apply the heat tester (Cordless Heat Detector Tester or Heat Tester 110V>24OV) at a distance 20cm to test the heat part of the detector. Within 8 sec the fire detector will enter in fire condition. Both LEDs will light up.
  4. Power off the detector for 2 sec minimum. After resetting the detector will enter in duty mode and the LEDs will light off.

The service maintenance periods for the detector should be executed as follows:

  1. Inspection for visible physical damage -weekly.
  2. Operational test in real conditions monthly.
  3. Check and clean dust contamination – six months.
  4. Check and clean base and head contacts and connections annually.

TECHNICAL SPECIFICATIONS

  • Operating Voltage Range: 9 – 30 V DC (Nom. 12/24VDC)
  • Average current consumption in the quiescent state: < 50μA
  • Alarm state current:
    • with base type B24, B24-HP and B24D: 20 mA / 12+30V
    • with base type B24RD: 33 mA / 12V; 49mA/24V; 57mA/30V
    • with base type B12L/U: 18 mA / 9V; 29mA/12V; 32mA/15V
  • Class (in accordance with EN 54-5): B/S
  • Output in alarm state at terminal RI: 20mA (max)/ -3.3V
    • (Towards terminals +IN /+OUT)
  • Degree of protection: IP30
  • Wire Gauge for terminals: 0.4mm2 + 2.0mm2
  • Operational temperature range: -10°C ё +60°C
  • Relative humidity resistance: (93 ± 3)% @ 40°C
  • Dimensions (incl. base): ø102mm, h 42mm* / ø103mm, h 56mm**
  • Weight (incl. base): 160g* / 170g**

This manual is subject to change without notice!

DoP No: 240
Tested by EVPU: N.B.1293

Teletek Electronics JSC

  • 14A Srebarna Str, 1407 Sofia, Bulgaria

EN 54-5:2017+A1:2018
Detector Class B/S

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Teletek User Manuals

Related Manuals