Teletek SensoIRIS S130 Fire Alarm Optical Smoke Detector User Manual

June 9, 2024
Teletek

Teletek SensoIRIS S130 Fire Alarm Optical Smoke Detector

Introduction

Essential characterist Performance
Performance under fire conditions Pass
Operational reliability Pass

Durability:
Temperature resistance| Pass
Humidity resistance| Pass
Shock and vibration resistance| Pass
Corrosion resistance| Pass

Installation

| 10°C ÷ +60°C
---|---
| 0.4mm2 – 2.0mm2
| ~125g Without base
| Indoor use
| Outdoor use

Color

  • RAL 9016
    White

  • RAL 9005
    Black

Installation Instruction

ATTENTION: Read carefully this installation Instructions before installing the device! This manual is subject to change without notice!
SensoIRIS S130 IS is аn addressable optical-smoke detector with built-in isolator module designed for installing in addressable fire alarm systems supporting TTE communication protocol. The detector is powered on from the panel and can be controlled via the communication protocol. The detector SensoIRIS S130 IS is compatible with fire bases B124 (low profile, white/black color) and B124-HP (high profile, white color).

Installation Instructions
  1. Choose the proper place for installation of the fire detector. Refer to the given installation instructions. Note: Do not install the detector near sources of steam, condensation or smoke, e.g. from cigarettes.

  2. If you want to “lock” the detector to the base remove the little “tooth” on the top of the locking mechanism (located in the narrow part).

  3. Mount the fire base on the ceiling of the protected premises using fixings according the mounting surface.

  4. Connect the detector base to the fire panel using the wiring diagram.
    ATTENTION: Disconnect the loop power before installing the detector!

  5. Insert the detector into the base and rotate clockwise until it drops into place – the short mark on the base fits with that on the detector body. Continue to rotate the detector until the detector mark coincides with the long mark on the base – a click is heard.

  6. Test the detector for proper operation and LED indication.
    ATTENTION:
    The blinking of the two LEDs can be managed from the control panel (ON/ OFF).To turn the blinking on/ off you have to be a User with Access control level 3.
    Choose in consecutiveness from the control panel: System – Programming – Devices – Loop. Find the installed detector, as enter address, loop and zone number – the panel automatically will recognize the type of the detector. Choose the button MORE to enter in the additional settings menu and to review the SW version and ID number of the detector. The blinking of LEDs is turned on/ off with pressing the ON/OFF button in the “Led Blink” field.

  7. If the detector has been locked to the base, when open it for a service schedule maintenance and cleaning you have to use a plain screw-driver. Light press with the screw-driver into the base opening and at the same time rotate the detector head counterclockwise.

Warranty

All detectors carry on a warranty valid from the date of manufacture. The date of manufacture can be checked by the code on the back of the detector. The first two numbers represent the year and the last two – the month. For example: The date code “20 07”, means the detector is manufactured in July, 2020.
To return goods for warranty service, please contact with your local distributer for details.

Specifications

Vmax . . . . Max. line voltage
Vnom . . . . Nom. line voltage.
Vmin. . . . . Min. line voltage
Vso max . . Max. voltage at which the device isolates
Vso min . . Min. voltage at which the device isolates

Vsc max . . Max. voltage at which the device reconnects
Vsc min . . Min. voltage at which the device reconnects

Ic max . . . Max. rated continuous current with the switch closed
Is max . . . Max. rated switching current (e.g. under short circuit).
II max . . . . Max. leakage current with the switch open (isolated state
Zc max . . . Max. series impedance with the switch closed

  • Note : Switches from closed to open
    Note** : Switches from open to closed

Bases

Bases

Wiring Diagram

Wiring Diagram
Wiring Diagram

LED Indication

LED Indication

Blinking is enabled

Blinking| |
---|---|---
Light on| |
Light of| |

Blinking is disabled

Light on| |
---|---|---
Light of| ``|

LED Indication

Maintenance

Maintenance

Test
  1. Apply power to the detector.
  2. Wait for 30 sec
  3. Еxert influence on the fire detector by smoke generator (Aerosol Dispenser) or another device with aerosol simulator of smoke. Within 8 sec the fire detector will enter in fire condition. Both LEDs will light up.
  4. Power off the detector for 2 sec minimum. After resetting the detector will enter in duty mode and the LEDs will light off.
Cleaning and Maintenance
  1. Remove the detector from its base
  2. Remove the inner protective cover – press the four clips (1) with a plain screw-driver gently down to unlock the cover from the detector’s body.
  3. Dismount the PCB from the supporting clips (2).
  4. Clean the smoke chamber.
  5. Mount the PCB back to the detector’s body – as a reference point use the side with a cut-out (3). Rotate the PCB until the cutout coincides with the pin on the inner part from the detector body. Gently press the PCB down to fix in place.
  6. Mount the inner protective cover – the mark with a rectangular shape (4) fits with the channel at the inner side of the detector’s body and the contact plates on the PCB coincide with the four openings on the protective cover. Press gently down until a click is heard.
  7. Mount the detector back to its base and test for correct operation and LED indication.

The service maintenance of the detector should be provided:

  1. Inspection for visible physical damage – weekly.
  2. Operational test in real conditions – monthly.
  3. Check and clean dust contamination – six months.
  4. Check and clean base and head contacts and connections – annually.

Teletek Electronics JSC
Address: 14A Srebarna Str,
1407 Sofia, Bulgaria

Documents / Resources

| Teletek SensoIRIS S130 Fire Alarm Optical Smoke Detector [pdf] User Manual
SensoIRIS S130 Fire Alarm Optical Smoke Detector, SensoIRIS S130, Fire Alarm Optical Smoke Detector, Smoke Detector
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Teletek User Manuals

Related Manuals