TELETEK SensoIRIS WSST Intelligent Analogue Addressable Fire Alarm Sounder and Strobe Instruction Manual

June 9, 2024
Teletek

TELETEK SensoIRIS WSST Intelligent Analogue Addressable Fire Alarm

Sounder and Strobe

Installation Instruction

ATTENTION : Read carefully this installation Instructions before installing the device! This manual is subject to change without notice! SensoIRIS WSST is аn addressable Wall Mount Sounder and Strobe designed for installing in addressable fire alarm systems supporting TTE communication protocol. The device is powered on from the panel and can be controlled via the communication protocol. The sounder SensoIRIS WSST is compatible with fire bases B124 for ceiling or wall mounting and WSB IP65 for wall mounting (refer to manual 18020861 for details).

Installation Instructions
Attention: Power off the loop circuit before installing the SensoIRIS WSST addressable sounder!

  1. Choose the proper place for installation of the device.
  2. Set the device address using SensoIRIS Programmer or directly from addressable fire panel. The address must be in the range from 1 to 250.
  3. Mount the fire base on the ceiling or on the wall of the protected premises using fixings according the mounting surface.
  4.  Connect the base to the fire panel using the wiring diagram.
  5. Insert the device into the base and rotate clockwise until it drops into place – the short mark on the base fits with that on the sounder body. Continue to rotate the sounder until its mark coincides with the long mark on the base – a click is heard.
  6.  Program the device parameters. Choose in consecutiveness from the control panel: System – Programming – Devices – Loop. Find the installed sounder, as enter address, loop and zone number – the panel automatically will recognize the type of the device. Choose the button MORE to enter in the additional settings menu.
  7. Test the sounder for proper operation.

Warranty

All devices carry on a warranty valid from the date of manufacture. The date of manufacture can be checked by the code marking on the back of the device. The date is printed numbers – YY MM. The first two numbers represent the year and the last two – the month. For example: The date code “20 07”, means the device is manufactured in July, 2020.
To return goods for warranty service, please contact with your local distributer for details.

Essential characteristics Performance
Performance under fire conditions Pass
Operational reliability Pass
Duration of operation Pass
Provision for external conductors Pass
Flammability of materials Pass
Enclosure protection Pass
Access Pass
Manufacturer’s adjustments Pass
On-site adjustments of behavior Pass
Requirements for software controlled devices Pass
Coverage volume Pass
Variation of light output Pass
Min. and max. light intensity Pass
Light color White
Light temporal pattern/ frequency of flashing Pass
Marking and data Pass
Synchronization Pass

Durability:
Temperature resistance| Pass
Humidity resistance| Pass
Shock and vibration resistance| Pass
Corrosion resistance| Pass
Resistance to ingress| Pass
Electrical stability| Pass

Technical Specifications

  • Operating Voltage Range: 15 – 32VDC (Nom. 27VDC
  • Nominal consumption (stand-by): <500μА@27VDC
  • Maximal consumption (main tone type 27
    • low volume level, sound only: <5mА
    • low volume level, sound and strobe: <12mА
    • high volume level, sound only: <16.5mА
    • high volume level, sound and strobe: <22mА
  • Maximal consumption (other tone types
    • low volume level, sound only: <4mА
    • low volume level, sound and strobe: <11mА
    • high volume level, sound only: <10mА
    • high volume level, sound and strobe: <16.5mА
  • Power volume (main tone type 27):
    • low volume: ~ 80dB (A) ± 6dB @ 1m
    • high volume: ~ 92dB (A) ± 5dB @ 1m
  • Power volume (other tone types):
    • low volume: 75-85dB ± 3dB @ 1m
    • high volume: 80-95dB ± 3dB @ 1m
  • Number of tone types: 32
  • Supported communication protocol: TTE
  • Wire Gauge for terminals: 2.5mm2
  • Relative humidity resistance: (93 ± 3)% @ 40°C
  • Color: white
  • Material (transparent): SAN
  • Dimensions: 116x55mm

weighted sound level diagram

TELETEK SensoIRIS WSST Intelligent Analogue Addressable Fire Alarm Sounder
and Strobe 1

When used with base B124/ Bei Anwendung eines Sockels B124/ При използване на основа B124 When used with base WSB IP65 (Tested by EVPU)/ Bei Anwendung eines Sockels WSB IP65/

BASE INSTRUCTION

TELETEK SensoIRIS WSST Intelligent Analogue Addressable Fire Alarm Sounder
and Strobe 2

Wiring Diagram

TELETEK SensoIRIS WSST Intelligent Analogue Addressable Fire Alarm Sounder
and Strobe 3

Tone types and description

TELETEK SensoIRIS WSST Intelligent Analogue Addressable Fire Alarm Sounder
and Strobe 4

Teletek Electronics JSC Address: 14A Srebarna Str, 1407 Sofia, Bulgaria Fire alarm devices – Visual alarm device (VAD) intended for use in and around buildings

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Teletek User Manuals

Related Manuals