TELETEK SensoIRIS WSST Intelligent Analogue Addressable Fire Alarm Sounder and Strobe Instruction Manual
- June 9, 2024
- Teletek
Table of Contents
TELETEK SensoIRIS WSST Intelligent Analogue Addressable Fire Alarm
Sounder and Strobe
Installation Instruction
ATTENTION : Read carefully this installation Instructions before installing the device! This manual is subject to change without notice! SensoIRIS WSST is аn addressable Wall Mount Sounder and Strobe designed for installing in addressable fire alarm systems supporting TTE communication protocol. The device is powered on from the panel and can be controlled via the communication protocol. The sounder SensoIRIS WSST is compatible with fire bases B124 for ceiling or wall mounting and WSB IP65 for wall mounting (refer to manual 18020861 for details).
Installation Instructions
Attention: Power off the loop circuit before installing the SensoIRIS
WSST addressable sounder!
- Choose the proper place for installation of the device.
- Set the device address using SensoIRIS Programmer or directly from addressable fire panel. The address must be in the range from 1 to 250.
- Mount the fire base on the ceiling or on the wall of the protected premises using fixings according the mounting surface.
- Connect the base to the fire panel using the wiring diagram.
- Insert the device into the base and rotate clockwise until it drops into place – the short mark on the base fits with that on the sounder body. Continue to rotate the sounder until its mark coincides with the long mark on the base – a click is heard.
- Program the device parameters. Choose in consecutiveness from the control panel: System – Programming – Devices – Loop. Find the installed sounder, as enter address, loop and zone number – the panel automatically will recognize the type of the device. Choose the button MORE to enter in the additional settings menu.
- Test the sounder for proper operation.
Warranty
All devices carry on a warranty valid from the date of manufacture. The date
of manufacture can be checked by the code marking on the back of the device.
The date is printed numbers – YY MM. The first two numbers represent the year
and the last two – the month. For example: The date code “20 07”, means the
device is manufactured in July, 2020.
To return goods for warranty service, please contact with your local
distributer for details.
Essential characteristics | Performance |
---|---|
Performance under fire conditions | Pass |
Operational reliability | Pass |
Duration of operation | Pass |
Provision for external conductors | Pass |
Flammability of materials | Pass |
Enclosure protection | Pass |
Access | Pass |
Manufacturer’s adjustments | Pass |
On-site adjustments of behavior | Pass |
Requirements for software controlled devices | Pass |
Coverage volume | Pass |
Variation of light output | Pass |
Min. and max. light intensity | Pass |
Light color | White |
Light temporal pattern/ frequency of flashing | Pass |
Marking and data | Pass |
Synchronization | Pass |
Durability:
Temperature resistance| Pass
Humidity resistance| Pass
Shock and vibration resistance| Pass
Corrosion resistance| Pass
Resistance to ingress| Pass
Electrical stability| Pass
Technical Specifications
- Operating Voltage Range: 15 – 32VDC (Nom. 27VDC
- Nominal consumption (stand-by): <500μА@27VDC
- Maximal consumption (main tone type 27
- low volume level, sound only: <5mА
- low volume level, sound and strobe: <12mА
- high volume level, sound only: <16.5mА
- high volume level, sound and strobe: <22mА
- Maximal consumption (other tone types
- low volume level, sound only: <4mА
- low volume level, sound and strobe: <11mА
- high volume level, sound only: <10mА
- high volume level, sound and strobe: <16.5mА
- Power volume (main tone type 27):
- low volume: ~ 80dB (A) ± 6dB @ 1m
- high volume: ~ 92dB (A) ± 5dB @ 1m
- Power volume (other tone types):
- low volume: 75-85dB ± 3dB @ 1m
- high volume: 80-95dB ± 3dB @ 1m
- Number of tone types: 32
- Supported communication protocol: TTE
- Wire Gauge for terminals: 2.5mm2
- Relative humidity resistance: (93 ± 3)% @ 40°C
- Color: white
- Material (transparent): SAN
- Dimensions: 116x55mm
weighted sound level diagram
When used with base B124/ Bei Anwendung eines Sockels B124/ При използване на основа B124 When used with base WSB IP65 (Tested by EVPU)/ Bei Anwendung eines Sockels WSB IP65/
BASE INSTRUCTION
Wiring Diagram
Tone types and description
Teletek Electronics JSC Address: 14A Srebarna Str, 1407 Sofia, Bulgaria Fire alarm devices – Visual alarm device (VAD) intended for use in and around buildings