TELETEK SensoIRIS M140 IS Addressable Combined Detector Instruction Manual
- June 9, 2024
- Teletek
Table of Contents
- TELETEK SensoIRIS M140 IS Addressable Combined Detector
- Product Information
- Essential Characteristics
- Warranty
- Product Usage Instructions
- **SensoIRIS M140 IS
- Installation
- Isolator Module Technical Specifications
- Maintenance
- Cleaning and Maintenance
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
TELETEK SensoIRIS M140 IS Addressable Combined Detector
Product Information
The SensoIRIS M140 IS detector is an intelligent analogue addressable fire alarm heat and optical smoke detector with built-in isolator module. It is designed to be installed in addressable fire alarm systems supporting TTE communication protocol. The detector is powered on from the panel and can be controlled via the communication protocol. The device is compatible with fire bases B124 (low profile, white/black color) and B124-HP (high profile, white color). It has been tested and certified to meet EN 54-5:2017+A1:2018, EN 54-7:2018, CEA 4021:2003, and EN 54-17:2005/AC:2007.
Essential Characteristics
- Performance under fire conditions: Pass
- Operational reliability: Pass
- Durability of operational reliability:
- Temperature resistance: Pass
- Humidity resistance: Pass
- Shock and vibration resistance: Pass
- Corrosion resistance: Pass
- Wiring range: 0.4mm2 – 2.0mm2
- Indoor use / Innenmontage / Montaje interno
Warranty
The detector is warranted against defects in materials and workmanship for a period of two (2) years from the date of purchase. Refer to the user manual for the full terms and conditions of the warranty.
Product Usage Instructions
- Read the installation instructions carefully before installing the device. Note: Do not install the device without reading the installation instructions.
- If you want to lock the detector to the base, remove the little tooth on the top of the locking mechanism (located in the narrow part).
- Mount the fire base on the ceiling of the protected premises using fixings according to the mounting surface.
- Disconnect the loop power before installing the detector.
- Connect the detector base to the fire panel using the wiring diagram.
- Insert the detector into the base and rotate clockwise until it drops into place – the short mark on the base fits with that on the detector body. Continue to rotate the detector until the detector mark coincides with the long mark on the base – a click is heard.
- Test the detector for proper operation and LED indication. The blinking of the two LEDs can be managed from the control panel (ON/OFF). To turn the blinking on/off, you have to be a User with Access control level 3. Choose in consecutiveness from the control panel: System – Programming – Devices – Loop. Find the installed detector and enter address, loop, and zone number – the panel will automatically recognize the type of detector. Choose the button MORE to enter in the setting menu and button in the review the SW version Led Blink field and ID number of the detector. The blinking of LEDs is turned on/off with.
- If the detector has been locked to the base, when open it for a service schedule maintenance and cleaning, you have to use a plain screw-driver. Light press with the screw-driver into the base opening and at the same time rotate the detector head counterclockwise.
**SensoIRIS M140 IS
**
Intelligent analogue addressable fire alarm heat and optical smoke detector with built-in isolator module
Installation
Installation Instruction
ATTENTION: Read carefully this installation Instructions before
installing the device! This manual is subject to change without notice!
SensoIRIS M140 IS is аn addressable combined (optical-smoke and heat) detector
with built-in isolator module designed for installing in addressable fire
alarm systems supporting TTE communication protocol. The detector is powered
on from the panel and can be controlled via the communication protocol. The
detector SensoIRIS M140 IS is compatible with fire bases B124 (low profile,
white/black color) and B124-HP (high profile, white color).
-
Choose the proper place for installation of the fire detector. Refer to the given installation instructions. Note: Do not install the detector near sources of steam, condensation or smoke and close to natural heat sources.
-
If you want to “lock” the detector to the base remove the little “tooth” on the top of the locking mechanism (located in the narrow part).
-
Mount the fire base on the ceiling of the protected premises using fixings according the mounting surface.
-
Connect the detector base to the fire panel using the wiring diagram.
ATTENTION : Disconnect the loop power before installing the detector! -
Insert the detector into the base and rotate clockwise until it drops into place – the short mark on the base fits with that on the detector body. Continue to rotate the detector until the detector mark coincides with the long mark on the base – a click is heard.
-
Test the detector for proper operation and LED indication.
ATTENTION: The blinking of the two LEDs can be managed from the control panel (ON/ OFF).To turn the blinking on/ off you have to be a User with Access control level 3.
Choose in consecutiveness from the control panel: System – Programming – Devices – Loop. Find the installed detector, as enter address, loop and zone number – the panel automatically will recognize the type of the detector. Choose the button MORE to enter in the additional settings menu and to review the SW version and ID number of the detector. The blinking of LEDs is turned on/ off with pressing the ON/OFF button in the “Led Blink” field. -
If the detector has been locked to the base, when open it for a service schedule maintenance and cleaning you have to use a plain screw-driver. Light press with the screw-driver into the base opening and at the same time rotate the detector head counter-clockwise.
Warranty
All detectors carry on a warranty valid from the date of manufacture. The date
of manufacture can be checked by the code on the back of the detector. The
first two numbers represent the year and the last two – the month. For
example: The date code “20 07”, means the detector is manufactured in July,
2020.
To return goods for warranty service, please contact with your local
distributer for details.
Isolator Module Technical Specifications
Note: Switches from closed to open
Note: Switches from open to closed
Maintenance
Test
- Apply power to the detector.
- Wait for 30 sec.
- Exert influence on the fire detector by smoke generator (Aerosol Dispenser) or by aerosol simulator of smoke to test the optical part; or use heat tester (Cordless Heat Detector Tester or Heat Tester 110V>240V) at distance of 20 cm to test the heat part. Within 8 sec the fire detector will enter in fire condition. Both LEDs will light up.
- Power off the detector for 2 sec minimum. After resetting the detector will enter in duty mode and the LEDs will light off.
Cleaning and Maintenance
- Remove the detector from its base.
- Remove the inner protective cover – press the four clips (1) with a plain screw-driver gently down to unlock the cover from the detector’s body.
- Dismount the PCB from the supporting clips (2).
- Clean the chamber.
- Mount the PCB back to the detector’s body – as a reference point use the side with a cut-out (3). Rotate the PCB until the cut-out coincides with the pin on the inner part from the detector body. Gently press the PCB down to fix in place.
- Mount the inner protective cover – the mark with a rectangular shape (4) fits with the channel at the inner side of the detector’s body and the contact plates on the PCB coincide with the four openings on the protective cover. Press gently down until a click is heard.
- Mount the detector back to its base and test for correct operation and LED indication.
The service maintenance of the detector should be provided:
- Inspection for visible physical damage – weekly.
- Operational test in real conditions – monthly.
- Check and clean dust contamination – six months.
- Check and clean base and head contacts and connections – annually.