Salicru SLC TWIN RT2 Uninterruptible Power Supply Systems (UPS) User Manual
- June 9, 2024
- Salicru
Table of Contents
SLC TWIN RT2 Uninterruptible Power Supply Systems (UPS)
Product Information: SLC TWIN RT2 0,7.. 10 kVA Uninterruptible Power Supply
Systems (UPS)
Introduction
The SLC TWIN RT2 is an uninterruptible power supply system that provides backup power to connected devices in case of a power outage. The system is available in different power ratings ranging from 0,7 kVA to 10 kVA.
Safety Information
Before using the UPS, please read the safety information provided in the manual. The manual includes conventions and symbols used throughout the text to indicate specific actions or warnings.
Quality Assurance and Standards
The SLC TWIN RT2 UPS has been designed to meet high-quality standards. The management provides a statement of quality assurance, and the system complies with different environmental standards for use in different environments.
Presentation
The SLC TWIN RT2 UPS comes with different viewing and product definition options. The manual provides detailed information on how to set up and use the system. The UPS has various operating modes and notable features that ensure reliable backup power supply to connected devices.
Installation
Before installation, ensure you unpack and check the contents of the package. Follow the instructions provided in the manual to install the UPS correctly. Carefully consider where to site the UPS, immobilize it, and connect external batteries if needed. Ensure proper connection of load devices, earth terminals, EPO (emergency power off) terminals, digital input/output terminals, and manual bypass auxiliary contact terminals to avoid damage to the UPS or connected devices.
Usage Instructions
- Ensure the UPS is correctly installed and connected to the input source.
- Turn on the UPS and connected devices. The UPS will automatically start its operation.
- In case of a power outage, the UPS will supply backup power to connected devices for a specific amount of time depending on the load and battery capacity.
- When the power comes back, the UPS will automatically switch back to normal operation.
- If the UPS is equipped with optional extras such as an isolation transformer, communication card, or extendable guide kits, follow the additional instructions provided in the manual for proper installation and usage.
Follow the instructions provided in the manual to maintain the UPS properly. For any issues, contact customer support.
USER MANUAL
UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
SLC TWIN RT2 0,7.. 10 kVA
General index.
1. INTRODUCTION.
1.1. THANK YOU LETTER.
2. SAFETY INFORMATION.
2.1. USING THIS MANUAL. 2.1.1. Conventions and symbols used.
3. QUALITY ASSURANCE AND STANDARDS.
3.1. STATEMENT BY THE MANAGEMENT. 3.2. STANDARDS. 3.2.1. First and second
environment. 3.2.1.1. First environment. 3.2.1.2. Second environment. 3.3.
ENVIRONMENT.
4. PRESENTATION.
4.1. VIEWS. 4.1.1. Views of the device. 4.2. DEFINITION OF THE PRODUCT. 4.2.1.
Nomenclature. 4.3. OPERATING PRINCIPLE. 4.4. UPS OPERATING MODES. 4.4.1.
Notable features. 4.5. OPTIONAL EXTRAS. 4.5.1. Isolation transformer: 4.5.2.
Exterior manual maintenance bypass. 4.5.3. Communication card. 4.5.3.1.
Integration into computer networks using an SNMP
adapter. 4.5.3.2. Modbus RS485. 4.5.3.3. Interface to relays. 4.5.4.
Extendable guide kits for mounting in a rack cabinet.
5. INSTALLATION.
5.1. RECEPTION OF THE DEVICE. 5.1.1. Reception, unpacking and contents. 5.1.2.
Storage. 5.1.3. Unpacking. 5.1.4. Transport to the site. 5.1.5. Siting,
immobilising and considerations. 5.1.5.1. Rotation of the control panel with
LCD display. 5.1.5.2. Vertical tower-type mounting.
5.1.5.3. Vertical tower-type mounting with backup extension (battery module).
5.1.5.4. Mounting as a rack in a 19″ cabinet. 5.1.5.5. Rack mounting in a 19″
cabinet with backup extension
(battery module). 5.1.5.6. Vertical tower-type mounting with PDU. 5.1.5.7.
Rack mounting in 19″ cabinet with PDU. 5.1.5.8. Preliminary considerations
before connection. 5.1.5.9. Preliminary considerations before connection,
regarding
the batteries and their protections. 5.1.5.10. Connection elements. 5.2.
CONNECTIONS. 5.2.1. Connection of the input. 5.2.2. Connection to IEC
connectors or output terminals. 5.2.2.1. Connection of loads in models up to 3
kVA. 5.2.2.2. Connection of loads in 4 to 10 kVA 10 kVA. 5.2.3. Connection to
external batteries (backup extension). 5.2.4. Connection of the input earth
terminal ( ) and the earth
connection terminal ( ) . 5.2.5. Terminals for EPO (emergency power off).
5.2.6. Terminals for digital input and output to relay. Only in
models with power ratings > 3 kVA. 5.2.7. Manual bypass auxiliary contact
terminals. Only in models
with power ratings > 3 kVA. 5.2.8. Connection in parallel, only in models with
power ratings >
3 kVA. 5.2.8.1. Introduction in redundancy. 5.2.8.2. Installation and
operation in parallel. 5.2.9. Communication port. 5.2.9.1. RS232 and USB port.
5.2.10. Smartslotfortheintegrationofanelectroniccommunication
unit. 5.2.11. Protection against voltage spikes for the modem / ADSL /
fax, etc., line. . 5.2.12. Software. 5.2.13. Considerations before start-up
with connected loads.
6. OPERATION.
6.1. START-UP. 6.1.1. Checks before start-up. 6.2. UPS START-UP AND SHUTDOWN.
6.2.1. UPS start-up with mains voltage. 6.2.2. UPS start-up without mains
voltage.
2
SALICRU
6.2.3. UPS shutdown with mains voltage. 6.2.4. UPS shutdown without mains
voltage. 6.3. OPERATING PROCEDURE FOR A PARALLEL SYSTEM
(ONLY IN 4 TO 10 KVA MODELS). 6.4. HOW TO ADD A UPS TO A SYSTEM IN PARALLEL
OPERATION OR TO A FUNCTIONING SINGLE UPS (ONLY IN 4 TO 10 KVA MODELS). 6.5.
HOW TO REPLACE A FAULTY UPS IN AN OPERATIONAL PARALLEL SYSTEM.
7. CONTROL PANEL WITH LCD DISPLAY.
7.1. GENERAL INFORMATION FOR THE SERIES. 7.1.1. Information represented by the
display. 7.1.2. Common messages shown on the LCD display. 7.1.3. Common
abbreviations shown on the display. 7.2. CONTROL PANEL FOR MODELS UP TO 3 KVA.
7.2.1. Composition of the control panel with LCD display. 7.2.2. Audible
alarms. 7.2.3. Location of the adjustment parameters on the display. 7.2.4.
Settings. 7.2.4.1. Ah configuration of parameter `12′. 7.2.4.2. Operating mode
/ Description of state. 7.2.4.3. Warning or alert codes. 7.2.4.4. Error or
fault codes. 7.2.4.5. Warning or alert indicators. 7.3. CONTROL PANEL FOR 4
KVA TO 10 KVA MODELS. 7.3.1. Audible alarms. 7.3.2. Optical indications.
7.3.3. Location of the adjustment parameters on the display. 7.3.4. Settings.
7.3.4.1. Operating mode / Description of state. 7.3.4.2. Operating mode /
Description of state. 7.3.4.3. Warning or alert codes. 7.3.4.4. Error or fault
codes. 7.3.4.5. Warning or alert indicators.
8. MAINTENANCE, WARRANTY AND SERVICE.
8.1. BATTERY MAINTENANCE. 8.1.1. Notes for the installation and replacement of
the battery. 8.2. UPS TROUBLESHOOTING GUIDE. 8.2.1. Troubleshooting guide for
devices up to 3 kVA. 8.2.2. Troubleshooting guide for 4 kVA to 10kVA devices.
8.3. WARRANTY CONDITIONS. 8.3.1. Terms of the warranty. 8.3.2. Exclusions.
8.4. TECHNICAL SERVICES NETWORK.
9. ANNEXES.
9.1. GENERAL TECHNICAL SPECIFICATIONS. 9.2. GLOSSARY.
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
3
1. INTRODUCTION.
1.1. THANK YOU LETTER.
We thank you in advance for the trust placed in us in the purchasing of this
product. Read this instruction manual carefully in order to familiarize
yourself with its content, since the more you know and understand the
equipment the greater your satisfaction, level of safety and optimization of
its functionalities will be. We remain at your disposal for any additional
information or queries that you may wish to make.
Yours sincerely.
SALICRU
· The equipment described herein is capable of causing significant physical
damage in the event of improper handling. For this reason its installation,
maintenance and/ or repair must be carried out exclusively by our personnel or
by qualified personnel.
· Although no effort has been spared to ensure that the information in this
user manual is complete and accurate, we are not responsible for any errors or
omissions that may exist. The images included in this document are for
illustrative purposes and may not represent exactly the parts of the equipment
shown, therefore they are not contractual. However, any divergence that may
arise will be remedied or solved with the correct labelling on the unit.
· Following our policy of constant evolution, we reserve the right to modify
the characteristics, operations or actions described in this document without
prior notice.
· Reproduction, copying, assignment to third parties, modification or total or
partial translation of this manual or document, in any form or by any means,
without previous written authorization by our firm is prohibited, with the
full and exclusive property rights over the same being reserved by our firm.
4
SALICRU
2. SAFETY INFORMATION.
2.1. USING THIS MANUAL.
The documentation of any standard equipment is available to the customer on
our website for download (www.salicru.com). · For devices “powered by socket”,
this is the website for
obtaining the user manual and “Safety Instructions” EK26608. · For devices
with “permanent connection” via terminals, a CD-ROM or pen drive containing
all necessary information for connection and start-up, including “Safety
Instructions” EK26608, may be supplied with it. Before carrying out any
action on the device relating to its installation or start-up, change of
location, configuration or handling of any kind, carefully read the safety
instructions. The purpose of the user manual is to provide information
regarding safety and explanations of the procedures for installation and
operation of the equipment. Read them carefully and follow the steps indicated
in the order established.
Compliance with the “Safety Instructions” is mandatory and the user is legally
responsible for compliance and enforcement.
The equipment is delivered properly labelled for the correct identification of
each of the parts, which together with the instructions described in this user
manual allows the operations of installation and commissioning to be performed
in a simple and orderly manner without having any doubts whatsoever. Finally,
once the equipment is installed and operating, it is recommended to save the
documentation downloaded from the website, CD-ROM or Pen Drive in a safe and
easy-to-access place, for any future queries or doubts that may arise. The
following terms are used interchangeably in the document to refer to: · SLC TWIN RT2′,
TWIN RT2′, TWIN’,
RT2′, device’,
unit’ and UPS’ – Uninterruptible power supply. Depending on the context of the phrase, it can refer either to the actual UPS itself or to the the UPS and the batteries, regardless of whether it is all assembled in the same metal casing – box – or not. · “Batteries or accumulators”.- Group or set of elements that stores the flow of electrons by electrochemical means. ·
T.S.S.’ – Technical Service and Support. · `Client, installer, operator or
user’ – These are used interchangeably and by extension to refer to the
installer and/or operator who will carry out the corresponding actions, and
the same person may be responsible for carrying out the respective actions
when acting on behalf of, or in representation of, same.
2.1.1. Conventions and symbols used.
Some symbols may be used and appear on the equipment, batteries and/or in the
context of the user manual. For more information, see section 1.1.1 of
document EK266*08 on “Safety instructions”.
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
5
3. QUALITY ASSURANCE AND STANDARDS.
3.1. STATEMENT BY THE MANAGEMENT.
Our goal is customer satisfaction, therefore this Management has decided to
establish a Quality and Environment Policy, through the implementation of a
Quality and Environmental Management System that will enable us to comply with
the requirements demanded in the ISO 9001 and ISO 14001 and also by our
Customers and Stakeholders. Likewise, the management of the company is
committed to the development and improvement of the Quality and Environmental
Management System, through: · Communication to the entire company of the
importance of
satisfying both the client’s requirements as well as legal and regulatory
requirements. · The dissemination of the Quality and Environment Policy and
the setting of the Quality and Environment objectives. · Conducting reviews by
the Management. · Providing the necessary resources.
3.2. STANDARDS.
The SLC TWIN RT2 is designed, manufactured and sold in accordance with Quality
Management Standard EN ISO 9001. The marking indicates conformity with EC
Directives through the application of the following standards: · 2014/35/EU. –
Low voltage safety. · 2014/30/EU. – Electromagnetic Compatibility – EMC-. ·
2011/65/EU. – Restriction of the use of hazardous
substances in electrical and electronic equipment (RoHS).
According to the specifications of the harmonized standards. Reference
standards: · EN-IEC 62040-1. Uninterruptible Power Supplies -UPS-. Part
1-1: General and safety requirements for UPS used in user access areas. · EN-
IEC 62040-2. Uninterruptible Power Supplies -UPS-. Part 2: EMC requirements.
The manufacturer accepts no liability in the event of modification of or
intervention on the device by the user.
WARNING!: SLC TWIN RT2 0.7.. 3 kVA. This is a category C2 UPS. In a
residential environment, this product may cause radio interference, in which
case the user must take additional measures. SLC TWIN RT2 4.. 10 kVA. This is
a category C3 UPS. This is a product for commercial and industrial application
in the second environment; Installation restrictions or additional measures
may be necessary to avoid disturbances. It is not appropriate to use this
equipment in basic life support applications (BLS), where a failure of the
former can render vital equipment out of service or significantly affect its
safety or effectiveness. It is also not recommended in medical applications,
commercial transport, nuclear installations, or other applications
or loads, where a failure of the product can lead to personal or material
damages.
The EC declaration of conformity of the product is available to the customer
upon express request to our headquarters.
3.2.1. First and second environment.
The environment examples that follow cover most UPS installations.
3.2.1.1. First environment.
Environment including residential, commercial and light industry
installations, directly connected, without intermediate transformers, to a low
voltage public power grid.
3.2.1.2. Second environment.
An environment that includes all commercial, light industrial and industrial
establishments that are not directly connected to a low voltage power grid
supplying buildings used for residential purposes.
3.3. ENVIRONMENT.
This product has been designed to respect the environment and manufactured
according to ISO 14001.
Recycling of the equipment at the end of its useful life:
Our company undertakes to use the services of authorized and regulatory
companies to treat the set of products recovered at the end of their useful
life (contact your distributor).
Packaging:
For the recycling of the packaging there must be compliance with the legal
requirements in force, according to the specific regulations of the country
where the equipment is installed.
Batteries:
Batteries pose a serious danger to health and the environment. The disposal of
them shall be carried out in accordance with the laws in force.
6
SALICRU
4. PRESENTATION.
4.1. VIEWS.
4.1.1. Views of the device.
In Fig. 1 to Fig. 4, illustrations of the device are shown according to box
size in relation to the power rating of the model. However, because the
product is constantly evolving, discrepancies or slight contradictions may
arise. If in any doubt, the labelling on the equipment itself will always
prevail.
The nameplate of the device shows all of the values relating to its main
properties and characteristics. Act accordingly for its installation.
0.7 to 3 kVA models
4 to 10 kVA models
Battery module for 0.7 to 10 kVA models Fig. 1. Front view of 0.7 to 10 kVA
models and their
battery modules for extended backups.
USER MANUAL
Control panel with LCD display
Plastic front trim
BYPASS
BATTERY
LINE
FAULT
Control panel with LCD display
Plastic front trim
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
7
Output connector, with protection for modem/ADSL/fax, etc.
COM port Connector for Connector for connection to IEC output connectors programmable
Fan
USB external EPO external battery module. at disconnection, for non-critical loads
Standard and B1 0.7 to 1.5 kVA models
AC power IEC connector
Input connector for modem/ ADSL/fax, etc., lines
RS232 Earth Smart slot COM port connection protective cover
Non-programmable IEC output connectors, for critical loads
Output connector, with protection for modem/ADSL/fax, etc.
COM port Connector for Connector for connection to IEC output connectors programmable
Fan
USB external EPO external battery module. at disconnection, for non-critical loads
Standard and B1 2 kVA models
AC power IEC connector
Input connector for modem/ ADSL/fax, etc., lines
RS232 COM Earth Smart slot port connection protective cover
Non-programmable IEC output connectors, for critical loads
Output connector, with protection Smart slot
COM port Connector for connection to IEC output connectors programmable
for modem/ADSL/fax, etc.
protective cover
USB external battery module. at disconnection, for non-critical loads
Standard and B1 3 kVA models
AC power IEC connector 16 A IEC output connector
Fans
Input connector for modem/ Connector for Earth RS232 COM Non-programmable IEC output
ADSL/fax, etc., lines
external EPO connection port connectors, for critical loads
Communication bus for
parallel systems
Fans
RS232 COM COM port Digital
port
USB input/output
Smart slot protective cover
4 to 10 kVA models
Current signal bus for parallel systems
Manual Bypass auxiliary contact.
Output, earth, Connector for Input input terminals external EPO switch
Connector for connection to external battery module.
Standard 4 to 10 kVA models, represented with battery module
Fig. 2. Rear view of 4 to 10 kVA models.
8
SALICRU
Battery module for 0.7 to 3 kVA devices
VDC protection
Battery module input Output connector for
connector
battery module
Earth connection
Battery module VDC protection connector
Battery module for 4 to 10 kVA devices
Fig. 3. Rear view of battery modules for extended backups.
Battery module connector
Output circuit breaker
PDU for 4 to 6 kVA devices
Output IEC connectors
Output IEC connectors
Output circuit breaker
PDU for 8 to 10 kVA devices
Output IEC connectors
Output IEC connectors
Output circuit breaker
Fig. 4. Front view of PDU (power distribution unit).
Output IEC connectors
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
9
4.2. DEFINITION OF THE PRODUCT. 4.2.1. Nomenclature. SLC-8000-TWIN RT2 B1 WCO
EE29503
MOD BAT TWIN RT2 2x6AB003 40A WCO EE29503
EE* CO
W B0 B1 TWIN RT2 8000 SLC CF
Special customer specifications. ‘Made in Spain’ marking on UPS and packaging (for customs purposes). Private-label device. Without batteries. Device with extra charger and without batteries. Device series. Power in VA. Brand acronym (for UPS). Frequency converter (device without batteries).
EE* CO
W 40A 003 AB 6 2x 0/
TWIN RT2 MOD BAT
Special customer specifications. `Made in Spain’ marking on UPS and packaging (for customs purposes). Private-label device. Protection size. Last three digits of the battery code. Initials of the battery family. Number of batteries in one branch. Number of branches in parallel. Omit for one. Battery module without them, but with the necessary accessories to install them. Battery module series. Battery module.
Note related to B0 and B1 batteries: (B0) The device is supplied without
batteries, but with
a space reserved for installation in the same box for models whose standard
version specifies this. For other models, the battery pack will be installed
in the manner considered most appropriate (box, cabinet, rack, etc.). For B0
devices ordered, the cost of acquisition, installation and connection of the
batteries shall always be borne by the customer or distributor and under their
responsibility. Accessories such as screws, cables and battery connection
plates are considered optional and can be supplied upon request.
(B1) Device with a more powerful charger, which does not have a battery pack,
nor the possibility of installing them in the same box. If an accumulator
module is required, it will need to be ordered as a separate item, which will
be connected to the UPS using the supplied cable.
Before connecting a module or group of batteries to the device or another
available module, it is necessary to check that the voltage value printed on
the back of the device next to the battery connector is appropriate and that
the polarity between the means of connection corresponds. For more
information, see Chapter 9 of this document.
10
SALICRU
4.3. OPERATING PRINCIPLE.
This manual describes the installation and operation of SLC TWIN RT2 series
UPSs as devices that can be independently operated or connected in parallel
(for models > 3 kVA). SLC TWIN RT2 series UPSs ensure optimum protection of
any critical load, maintaining the supply voltage of the loads between the
specified parameters without interruption during failure, deterioration or
fluctuation of mains power, and come in a wide range of models (from 0.7 kVA
to 10 kVA), enabling the end user to select the model that best suits his
needs. Thanks to their PWM (pulse width modulation) and doubleconversion
technology, SLC TWIN RT2 series UPSs are compact, cool, silent and high
performance. The double converter principle eliminates all mains power
disturbances. A rectifier converts the AC current of the mains into DC
current, thereby maintaining optimum battery charge level and powering the
inverter, which, in turn, generates a suitable AC sine-wave voltage for
continuously powering the loads. In the event of failure of the UPS’s mains
power, the batteries supply clean power to the inverter. The design and
construction of the SLC TWIN RT2 series UPS has been carried out in accordance
with international standards. In addition, models with power ratings greater
than 3 kVA can be expanded with the connection of additional modules with the
same power in parallel to obtain N+X redundancy or an increase in the system’s
power. Thus, this series has been designed to maximise the availability of
critical loads and to ensure that your business is protected from variations
in power distribution line voltage, frequency, electrical noise, cuts and
micro-cuts. This is the primary goal of SLC TWIN RT2 series UPSs. This manual
applies to the standardised models shown in Tab. 1.
4.4. UPS OPERATING MODES.
· Normal mode. Device running supplying output voltage from the inverter.
Mains power present with correct input voltage and frequency.
· Battery mode. Device running with mains voltage or frequency out of range or
without AC input power, either due to mains failure or absence of cable
connection, supplying output voltage from the batteries.
· Bypass mode. Device running or not, supplying output voltage directly from
the AC mains. With the inverter running, this operating mode may be due to an
overload, blockage or inverter fault. The actions for each incident will be as
follows: Reduce the load connected to the output, unblock the device by
resetting it stop it and start it up again and, if the blockage or fault
remains, contact T.S.S. With the inverter shut down, the output supplies mains
power directly through the static bypass of the device provided that it has AC
input power.
· Frequency converter (CF) mode. Operating mode of the UPS as a frequency
converter. In this mode, the static bypass is disabled by the condition of
disparate input and output frequencies.
Even if the LCD display on the backlit control panel shows messages, it does
not mean that the inverter is operational. It is switched on by pressing the
ON’ button on the control panel, see Chapter 6. 4.4.1. Notable features. · True on-line with double-conversion technology and output frequency separate from the mains. · Output power factor 1, except for B1 models where it is 0.8. Pure sine waveform, suitable for almost all kinds of loads. · Input power factor > 0.99 and high overall performance (between 0.89 and 0.91 for 0.7 to 3 kVA models and > 0.93 for higher power ratings). Greater energy savings and lower user installation costs (wiring), as well as low distortion of the input current, which reduces pollution in the power supply network. · Great adaptability to the worst conditions of the mains. Wide input voltage, frequency and waveform ranges, thus avoiding excessive dependence on limited battery power. · Possibility of fast and easy backup extension by adding modules in rack format. Each battery module has two connectors for easy connection to the device and other identical modules. · Availability of battery chargers of up to 6 A to reduce battery recharge times. · N+X redundant parallel connection to increase reliability and flexibility in power models > 3 kVA, with a maximum of 3 devices in parallel. · Selectable high-performance mode (ECO MODE) > 0.95 to 0.99 depending on model. Energy savings, economically beneficial for the user. · Possibility of starting the device without mains power supply or discharged battery. Be careful with this aspect because the greater the batteries are discharged, the more the backup will be reduced. · Intelligent battery management technology is very useful for extending the life of accumulators and optimising recharge times. · Standard communication options via the RS232 serial port or USB port. · Digital input for device Start/Stop and
Error or fault’ digital output in
models with power ratings > 3 kVA.
· Remote emergency power off control (EPO). · Control panel with LCD display
available on all models and
LED indicators on devices with power ratings > 3 kVA. · Availability of
optional connectability cards to improve
communication capabilities. · Device that can be installed as a tower or rack
using the
accessories supplied. The control panel can be rotated to adapt to either
format.
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
11
Model
Type
SLC-700-TWIN RT2
SLC-1000-TWIN RT2
SLC-1500-TWIN RT2
SLC-2000-TWIN RT2
Standard
SLC-3000-TWIN RT2
SLC-4000-TWIN RT2
SLC-5000-TWIN RT2
SLC-6000-TWIN RT2
SLC-8000-TWIN RT2
SLC-10000-TWIN RT2
SLC-700-TWIN RT2 (B0)
SLC-1000-TWIN RT2 (B0)
SLC-1500-TWIN RT2 (B0)
Without batteries
SLC-2000-TWIN RT2 (B0)
SLC-3000-TWIN RT2 (B0)
SLC-4000-TWIN RT2 (B0)
SLC-5000-TWIN RT2 (B0)
SLC-6000-TWIN RT2 (B0)
SLC-8000-TWIN RT2 (B0)
SLC-10000-TWIN RT2 (B0)
Long backup with additional charger
SLC-700-TWIN RT2 (B1)
SLC-1000-TWIN RT2 (B1)
SLC-1500-TWIN RT2 (B1)
SLC-2000-TWIN RT2 (B1)
SLC-3000-TWIN RT2 (B1)
SLC-4000-TWIN RT2 (B1)
SLC-6000-TWIN RT2 (B1)
SLC-8000-TWIN RT2 (B1)
SLC-10000-TWIN RT2 (B1)
Tab. 1. Standardised models.
Input/output type Single-phase / Single-phase.
4.5. OPTIONAL EXTRAS.
Depending on the configuration chosen, the device may include any of the
following options:
4.5.1. Isolation transformer:
The isolation transformer provides galvanic isolation in order to completely
isolate the output from the input and/or change neutral mode. The placement of
an electrostatic screen between the primary and secondary windings of the
transformer provides a high level of electrical noise attenuation. The
isolation transformer can be physically placed at the input or output of the
UPS depending on the technical conditions of the whole system (device supply
voltage and/or load voltage, characteristics or their type, etc.). In parallel
systems, it is not possible to operate with independent transformers for each
UPS; on the contrary, it is necessary to have a single common element for the
total adequate power. In any event, it will always be supplied as a peripheral
component external to the device itself in a separate box.
4.5.2. Exterior manual maintenance bypass.
The purpose of this option is to electrically isolate the device from the
mains and the critical loads without cutting the power to the latter. In this
way, maintenance or repair operations on
the device can be carried out without interruptions to the power supply of the
protected system, while preventing unnecessary hazards for the technical
personnel.
4.5.3. Communication card.
The UPS features a slot at the rear for inserting one of the following
communication cards.
4.5.3.1. Integration into computer networks using an SNMP adapter.
Large computer systems based on LANs and WANs that integrate servers in
different operating systems must provide the system manager with ease of
control and administration. This facility is obtained through an SNMP adapter,
which is universally supported by the main software and hardware
manufacturers. Connection of the UPS to the SNMP is internal while that of the
SNMP to the computer network is made through a RJ45 10 base connector.
4.5.3.2. Modbus RS485.
Large computer systems based on LANs and WANs often require that communication
with any element that is integrated into the computer network be made through
a standard industrial protocol. One of the most used standard industrial
protocols on the market is the MODBUS protocol.
4.5.3.3. Interface to relays.
· The UPS has, as an option, an interface to relays card that provides digital
signals in the form of potential-free contacts, with a maximum applicable
voltage and current of 240 V AC or 30 V DC and 1A.
· This communication port enables dialogue between the device and other
machines or devices through the relays supplied in the terminal block arranged
on the same card, with a single common terminal for all of them. From the
factory, all contacts are normally open and can be changed one by one, as
indicated in the information supplied with the optional extra.
· The most common use of these types of ports is to provide the necessary
information to the file-closing software.
· For more information, contact our T.S.S. or our nearest distributor.
4.5.4. Extendable guide kits for mounting in a rack cabinet.
An extendable and unique guide kit is available for all device models, valid
for any kind of rack-type cabinet. These guides allow the installation of any
TWIN RT2 device unit and possible battery modules in the case of extended
backups, as if it were a rack in its respective cabinet.
12
SALICRU
5. INSTALLATION.
·
Read and respect the Safety Information, described
in chapter 2 of this document. Failure to obey some
of the instructions described in this manual can result in a
serious or very serious accident to persons in direct contact
or in the vicinity, as well as faults in the equipment and/or
loads connected to it.
· In addition to the device’s own user manual, other
documents are supplied on the CD-ROM or documentation
pen drive. Consult them and strictly follow the indicated
procedure.
· Unless otherwise indicated, all actions, instructions,
guidelines and notes are applicable to the devices, whether
or not they form part of a parallel system.
5.1. RECEPTION OF THE DEVICE.
· Pay attention to section 1.2.1. of the safety instructions -EK266 * 08- in
all matters relating to the handling, movement and location of the unit.
· Use the most suitable means to move the UPS while it is packed, with a
transpalet or forklift.
· Any handling of the device must be carried out in accordance with the
weights shown in the technical specifications according to the model,
indicated in chapter `9. Annexes’.
5.1.1. Reception, unpacking and contents.
· Reception. Check that: The data on the label affixed to the packaging
correspond to those specified in the order. Once the UPS is unpacked, check
the previous data with those of the equipment nameplate. If there are
discrepancies, file the disagreement as soon as possible, citing the equipment
manufacture number and the delivery note references. It has not suffered any
mishaps during transportation (packaging and impact indicator in perfect
condition). Otherwise, follow the protocol indicated on the label attached to
the impact indicator, located on the packaging.
· Unpacking. To check the contents, it will be necessary to remove the
packaging. Complete the unpacking according to the procedure of section 5.1.3.
Content.
· Content 0.7 to 3 kVA device: 1 UPS. Quick guide on paper. Information
for warranty registration. 1 USB cable. 3 cables with IEC connectors for
loads. 1 cable for the device’s AC power supply. 2 metal pieces for use as
handles and screws for installing the unit in a rack cabinet. 4 plastic
pieces for use as a base to facilitate the arrangement of the UPS as a tower
(vertical position).
Optional battery module for 0.7 to 3 kVA UPS: 1 battery module.
Information for warranty registration. 2 metal pieces for use as handles and
screws for installing the unit in a rack cabinet. 2 plastic pieces to extend
the base of the UPS and enable the arrangement of the attached battery module
in its mounting as a tower. 1 cable for interconnecting the battery module
and UPS or other module.
4 to 10 kVA device: 1 UPS. 1 PDU module (power distribution unit).
Information for warranty registration. 2 metal pieces for use as handles and
screws for installing the UPS in a rack cabinet. 2 metal pieces for use as
handles and screws for installing the PDU in a rack cabinet. 1 metal piece
and screws for mounting the PDU attached to the UPS arranged as a tower. 1
USB cable. 4 plastic pieces for use as a base to facilitate the arrangement
of the UPS as a tower (vertical position). 1 cable for connecting the
communication bus. Useful only for connection to a parallel device. 1 cable
for connecting the current bus. Useful only for connection to a parallel
device. 1 cable for interconnecting the battery module and UPS.
4 to 10 kVA battery module: 1 battery module. Information for warranty
registration. 2 metal pieces for use as handles and screws for installing
the unit in a rack cabinet. 2 plastic pieces to extend the base of the UPS
and enable the arrangement of the attached battery module in its mounting as a
tower. 1 cable for interconnecting the battery module and another module.
· Once the reception is completed, it is advisable to re-pack the UPS until it
is put into service in order to protect it against mechanical shock, dust,
dirt, etc.
· The packaging of the device consists of a wooden pallet, cardboard or wooden
box, depending on the item, expanded polystyrene corners, polyethylene cover
and strapping, all of which are recyclable materials. When the packaging
requires disposal, it must be carried out in accordance with current laws. We
recommend keeping it for at least 1 year.
5.1.2. Storage.
· The device should be stored in a dry, ventilated room and
protected from rain, dust, and water or chemical splashes. It
is advisable to keep each device and battery unit in its orig-
inal packaging, as it has been specifically designed to en-
sure maximum protection during transportation and storage.
·
For devices that contain Pb-Ca batteries, the
charging times indicated in Tab. 2 of document
EK266*08, determined by the temperature to which they
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
13
are exposed, must be respected, otherwise the warranty may be invalidated. ·
After this period, connect the device to the mains together with the battery
unit if applicable, start it according to the instructions described in this
manual and charge for 12 hours. In parallel systems, it is not necessary to
interconnect devices before battery charging. Each of them can be treated
independently to charge them. · Then shut down the device, disconnect it and
store the UPS and batteries in their original packaging, noting the new date
for recharging the batteries on a document as a record or even on the
packaging itself. · Do not store the devices where the ambient temperature
exceeds 50ºC or drops below -15ºC, as this may cause degradation of the
electrical characteristics of the batteries.
5.1.3. Unpacking.
· The packaging of the device consists of a cardboard box, expanded
polystyrene (EPS) or polyethylene foam (EPE) corners, polyethylene cover and
strapping, all of which are recyclable materials; consequently, if it requires
disposal, it must be carried out in accordance with current laws. We recommend
keeping the packaging in case it needs to be used in the future.
· Proceed as follows: Cut the straps around the cardboard box. Remove the
accessories (cables, brackets, etc. ) Remove the device or battery module from
the box with the help, if necessary, of a second person depending on the
weight of the model or using appropriate mechanical means. Remove the
protective corners from the device and the plastic bag. Do not leave the
plastic bag within the reach of children to avoid danger of suffocation.
Inspect the device before proceeding and, in the event of finding damage,
contact the supplier or, failing that, our firm.
5.1.4. Transport to the site.
It is recommended to transport the UPS by means of a pallet jack or the most
appropriate method considering the distance between the two points. If the
distance is considerable, it is recommended to transport the device in its
packaging to the installation site and then unpack it.
5.1.5. Siting, immobilising and considerations.
· All TWIN RT2 series UPSs are designed to be mounted as a tower model
-vertical arrangement of the device- or rack -horizontal arrangement- for
installation in 19″ cabinets, regardless of whether they operate independently
or as parallel systems, whether or not they have a battery module or whether
the available backup is standard or extended (greater number of battery
modules). Follow the instructions indicated in the sections relating to
either of the two possibilities, according to the particular configuration of
your device. · Figs. 5 to 11 show, by way of example, illustrations of a
device with or without battery module. These illustrations provide help and
guidance in the steps to follow, but the instructions are not intended to
refer to a single model, although, in practice, the actions to be carried out
are always the same for all of them. · For all instructions regarding
connections, refer to section 5.2. 5.1.5.1. Rotation of the control panel with
LCD display.
Fig. 5. Rotation of the control panel with LCD display on the plastic front
trim.
· To facilitate the reading of messages on the display when the device is
installed vertically, it is possible to rotate the control panel clockwise by
90º (see Fig. 5).
· Likewise, reverse the rotation of the control panel if a device arranged as
a tower needs to be installed as a rack. In this case, the rotation of the
control panel will be anticlockwise.
· Proceed as follows: Insert fingertips into the recesses of the plastic trim
around the display and pull outwards. Rotate the control panel with LCD
display 90º to the right with respect to its initial position and insert it
back into the front.
5.1.5.2. Vertical tower-type mounting. · Rotate the control panel according to
section 5.1.5.1. · Take the 4 pieces of plastic supplied with the device and
join them together in twos to obtain two bases. · Place the UPS upright
between the two bases at a distance
of 70 mm from each end (see Fig. 6).
14
SALICRU
and install them to obtain two bases to hold the device and the battery module. · Place the UPS and battery module upright between the two bases (see Fig. 7) and at a distance of 70 mm from each end, similar to as shown in Fig. 7.
Fig. 6. Vertical tower-type mounting.
5.1.5.3. Vertical tower-type mounting with backup extension (battery module).
· The description in this section refers to a device with a single battery
module. For a greater number, proceed in a similar way.
· Rotate the control panel according to section 5.1.5.1. · Take the 4 plastic
pieces in the form of an angle supplied
with the UPS and the two supplied with the battery module,
Fig. 7. Vertically mounted tower-type model with backup extension (battery
module).
5.1.5.4. Mounting as a rack in a 19″ cabinet.
· To mount a device in a 19″ rack cabinet, proceed as follows (see Fig. 8):
Using the supplied screws, fix the two adapter angles for use as handles on
each side of the UPS, respecting your hand. To install the device in a rack
cabinet, it is necessary to have internal lateral guides for use as supports.
Alternatively, and upon request, we can supply universal slides for use as
guides, for installation by the user. Mount the guides at the required height,
ensuring correct tightening of the fixing screws and appropriate fitting in
the machining, according to each case. Place the device onto the guides and
insert it all the way to the back. Depending on the device model and weight,
and/or whether it is installed in the upper or lower part of the cabinet, it
is recommended that two people carry out the installation operations. Fix the
UPS to the cabinet frame using the screws supplied with the handles.
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
15
Fig. 8. Rack-type mounting in a 19″ cabinet.
5.1.5.5. Rack mounting in a 19″ cabinet with backup extension (battery
module).
· This section describes a device with one battery module. For more battery
modules, repeat the same procedure for each of them.
· To install a device and its battery module in a 19″ rack cabinet, proceed as
follows (see Fig. 9): Using the supplied screws, fix the two adapter angles
for use as handles on each side of the UPS, respecting your hand. Repeat the
same procedure for the battery module. To install each unit, UPS and battery
module in a rack cabinet, it is necessary to have internal lateral guides for
use as supports. Alternatively, and upon request, we can supply universal
slides for use as guides, for installation by the user. Mount the guides at
the required height, ensuring correct tightening of the fixing screws and
appropriate fitting in the machining, according to each case. Place the device
onto the guides and insert it all the way to the back. Proceed in the same way
for the battery module. Depending on the weight of each unit according to the
type of device and battery module, and/or whether it is installed in the upper
or lower part of the cabinet, it is recommended that two people carry out the
installation operations. Fix the UPS and the battery module to the cabinet
frame by means of the screws supplied with the respective handles.
Fig. 9. Rack-mounted model in a 19″ cabinet with backup extension (battery
module).
5.1.5.6. Vertical tower-type mounting with PDU. 4 to 10 kVA models are
supplied as standard with a PDU module, designed to be attached to the side of
the device. Fix it to the UPS using the plate supplied as a support as shown
in Fig. 10.
Fig. 10. Vertically mounted tower-type model with PDU. 5.1.5.7. Rack mounting
in 19″ cabinet with PDU. Similar to the UPS, the PDU module has angles for use
as handles for mounting in a rack cabinet. · Proceed as follows (see Fig. 11):
Using the supplied screws, fix the two adapter angles for use as handles on
each side of the PDU, respecting your hand.
According to each case, perform the steps indicated in section 5.1.5.4 or
5.1.5.5.
To install the PDU in a rack cabinet, it is necessary to have internal lateral
guides for use as supports, just like for the UPS and/or battery module.
Follow the guidelines described in section 5.1.5.4 or 5.1.5.5 for everything
related to the guides.
Place the PDU onto the guides and insert it all the way to the back.
Fix it to the cabinet frame using the screws supplied with the handles.
16
SALICRU
Fig. 11. Rack-type mounting in a 19″ cabinet with PDU.
5.1.5.8. Preliminary considerations before connection.
· In the description of this manual, reference is made to the
connection of terminals and switch operations that are
only available in some versions or devices with extended
backup. Ignore the related operations if your unit does not
feature them.
· Thermal control of these devices is carried out with the
passage of forced air from the front to the rear.
The front surface and about 15 cm on the rear side should
be left free of obstructions to facilitate the free circulation
of air for ventilation.
· Follow and respect the instructions described in this section
referring to the installation of a single device or a system
in parallel.
· Protection or external manual bypass board:
The system will have at least one short-circuit
protection on the UPS’s power supply line.
It is advisable to have an external manual bypass board
fitted with input, output and manual bypass protections
in single systems.
For parallel systems, it is essential to have a
distribution or manual bypass board. The board’s
circuit breakers must be able to isolate a UPS from
the system in the event of a fault and power the loads
with the others, either during periods of preventative
maintenance or during breakdown and repair.
· Upon request, we can supply an external manual bypass
board for a single device or parallel system.
You can also choose to manufacture it, taking into account
the version and configuration of the device or system
available and the documentation contained in the CD-ROM
or pen drive relating to `Recommended installation’.
·
In the documentation supplied with this user manual
and/or on the CD-ROM or pen drive, information is
available on `Recommended installation’ for each input and
output configuration. This documentation includes wiring
diagrams and information about the sizes of the protections
and the minimum cross sections of cables connected to the
device according to their rated working voltage. All values
are calculated for a maximum total cable length of 30 m
between the distribution board, equipment and loads.
For longer lengths correct the cross sections to avoid
voltage drops, respecting the regulations or standards
corresponding to the country.
In the same documentation and for each configuration,
information for `N’ units in parallel, as well as backfeed
protection characteristics, is available.
·
In parallel systems, the length and cross section of
the cables that run from the distribution or manual
bypass board to each UPS and from these to the board will
be the same for all of them without exception.
· The cross section of the cables must always be considered
in relation to the size of the terminals of the switches, so
that they are correctly fastened across their entire cross
section for optimum contact between the two elements.
· Only rated currents are printed on the nameplate of the
equipment as indicated by the EN-IEC 62040-1 safety
standard. For the calculation of the input current, the power
factor and the equipment’s own performance have been
considered.
Overload conditions are considered a non-permanent
and exceptional working mode, and will not be taken
into account in the application of the protections. Do not
connect appliances or devices which may overload the UPS
to the terminals and/or outlets, such as motors.
· If peripheral input, output or bypass elements such as
transformers or autotransformers are added to the UPS or
parallel system, the currents indicated on the nameplates of
these elements must be taken into consideration in order to
use the appropriate cross sections, in compliance with local
and/or national Low Voltage Electrotechnical Regulations.
· When a galvanic isolation transformer is added to a UPS
or parallel system as an optional extra, as standard or
independently, either on the input line, at the output or
both, it must be fitted with protection against indirect
contact (differential circuit breaker) at the output of each
transformer, since, due to its own insulation properties, it
will prevent the tripping of the protections placed on the
primary of the isolation transformer in case of electric shock
on the secondary (output of the isolation transformer).
· We remind you that all the isolation transformers installed
or factory supplied, have the output neutral grounded
through a bridge between the neutral terminal and ground.
If the isolated output neutral is required, this bridge must be
removed, taking the precautions indicated in the respective
local and/or national low voltage regulations.
·
This device is suitable for installation in networks
with TT, TN-S, TN-C or IT power distribution
systems, taking into account at the time of installation the
particularities of the system used and the national electrical
regulations of the destination country.
· The SLC TWIN RT2 features terminals for the installation
of an external emergency power off button (EPO) or, failing
that, a single device must be installed to cut the power
supply to the loads in any operating mode.
5.1.5.9. Preliminary considerations before connection, regarding the batteries and their protections.
· SLC TWIN RT2 devices from 0.7 to 3 kVA incorporate the batteries in the same
box as the device, except for B0, B1 and higher power models.
· The battery protection of the device and of any accumulator module is always
by means of internal fuses that are not accessible to the user.
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
17
·
IMPORTANT FOR SAFETY: If batteries are installed
independently, the accumulator group must be fitted
with a bipolar circuit breaker or disconnect fuse of the size
indicated in Tab. 2.
· Inside the battery module, there are HAZARDOUS
VOLTAGES with risk of electric shock, so it is classified as a
RESTRICTED ACCESS AREA.
·
Do not handle the fuse holder or battery circuit
breaker when the device is running.
·
If the mains power of the device or parallel system
is cut for longer than a simple intervention and it is
expected that it will be out of service for a prolonged period
time, the system must be shut down completely.
·
The battery circuit is not isolated from the input
voltage. Dangerous voltages can occur between the
terminals of the battery group and the earth. Check that
there is no input voltage before intervening on the terminals.
5.1.5.10. Connection elements.
· All of the device’s electrical connections are made from the back of each unit: Input and output connection. For models up to 3 kVA. Input by means of a cable with plug, connectable to the UPS through an IEC connector. Outputs through IEC connectors. For models with power ratings greater than 3 kVA. Terminals for powering the device and loads. It is necessary to remove the transparent protective cover to access the terminals. Replace the cover after making the connections to prevent possible accidents due to direct contact, especially in tower mountings as there is a greater risk. Connection to batteries. The device and battery module have a polarised connector. Remove the screws and protective cover of the connector before interconnecting it. All battery modules have two connectors that enable backup extension. Communication connectors available: DB9 for RS232. In models up to 3 kVA, the interface to relays signals are supplied with the same connector. USB to operate the UPS as a PC peripheral. Digital input and output (only in models
3 kVA). For connection to external EPO button. Auxiliary contact for the manual bypass switch (only in models > 3 kVA). DB15 communication bus connectors and analogue current signal block for connecting systems in parallel (only in models > 3 kVA). To access the signal block, it is necessary to remove its protective cover. Slot for the integration of one of the optional electronic communication units. Remove the fixing screws and plastic cover to enable it to be inserted.
· It is recommended to use terminals on all of the ends of the cables
connected to power terminals (input and output).
· Check that the terminal screws are correctly tightened.
5.2. CONNECTIONS.
5.2.1. Connection of the input.
· 0.7 to 3 kVA models:
Take the power cable with plug and IEC connector on
the end and insert the latter into the input connector
of the UPS.
Plug the power cable into an AC power socket with
earthing.
· 4 to 10 kVA models:
As the device has Class I protection against
electric shock, it is essential to install a
protective earth conductor (connect earth ( )).
Connect this conductor before supplying voltage to the
input terminals.
Connect the power cables to the input terminals
respecting the order of the phase (R) and the
neutral (N) indicated on the labelling of the device and in
this manual. Pay particular attention when connecting
the power cables to the input terminals and do not
reverse the connection to the output terminals or vice
versa. Failure to respect the order will result in faults.
Where there are discrepancies between the labelling
and the instructions in this manual, labelling shall
always prevail.
In accordance with safety standard EN-IEC 62040-1, the
facility must be equipped with an automatic backfeed
protection system, such as a contactor, which prevents
the appearance of hazardous voltage or power on the
UPS input line during a mains failure (see Fig. 12).
The standard applies to both individual units and all
UPSs in parallel systems.
There can be no derivation of the line that goes
from the backfeed protection to the UPS, as this
would breach the safety standard.
Warning labels shall be affixed to all primary power
switches installed in areas remote from the equipment
to alert electrical maintenance personnel of the
presence of a UPS in the circuit.
The label shall bear the following text or an equivalent:
Before working on the circuit. · Isolate the uninterruptible power supply
system
(UPS). · Check the voltage between all terminals, including
the protective earth.
Return voltage risk of the UPS.
18
SALICRU
U (L)
Input Output
(1)
N
R (L)
N
UPS
(2)
(3)
(1) Automatic backfeed protection system external to the UPS (EN-IEC 62040-1).
(2) Fuse holder and general purpose fuse 250V AC / 3A type F. (3) 230V AC
bipolar contactor with minimum contact spacing of 1.4 mm and coil
with same voltage and the minimum current indicated on the nameplate of the
UPS (input or bypass as appropriate). For parallel systems, each device must
have its own separate backfeed protection.
Fig. 12. Backfeed protection wiring diagrams.
5.2.2. Connection to IEC connectors or output terminals.
· SLC TWIN RT2 devices feature female IEC output connectors
or terminals depending on the power of the model:
Models up to 2 kVA: 2 groups of 4 x 10A IEC
connectors identified as «OUTPUT» and «OUTPUT
PROGRAMMABLE (P1)», configurable through the
control panel and/or ViewPower.
3 kVA models: same connectors as models up to 2 kVA
and an additional 16A IEC connector.
4 to 10 kVA models: 1 group of output terminals.
In these models, a PDU (power distribution unit) is
supplied to connect to the output terminals of the
UPS. Through it, loads can be powered directly through
the two or three groups of 10 or 16 A IEC connectors
protected by a selective circuit breaker.
·
Do not connect loads that in their entirety exceed
the specifications of the device, as this would cause
inconvenient cuts in the power supply of the loads
connected to the output.
· If, in addition to the more sensitive `critical loads’, it is
necessary to connect high-consumption inductive loads,
such as for laser printers or CRT monitors, the starting up
of these peripherals will need to be taken into account to
prevent the device from crashing.
We do not recommend connecting loads of this type due to
the amount of power they absorb from the UPS.
5.2.2.1. Connection of loads in models up to 3 kVA.
· Connect the loads to the 10 A IEC connectors. It is important to consider
the two groups of IEC connectors available, those for critical loads’ and those for
non-critical loads’. By definition, `critical loads’ are considered
to be those that can cause economic damage if they stop functioning or
function incorrectly.
The IEC connectors indicated in Fig. 2 as `non-critical
loads’ can be programmed as such through the control
panel. In this case, the backup of the batteries for the
loads connected to the IEC connectors indicated in Fig. 2 as
`critical loads’ will be reserved. Take into account that they
are set by default as `critical loads’.
·
The 3 kVA models also have a 16A IEC connector
that enables the connection of a load of the total
power of the device.
5.2.2.2. Connection of loads in 4 to 10 kVA 10 kVA.
·
As the device has Class I protection against electric
shock, it is essential to install a protective earth
conductor (connect earth ( )). Connect this conductor
before supplying voltage to the input terminals.
· Connect the loads to output terminals U (L) and N,
respecting the order of the phase and the neutral
indicated on the labelling of the device and in this manual
(see Fig. 2). Where there are discrepancies between the
labelling and the instructions in this manual, labelling shall
always prevail.
· Together with the device, a PDU with several 10 and 16A
IEC output connectors with their respective circuit breaker
is supplied.
When the utility of the PDU is required to power the loads,
it will be necessary to connect its input cables to the output
of the UPS, respecting the following assignment:
Black or brown cable to phase U (L).
Red or blue cable to neutral (N).
Green-yellow cable to earth terminal ( ).
· With regard to the protection that must be placed at the
output of the UPS when the PDU is not used, we recommend
distributing the output power over at least four lines. Each of
them will have a circuit breaker with a value of one quarter
of the rated power. This type of output power distribution
will allow that in the event of a fault in any of the machines
connected to the equipment, which provokes a short circuit,
does not affect more than the line that is broken.
The remaining connected loads will have continuity
assured due to the tripping of the protection, only in the
line affected by the short circuit.
5.2.3. Connection to external batteries (backup extension).
·
Failure to comply with the instructions in this
section and Safety Instructions EK266*08 car-
ries a high risk of electric shock and even death.
· SLC TWIN RT2 devices from 0.7 to 3 kVA incorporate the
batteries in the same box as the device, except for B0, B1
and higher power models.
· The battery protection of the device and of any accumulator
module is always by means of internal fuses that are not
accessible to the user.
·
IMPORTANT FOR SAFETY: If batteries are installed
independently, the accumulator group must be fitted
with a bipolar circuit breaker or disconnect fuse of the size
indicated in Tab. 2.
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
19
Model
Rated voltage of batteries
Minimum values, fast type fuses
DC voltage (V) Current (A)
SLC-700-TWIN RT2
20
SLC-1000-TWIN RT2 (12 V x 3) = 36 V
32
SLC-1500-TWIN RT2
125
SLC-2000-TWIN RT2 (12 V x 4) = 48 V
50
SLC-3000-TWIN RT2 (12 V x 6) = 72 V
SLC-4000-TWIN RT2
20
SLC-5000-TWIN RT2
32
SLC-6000-TWIN RT2 (12 V x 16) = 192V
400
SLC-8000-TWIN RT2
40
SLC-10000-TWIN RT2
50
Tab. 2. Protection features between device and battery module.
·
Before starting the connection process between
battery module or modules and device, check that
the device and loads are `Off’.
Also, when the batteries are installed by the user
independently, the protection fuse or isolator must be
deactivated.
· Connection of the battery module to the device is made by
means of a cable featuring polarised connectors at both
ends, which is supplied with the first one. Two connectors
are available for this purpose on the device and battery
module.
Similarly, the battery modules feature two connectors that
allow the linking of modules in parallel.
·
Each battery module is independent for each device.
Two devices must not be connected to the
same battery module.
Likewise, in parallel systems (4 to 10 kVA models), with
each device connected to its battery module or modules,
they should be considered as single devices that are
independent of each other.
· Fig. 13 shows the connection of a 10 kVA device in a
rack arrangement with two battery modules. For a larger
number, proceed in a manner similar to those shown in the
illustration.
5.2.4. Connection of the input earth terminal ( ) and the earth connection terminal ( ) .
·
As the device has Class I protection against electric
shock, it is essential to install a protective earth
conductor (connect earth ( )). Connect this conductor
before supplying voltage to the input terminals.
Not applicable in models up to 3kVA, because the earth con-
nection is done through the AC power cord and regarding
the battery modules is done through the mesh available in
the cable bundle of them, being compulsory to fix the con-
nectors of both ends to the connectors fitted in the battery
case, by means of the supplied screws and duly tightened.
· Make sure that all of the loads connected to the UPS are only
connected to its earth connection terminal ( ). Failure to
limit the earthing of the load or loads and battery module or
modules to this single point will create earth return loops
that will degrade the quality of the power supplied.
· All terminals identified as an earth connection ( ) are
connected to each other, to the earth terminal ( ) and to
the device’s earth.
5.2.5. Terminals for EPO (emergency power off).
· The UPSs have two terminals for the installation of an external emergency
power off (EPO) output button.
· The device is dispatched from the factory with its EPO circuit set to closed
(NC) by default. In other words, the UPS will cut the output power supply,
emergency power off, when the circuit is opened: Either by removing the female
connector from the socket where it is inserted. This connector has a cable
connected as a jumper that closes the circuit (see Fig. 14-A). Or by pressing
the button external to the device belonging to the user installed between the
terminals of the connector (see Fig. 14-B). The connection on the button must
be in the normally closed contact (NC), so it will open the circuit when
activated. The reverse functionality can be selected through the
communications software and control panel. Except for specific cases, we
advise against this type of connection in view of the purpose of the EPO
button, since it will not act upon an emergency request if either of the two
cables that run from the button to the UPS is accidentally cut. By contrast,
this anomaly would immediately be detected in a closed EPO circuit, with the
inconvenience of an unexpected cut in the powering of the loads, but a
guarantee of effective emergency functionality.
· To recover the normal operating state of the UPS, it is necessary to insert
the connector with the jumper in its receptacle or deactivate the EPO button.
The device will be operational.
Fig. 13. Connection to battery modules.
A
B
Fig. 14. Connector for external EPO.
20
SALICRU
5.2.6. Terminals for digital input and output to relay. Only in models with
power ratings > 3 kVA.
· The device has a four-terminal connector for a digital input and output to
relay (see Fig. 15). `Start/Stop’ digital input. With the device running,
apply a sequential voltage of between 5 and 12 V DC to reverse its state. The
static bypass function of the UPS is enabled by default. In this condition,
when the inverter shuts down, the output terminals will supply voltage through
the internal static bypass. Disable the bypass function through the control
panel if the output supply needs to be cut when giving the shut down command.
Error or fault dry contact. Any error or fault, such as those described in
Tab.13, will modify the state of the normally open (NO) 24V DC 1A contact.
(PAY ATTENTION to the voltage and current applied).
Digital input + Digital input
Output to relay, error or fault
Fig. 15. Digital input/output to relay connector.
5.2.7. Manual bypass auxiliary contact terminals. Only in models with power ratings > 3 kVA.
· The SLC TWIN has a signal block through which it is
possible to activate the shut down command for the UPS’s
inverter when closing the circuit. This normally open
contact is intended for connection to an external manual
bypass switch or disconnector. (see Fig. 16).
· On the distribution boards with manual bypass that
we supply upon request, there is a two-terminal block
connected in parallel to the normally open auxiliary contact
of the board’s manual bypass switch or disconnector. The
manual bypass auxiliary contacts are of the advanced type
when closing.
· The connection between the auxiliary contact of the board
and the UPS or UPSs is in parallel. This way, any of the
auxiliary contacts that close the circuit will activate the
shut down command of the inverter, transferring the
powering of the loads to the internal static bypass, unless
this is disabled through the control panel, in which it will
cut the powering of the loads.
·
In parallel systems, the distribution board’s manual
bypass switch or disconnector will have an auxiliary
contact block for each device. Under no circumstances
should the different contacts be joined together as this
would connect the different earths of the control of each
UPS.
·
In the event of acquiring a manual bypass board
through another conduit, check that it has this
auxiliary contact and connect it to the terminal block of the
UPS or each device in parallel systems. The type of auxiliary
contact has to necessarily be advanced when closing.
·
It is ESSENTIAL, as a safety measure for the
assembly, including the loads, to connect the UPS’s auxiliary bypass contact to the block of the same functionality on the manual bypass board. This will prevent any incorrect action on the manual bypass disconnector when the UPS is running from causing total or partial failure of the system. This is also applicable for systems in parallel.
Fig. 16. Terminal block for connection to the inverter shutdown auxiliary contact of the manual bypass board.
5.2.8. Connection in parallel, only in models with power ratings > 3 kVA.
5.2.8.1. Introduction in redundancy.
N+X is usually the most reliable power structure. N represents the minimum number of devices that the total load needs; X represents the number of redundant devices, that is, the number of faulty UPSs that the system can simultaneously allow. The higher X is, the greater the reliability of the system. For occasions where reliability is essential, N+X will be the optimum mode. Up to 3 devices can be connected in parallel to configure a shared output or power redundancy.
5.2.8.2. Installation and operation in parallel.
·
The communications line -COM- constitutes a very
low voltage safety circuit. To preserve the quality
must be installed separately from other lines carrying
dangerous voltages (power distribution line).
· Parallel connections and current signal bus.
Use the 15-wire signal cable with mesh and DB15
connectors at the ends to connect a maximum of 3 devices.
Each cable has a male and a female connector at the ends
which must be connected to link two devices. It is essential
to close the communications loop of the parallel bus and
the current signal bus through the cable with connectors
(see Fig. 17).
The length of the cables related to the parallel bus is ap-
prox. 1.5 metres and must not be prolonged under any
circumstances due to the risk of interference and communi-
cation failures that this would entail.
Communication bus.
Current signal bus
Fig. 17. Communication and current signal connections for system in parallel.
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
21
· When installing systems in parallel, it is necessary to provide them with a
board equipped with individual input and output protections, as well as a
manual bypass with mechanical locking, see Fig. 18. This protections board
will enable a single device in the system to be isolated in the event of a
fault and the loads to be powered with the rest during preventive maintenance
or repair. It also allows the removal of a device in parallel and its
replacement or reintegration once repaired without interrupting the powering
of the loads at any time, provided that the power of the operational device
permits it. Upon request, we can supply a manual bypass board for a two-device
system in parallel.
· Follow the connection procedure for the input described in section 5.2.1.
· Follow the connection procedure for the output (loads) described in section
5.2.2.
· Follow the procedure established for the connection of the battery module or
devices with backup extension described in section 5.2.3.
Input Input circuit breaker
UPS No. 1
BYPASS
BATTERY
LINE
FAULT
Manual Bypass
BYPASS
BATTERY
LINE
FAULT
UPS No. 3 Output circuit breaker
To loads
Fig. 18. Parallel installation of two 4 to 10 kVA UPSs with protections panel and manual bypass.
·
In parallel systems, the length and cross section of
the cables that run from the protections board to
each UPS and from the UPSs to the board will be the same
for all of them without exception.
In the worst case, the following deviations must be strictly
observed:
When the distance between the UPSs in parallel and
the circuit breaker board is less than 20 metres, the
difference in length between the input and output
cables of the device must be less than 20%.
When the distance between the UPSs in parallel and
the circuit breaker board is more than 20 metres, the difference in length between the input and output cables of the device must be less than 10%.
5.2.9. Communication port.
5.2.9.1. RS232 and USB port.
·
The communications line -COM- constitutes a very
low voltage safety circuit. To preserve the quality
must be installed separately from other lines carrying
dangerous voltages (power distribution line).
· The RS232 and USB interfaces are useful for the monitoring
software and updating the firmware.
· It is not possible to use both the RS232 and USB ports at
the same time.
· The DB9 connector supplies the RS232 signals and, in
models up to 3 kVA, the normally open (NO) potential-free
contacts using relays.
The maximum voltage and current applicable to these
contacts is 30V DC and 1A.
Also, there is a «Shutdown» input that allows turning off
the inverter, when a voltage between 10 a 12 V is applied
for 1 second at this input.
· The RS232 port consists of the transmission of serial data
in such a way that a large amount of information can be
sent through a communication cable with only 3 wires.
· The USB port is compatible with the USB 1.1 protocol for
communication software.
Pin #
Description
Input / Output
1
UPS fault
Output
2
TXD for RS232
Output
3
RXD for RS232
Input
4
GND for shutdown
Earth
5
GND for RS232
Earth
6
Common relays
–
7
Shutdown order
Input
8
Low battery
Output
9
Mains fault
Output
Tab. 3. Pinout of DB9 connector, RS232.
5
1
2 1
9 6
3 4
Fig. 19. DB9 connectors for RS232 and USB.
5.2.10. Smart slot for the integration of an electronic communication unit.
· Optional electronic communication units include: Interface to relays to terminals, not programmable. SNMP adapter. Modbus RS485 adapter.
22
SALICRU
· The corresponding documentation is supplied with each option. Read it before starting installation.
Installation. · Remove the protective cover from the device’s slot. · Take the
corresponding electronic unit and insert it into the
reserved slot. Make sure that it is properly connected, for which it is
necessary to overcome the resistance caused in the connector located in the
slot. · Make the necessary connections in the terminal block or connectors
available according to each case. · Fit the new protective cover supplied with
the interface to relays card and secure it with the screws from the old cover.
· For more information, contact our T.S.S. or our nearest distributor.
5.2.11. Protection against voltage spikes for the modem / ADSL / fax, etc., line. .
·
The communications line -COM- constitutes a very
low voltage safety circuit. To preserve the quality
must be installed separately from other lines carrying
dangerous voltages (power distribution line).
· Connect the main line for the modem / ADSL / fax, etc., to
the RJ45 connector of the device, identified as `Input’.
· Connect the modem / ADSL / fax, etc., to the RJ45 connector
of the device, identified as `Output’.
5.2.12. Software.
· Download of free ViewPower software. ViewPower is a UPS monitoring software which provides a user-friendly interface for monitoring and control. It features an auto shutdown function for systems consisting of several PCs in case of power failure. The software enables users to monitor and control any UPS in the same LAN through an RS232 or USB communications port, regardless of how far away they are from each other.
5.2.13. Considerations before start-up with connected loads.
·
It is recommended to charge the batteries for at
least 12 hours before using the UPS for the first time.
For this, it will be necessary to supply voltage to the
device and turn the circuit breaker at the back to `On’.
The battery charger will work automatically.
For the battery modules.
For the models with batteries external to the device or
backup extension modules, it will also be necessary to
turn the fuse or circuit breaker of the batteries arranged
between each one to `On’.
· Although the device can operate correctly without charging
the batteries for the specified 12 hours, the risk of a
prolonged power cut during the first hours of operation and
the UPS’s available backup time should be assessed.
· Do not start up the device and loads completely until
indicated in Chapter 6.
When it is done, however, it should be carried out gradually
to avoid possible difficulties, if not at the first start-up.
· If, in addition to the more sensitive loads, it is necessary
to connect high-consumption inductive loads, such as for
laser printers or CRT monitors, the starting up of these
peripherals will need to be taken into account to prevent
the device from crashing.
For this type of load considered NON-PRIORITY, a group
of programmable terminals is available depending on the
model. Depending on the programming of these, the power
supply may or may not be affected in the event of mains
failure.
Fig. 20. View of ViewPower’s main screen.
· Installation procedure: Go to the web page: http://support.salicru.com
Select the required operating system and follow the instructions described on
the web page to download the software.
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
23
6. OPERATION.
6.1. START-UP.
6.1.1. Checks before start-up.
· Make sure that all of the connections have been made correctly and with
sufficient tightening torque, following the instructions on the labelling of
the device and in Chapter 5.
· Check that the UPS and battery module or modules switches are Off’. · Make sure that all loads are
Off’. Shut down the connected loads before
starting the UPS and start the loads, one by one, only
when the UPS is running. Before shutting down the UPS, check that all of the
loads are Off’. · It is very important to proceed in the established order. · For views of the UPS, see Fig. 1 to Fig. 3. · In Fig. 18 , a distribution board with manual bypass is represented conceptually for a parallel system, representative for a single device, with the number of switches adapted. 6.2. UPS START-UP AND SHUTDOWN. 6.2.1. UPS start-up with mains voltage. · Check that the power connection is correct. · Supply voltage to the device (turn the input protection on the distribution board or manual bypass to
On’. If the board has an output
switch, turn it to On’. · Turn the battery switch to
On’ (models B0 and B1).
· In 4 to 10 kVA models, turn the UPS’s input circuit breaker located at the
back of the device to On’. The output terminals will have voltage through the device’s internal static bypass block. The fan or fans, depending on the model, will start to function. Then the main start screen will be displayed after a test of the device. · Press the
ON’ button for more than 2 seconds, the audible alarm will sound
for 1 second and the UPS will start up. · The UPS is set to Normal mode’ after a few seconds. If the mains voltage is incorrect, the UPS will switch to
Battery mode’, without interrupting the power supply at the output terminals.
· Start the load or loads, making sure that the rated power of the device is
not exceeded.
6.2.2. UPS start-up without mains voltage.
· If it has a distribution board, turn the input and output protections to
On’. · Turn the battery switch to
On’ (models B0 and B1). · Turn the device’s
input circuit breaker to On’. · Press the
ON’ button for more than 2
seconds, the
audible alarm will sound for 1 second and the UPS will start up.
The fan or fans, depending on the model, will start to function. Then the main
start screen will be displayed after a test of the device. On the 4 to 10 kVA
models, it is necessary to press the ON’ button for a second time, about 5 to 7 seconds after the first press, for longer than 2 seconds. · The UPS is set to
Battery mode’ after a few seconds. Depending on the level of charge of the
batteries, the residual backup available may be very limited. Consider the
risk involved in operating without mains and discharged batteries. If the
mains voltage returns, the UPS will transfer to Normal mode’ without interrupting the power supply at the output terminals. · Start the load or loads, making sure that the rated power of the device is not exceeded. 6.2.3. UPS shutdown with mains voltage. · Shut down the load or loads. · Press the
OFF’ button for more than 2
seconds to shut
down the inverter. The audible alarm will sound for 1 second. The device will
be set to Bypass mode’. The output terminals will have voltage through the device’s internal static bypass block. · To cut the UPS’s output voltage: Disconnect the input plug of the power socket on models up to 3 kVA and from 4 to 10 kVA and turn the input circuit breaker located at the back of the device to
Off’. Or simply turn the
input and output protections of the UPS’s distribution board on any model to
Off’. A few seconds later, the LCD screen turns off and the entire device will be out of service. 6.2.4. UPS shutdown without mains voltage. · Shut down the load or loads. · Press the
OFF’ button for more than 2
seconds to shut
down the inverter. The audible alarm will sound for 1 second. The device will
leave the output terminals without voltage. A few seconds later, the LCD
screen turns off and the entire device will be out of service. · To leave the
assembly completely isolated, turn the input and output switches of the board
to Off’. 6.3. OPERATING PROCEDURE FOR A PARALLEL SYSTEM (ONLY IN 4 TO 10 KVA MODELS). · In parallel systems, check that the programming of Output 2 is the same on all of them to avoid conflicts. · The operating procedure established here is for devices with a configuration determined by factory default. · Check that the load or loads and/or the output circuit breakers on the distribution board are
Off’.
· Turn “On” the input circuit breakers on the distribution or manual bypass
board and those on each UPS in 4 to 10 kVA.
24
SALICRU
The UPSs supply output voltage from the internal static
bypass of each unit. Observe the LCD screen of the
control panel for any warnings or error information.
Measure the output voltage at the terminals of each UPS
separately to check that the voltage difference between
them is less than 1 V. If the difference is greater than 1
V, check the connection and the associated instructions.
· If everything is correct, proceed. Press the `ON’ button
on all of the UPSs for more than 2 seconds and each
of them will start up. All of the UPSs will transfer to
`Normal mode’.
Measure the output voltage at the terminals of each UPS
separately to check that the voltage difference between
them is less than 0.5 V. If the difference is greater than
1 V, the UPSs will need to be adjusted (contact T.S.S.).
· If everything is correct, proceed. Press the `OFF’ button
for more than 2 seconds on all of the UPSs and each of
them will begin to shut down the device.
Turn the input circuit breakers on the distribution or
manual bypass board to `On’. The output terminals on
the distribution board will be under potential through
the static bypass of the device.
· Press the `ON’ button for more than 0.5 seconds on all
of the UPSs and each one of them will begin to start up
in order to finally leave the system in parallel operation
in `Normal mode’.
· Start the load or loads.
·
Do not leave a floating UPS with respect to the
others. There must always be a connection
between the neutrals, either input or output. Do not
open the input and output circuit breakers of a UPS at
the same time on the distribution board while the UPS
running. Otherwise, a fault in the UPS may occur and the
connected loads may shut down
6.4. HOW TO ADD A UPS TO A SYSTEM IN PARALLEL OPERATION OR TO A FUNCTIONING SINGLE UPS (ONLY IN 4 TO 10 KVA MODELS).
· To operate the parallel system, it is necessary to have a manual bypass
board for the parallel system. In the event of not having one, the shutdown of
the entire system and the loads powered by it must be anticipated.
· The steps to follow are for the addition of a device to a system with two
units. To incorporate a device into a system with only one UPS, proceed in the
same way.
· The distribution board must have input and output switches for each UPS, in
addition to the one for the manual bypass. Otherwise, it will be necessary to
adapt the board or acquire a new one if it has not been previously
anticipated.
· Since it is necessary to change the parallel bus connection to incorporate
the new device into the system (cable with DB15 connectors), it will be
necessary to switch the powering of the loads to the manual bypass. Proceed as
follows: Press the OFF’ button on all of the UPSs for more than 2 seconds to shut down the inverter in all of them. The audible alarm will sound for 1 second. The devices that make up the current parallel system will switch to
Bypass mode’.
Switch the devices to manual bypass.
1. Remove the mechanical lock on the distribution
board’s manual bypass switch or disconnector
and turn it to `On’.
Take into consideration that in `Bypass mode’
(with the switch turned to `BYPASS’), the
loads will be exposed to voltage and frequency
variations and cuts or micro-cuts in mains power, so,
if possible, it is recommended to choose a day with
lower probability of failure (days without
fluctuations, days without storms, etc.) and a certain
speed in the process.
Turn the input circuit breakers of each device to `Off’.
Turn the input and output circuit breakers of the
board to `Off’.
· Before incorporating the new TWIN RT2 into the system,
carry out the appropriate steps to leave it in the same
condition as the others (input switch turned to `Off’).
· Incorporate the new UPS to the system following the
procedure established in section 5.2.8.2 for connection
in parallel.
· Disconnect the communication bus between the first
and last device, and reconnect it including the new UPS.
The bus must be closed for proper operation.
· Turn the input circuit breakers of each UPS on the
distribution board to `On’.
· Turn the input circuit breakers of each UPS to `On’.
The output switches of each UPS on the distribution
board must be open.
The UPSs supply output voltage from the internal static
bypass of each unit. Observe the LCD screen of the
control panel for any warnings or error information.
Measure the output voltage at the terminals of each UPS
separately to check that the voltage difference between
them is less than 1 V. If the difference is greater than 1 V,
check the connection and the associated instructions.
· If everything is correct, proceed. Press the `ON’ button
on all of the UPSs for more than 2 seconds and each
of them will start up. All of the UPSs will transfer to
`Normal mode’.
Measure the output voltage at the terminals of each UPS
separately to check that the voltage difference between
them is less than 0.5 V. If the difference is greater than
1 V, the UPSs will need to be adjusted (contact T.S.S.).
· If everything is correct, proceed. Press the `OFF’ button
on all of the UPSs for more than 2 seconds and each of
them will begin to shut down the device.
Turn the output circuit breakers on the distribution board
to `On’. The output terminals on the board will be under
potential through the static bypass of the devices, the
same potential as the manual bypass line.
· Turn the manual bypass switch or disconnector on the
distribution board to `Off’ and reposition the mechanical
lock to prevent possible accidents
·
To prevent incorrect operations, it is necessary to
fit the mechanical lock of the manual bypass and
their fixing screws.
· Press the `ON’ button on all of the UPSs for more than 2
seconds and each of them will start up, in order to finally
leave the system in parallel operation in `Normal mode’.
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
25
· The load or loads are again protected by the parallel system.
6.5. HOW TO REPLACE A FAULTY UPS IN AN OPERATIONAL PARALLEL SYSTEM.
· The steps to follow to replace a UPS in a system consisting of two or three
units are the same as those for incorporating a device, except for the
difference in the type of action to be carried out. Proceed therefore as
described in section 6.4.
26
SALICRU
7. CONTROL PANEL WITH LCD DISPLAY.
7.1. GENERAL INFORMATION FOR THE SERIES. 7.1.1. Information represented by the
display.
Fault information
Discharge time information
Audible alarm disabled
Information about battery charge level
Input voltage and battery information
Information about the charge level connected to the output
Output voltage information
Information about the operating mode of the device Fig. 21. Graphic and textual information shown on the display.
7.1.2. Common messages shown on the LCD display.
Display Backup time information.
Meaning
Indicates the backup time in analogue clock mode.
Indicates the backup time in digital clock mode. H – Hours, M – Minutes, S –
Seconds.
Fault information.
Indicates as a warning that a fault has occurred.
Indicates a numerical code from the settings menu shown in Table 9 of Section
7.5.
Audible alarm information.
Indicates that the audible alarm is disabled.
Output voltage information. Indicates the output voltage or frequency. V AC – Output voltage, Hz – Output frequency.
Information about the charge level connected to the output.
Indicates the charge level connected to the output as a %,
by displaying four equivalent segments respectively in the
following proportion: 0-25 %, 26-50 %, 51-75 % and 76-100
%.
Information about programmable outputs
P1
Indicates that the programmable outputs are activated.
Information about the operating mode of the device.
BATTERY
Indicates that the device is supplying output voltage from the battery (battery mode).
BYPASS Indicates that the device is activated in BYPASS mode.
ECO
Indicates that the device is supplying output voltage from the bypass (ECO mode).
CHARGING Indicates that the device is in charging mode.
CF/CVCF Indicates that the device is in converter mode.
ONLINE Indicates that the inverter is working.
P1
Indicates that the output is activated.
Information about battery charge level.
Indicates the battery charge level as a %, by displaying four equivalent segments respectively in the following proportion: 0-25 %, 26-50 %, 51-75 % and 76-100 %.
BATT FAULT
Indicates that the battery is not connected. Indicates low battery voltage level.
Information about input and battery voltage. Indicates the input voltage, frequency or battery voltage. V AC – Input voltage, V DC – Battery voltage, Hz – Input frequency.
Tab. 4. Information shown on the LCD panel of the control panel and its meaning.
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
27
7.1.3. Common abbreviations shown on the display.
Code
UOn display
ENA
E A Enabled.
Meaning
DIS
d1S Disabled.
ATO
AtO Automatic.
BAT
UbAt Battery.
NCF
CF Normal mode, working mode as UPS.
CF
CF
Working mode as frequency converter.
SUB
SUb Subtract.
Add ADD
Add.
ON
ON Start-up.
OFF
OFF Shutdown.
FBD
FbUd Not permitted.
OP OPN
Permitted.
RES
RUES Reserved.
N.L
.L Neutral lost.
CHE CHE
Check.
OP.U OP.V
Output voltage
PAR
PAR Parallel, 001 refers to the first.
EPO
EP
Emergency power off.
FR
FR Frequency.
OPL
OPL Load percentage.
ESC ESC
Escape.
HLS
HLS Upper voltage limit for transfer to battery mode.
LLS
LLS Lower voltage limit for transfer to battery mode.
AO
AO
EPO normally open.
AC
AC
EPO normally closed.
EAT
EAt Estimated backup time.
Code
On display
Meaning
RAT
tAt Current time in backup mode.
Ok
OK Ok.
SD
Sd Shutdown.
BL
bL
Low battery.
OL
OL Overload.
OI
OI
Input overcurrent
NC
NC
Battery not connected
OC
OC
Battery overcharge
SF
SF
Connection error. Rotate the connection of the input, phase and neutral cables.
TP
TP
Overtemperature.
CH
CH Charger
BF
bF
Battery failure, low voltage.
BV
bV
Bypass voltage out of range.
FU
FU
Bypass frequency out of range.
BR
bR
Replace batteries.
EE
EE
Internal EEPROM error.
Tab. 5. Abbreviations shown on the LCD display.
28
SALICRU
7.2. CONTROL PANEL FOR MODELS UP TO 3 KVA.
7.2.1. Composition of the control panel with LCD display.
· The control panel consists of: Three buttons with the functions described in
Tab. 6. An LCD display with backlighting.
ON/MUTE
SELECT
OFF/ENTER
7.2.2. Audible alarms.
Description
State of the UPS Bypass mode Battery mode Fault Warning Overload
End of autonomy Faults All
Alarm modulation or tone
Possibility of muting
Beep every 10 seconds. Yes
Beep every 5 seconds.
Continuous.
No
Beep every second.
Yes
Beep every 1 seconds.
No
Continuous.
No
Tab. 7. Audible alarms. 7.2.3. Location of the adjustment parameters on the display.
Parameter 1
Fig. 22. View of the control panel.
Button ON/MUTE
SELECT OFF/ENTER
Description
– Starting up the UPS. Press the button for at least 2 seconds. – Muting the
alarm. Press the button for at least 3 seconds to mute or unmute the audible
alarm. – Button to navigate upwards. When this button is pressed in UPS
settings mode, it will move upwards through the menu structure in relation to
the point where it is located, accessing the previous variable with each
press. – Activating the battery test. Press this button for 3 seconds while in
normal or frequency converter (CF) mode. At the end of the test, it returns to
the respective mode.
– Settings or configuration mode. Press this button for at least 3 seconds to
access this mode when the inverter of the UPS is shut down (bypass mode). –
Button to navigate downwards. When this button is pressed in UPS settings
mode, it will move downwards through the menu structure in relation to the
point where it is located, accessing the following variable with each press.
– UPS shutdown. Press this button for at least 2 seconds. – Confirmation of
selection. Press this button to confirm selection in the device’s settings
mode.
Tab. 6. Functionality of the control panel buttons.
Parameter 2
Parameter 3
Fig. 23. Arrangement of the parameters on the LCD display.
· Parameter 1: Code of the settings menu. For more information consult Tab. 8.
· Parameters 2 and 3 are the configuration or value options for each settings
menu. Select with buttons ‘ or
‘ to modify the menus or parameters. All of
the parameter settings are saved when the UPS is completely shut down and
provided that it has connected batteries, whether internal or external. If a
complete shutdown is not carried out, the setting will not be saved to the
memory.
7.2.4. Settings.
Tab. 8 shows a summary of parameter 1’s adjustable codes for each operating
mode and Fig. 24 shows the structure of the menu tree with the operating mode
for the settings.
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
29
Code
01 02 03 04 06 09 10 11 12 15 17
Description
Output voltage. Frequency converter state.
Output frequency. ECO enable/disable mode. Bypass state (UPS `Off’).
Programmable output state. Programmable output configuration. Backup
limitation configuration. Total battery pack Ah configuration. EPO logical
configuration. Viewable backup time configuration.
Bypass mode/ No output mode
AC mode
YES
–
YES
–
YES
–
YES
–
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
ECO mode
YES YES YES YES –
CF mode
YES YES YES YES YES
Tab. 8. Parameter 1 codes list. Description and settings
Battery mode
YES YES YES YES YES
Battery test
YES YES YES YES –
7.2.4.1. Ah configuration of parameter `12′.
· Standard models are configured with factory default settings, so it is not
necessary to perform any actions to adjust this parameter. For extended backup
and B1 models, however, it is necessary to adjust the value to the total
capacity of the battery pack. Any alteration of the battery pack will entail a
readjustment, so it will be necessary to adapt the value in the event of
future expansions.
· There are basically two reasons to perform the adjustment without it
affecting the correct functioning of the device if it is not done, although it
is more than recommended: a. The charging current of the batteries is directly
related to the capacity of the battery pack. The charger will adapt the
charging factor automatically according to the value of the total capacity
entered, up to the maximum of the current that is possible. This results in
faster charging and therefore greater availability and more immediate backup
in the event of frequent mains failures. b. Entering the value in Ah is vital
for the control to be able to calculate and show the backup available on the
LCD display, without further alterations.
The settings values are determined as follows: 1. Devices with backup
extension.
They are configured by a standard model plus the battery module or modules.
The capacity of the batteries of both are indicated in the following Tab. 9
and Tab. 10. Example for an SLC 1500 TWIN RT2 and backup extension module
698BU000003:
9 Ah + 18 Ah = 27 Ah (value for parameter 12).
UPS model
SLC 700 TWIN RT2 SLC 1000 TWIN RT2 SLC 1500 TWIN RT2 SLC 2000 TWIN RT2 SLC
3000 TWIN RT2
Internal batteries
Voltage (V)
Capacity (Ah)
36
7
48 9
72
Tab. 9. Characteristics of batteries in standard devices.
Code 698BU000001 698BU000002 698BU000003 698BU000004
Battery module Voltage (V) 36 36 48 72
Capacity (Ah) 14 (2 x 7)
18 (2 x 9)
Tab. 10.Characteristics of batteries in modules.
2. Device B1. B1 models do not have batteries in the same box, so a battery module will always be necessary or the user will have them. Example for an SLC 1500 TWIN RT2 B1 and three backup extension modules 698BU000003: (3 x 18 Ah) = 54 Ah (value for parameter 12).
30
SALICRU
3 sec.
O1 Output voltage selection
O2 Selection of device as UPS or CF
O3 Selection of device as CF
ECO mode selection
O4
Static bypass selection
O6
O9 Non-critical load
output sockets Backup time for
1O non-critical load
output sockets
11 Backup time for all output sockets
12 Battery pack Ah capacity
EPO contact configuration
15
Time shown configuration
17
OO
Fig. 24. Settings menu.
USER MANUAL
· The values indicated with(*) are factory default settings. · The settings
can only be carried in ‘byPA’ or ‘STby’ mode. · To carry out any modification
of the configuration, follow the indicated
sequence with the inverter necessarily Off. · To exit the main menu from any
position, press buttons + together.
230 () 240 208 200 220
DIS () ENA
BAT50 () BAT60
DIS () ENA
DIS Frequency converter disabled. Device functions as a UPS. ENA Frequency
converter enabled. In this operating mode, the
static bypass is disabled by default.
BAT 50 UPS with output frequency of 50 Hz. BAT 60 UPS with output frequency of
60 Hz. CF 50 (1) CF with output frequency of 50 Hz. CF 60 (1) CF with output
frequency of 60 Hz.
(1) With parameter 02′ =
ENA’, the CF 50′ or
CF 60′ variables are
displayed instead of BAT 50′ or
BAT 60′.
DIS ECO mode disabled. ENA ECO mode enabled.
ENA (*) DIS
ENA Bypass enabled, with the inverter of the UPS Off’. DIS Bypass disabled, with the inverter of the UPS
Off’.
DIS () ENA
0.. 999
DIS () 0.. 999
7.. 999
AO () AC
EAT () RAT
DIS Programming of output sockets for non-critical loads disabled. ENA
Programming of output sockets for non-critical loads enabled.
Backup time setting for non-critical load output sockets when operating in
Battery mode. Default setting is 999.
Backup time setting for all output sockets when operating in Battery mode.
Default setting is DIS’, deactivated. Take into consideration that the available backup will depend on battery charge level Note: When it is at
0′,
the backup time will be 10 seconds. Battery pack Ah. Do not change for
standard models and adjust in B1 or extended backup models (see section
7.2.4.1). Although the device will still work without adjusting this value on
the display, the time shown in minutes will be incorrect and the battery
charging current will not automatically adjust to them.
EPO button contact type setting. AO EPO activated when circuit opened. AC EPO
activated when circuit closed.
EAT Shows available backup time. RAT Shows elapsed backup time.
ESC
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
31
7.2.4.2. Operating mode / Description of state.
Operating mode / state Description. When the UPS is started, the display
screen of this mode is displayed for a few seconds to initialise the CPU and
system.
UPS start-up LCD display.
Description. The UPS is off and no output voltage is available, but it is
charging the batteries. No output mode
LCD display.
Description.
If the input voltage is within the range of the device, the UPS will supply stable AC sine-wave voltage to the load or loads, and charge the batteries.
AC mode LCD display.
Description.
If the input voltage is within the regulation ranges and ECO mode is activated, the UPS supplies the output voltage from the bypass in ECO mode (energy saving).
ECO mode LCD display.
Description.
When the input frequency is between 46 and 64 Hz, the UPS can be set to a constant output frequency of 50 or 60 Hz. The device will still charge the batteries in this mode.
CF mode
LCD display.
Description.
Description: When the input / frequency voltage is not within the predefined range of the device or there is an AC mains failure, the UPS powers the loads from the batteries for a limited time due to their own capacity and activates the audible alarm modulated every 5 seconds.
Battery mode LCD display.
Description.
When the input voltage is within the range but the UPS is overloaded, the system will automatically transfer to bypass mode or the transfer to this mode can be forced through the front panel. The audible alarm beeps every 10 seconds.
Bypass mode LCD display.
32
SALICRU
Operating mode / state Description. When an error occurs, the ERROR icon and the fault code are displayed.
Error or fault
state
LCD display.
Tab. 11.Operating modes.
7.2.4.3. Warning or alert codes.
Code
Warning or alert description
bl
Low battery
Ol
Overload
OI
Input overcurrent
NC
Battery not connected
OC
Battery overcharge
SF
Input socket connection fault
EP
EPO enabled
TP
Overtemperature
CH
Charger fault
bF
Battery fault
bV
Static bypass voltage out of range
FU
Unstable static bypass frequency
bR
Replace batteries
EE
EEPROM error
Tab. 12.Warning or alert code.
7.2.4.4. Error or fault codes.
Code 01 02 03 11 12 13 14 27 28 2A 41 43 45 49
Error or fault description DC bus start-up fault. DC bus overvoltage. DC bus
undervoltage. Inverter soft start fault
High voltage in the inverter Low voltage in the inverter Inverter output
short-circuited Battery voltage too high
Battery voltage too low Battery charger short-circuited at its output
Overtemperature Output overload
Charger fault Input overcurrent
Tab. 13.Error or fault code.
7.2.4.5. Warning or alert indicators.
Code
Icon (flashing)
Battery voltage low.
Audible alarm Modulated every 2 seconds
Overload. Input overcurrent Disconnected battery
Modulated every 1 seconds
Modulated twice every 10 seconds
Modulated every 2 seconds
Battery overcharge
Input socket connection fault
EPO enabled
Modulated every 2 seconds Modulated every 2 seconds Modulated every 2 seconds
Overtemperature
Modulated every 2 seconds
Charger fault
Battery fault
Static bypass voltage out of range
Unstable static bypass frequency
Replace batteries
Modulated every 2 seconds
BATT FAULT
Modulated every 2 seconds (The UPS disconnects to warn the user that the batteries are incorrect).
BYPASS Modulated every 2 seconds
BYPASS Modulated every 2 seconds
Modulated every 2 seconds
EEPROM error
Modulated every 2 seconds
Tab. 14.Warning or alert indicators.
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
33
7.3. CONTROL PANEL FOR 4 KVA TO 10 KVA MODELS.
· The control panel consists of: Four buttons with the functions described in
Tab. 15. A backlit LCD display. Four optical LEDS (see Tab. 17).
BYPASS LINE BATTERY FAULT
OFF/ESC TEST/ MUTE/
ON/
Fig. 25. View of the control panel.
Button OFF/ESC
TEST/
MUTE/
ON/ TEST/ + MUTE/
Description
– UPS shutdown. Press this button for at least 2 seconds. – ESC functionality.
Press this button to return to the last parameter of the settings or
configuration menu.
– Activating the battery test. Press this button for 3 seconds while in normal
or frequency converter (CF) mode. At the end of the test, it returns to the
respective mode. – Button to navigate upwards. When this button is pressed in
UPS settings mode, it will move through the menu structure to the following
variable in relation to the point where it is located.
– Muting the alarm. Press the button for at least 3 seconds to mute or unmute
the audible alarm. – Button to navigate downwards. When this button is pressed
in UPS settings mode, it will move through the menu structure to the previous
variable in relation to the point where it is located.
– Starting up the UPS. Press the button for at least 2 seconds. – Confirmation
of selection. Press this button to confirm selection in the device’s settings
mode.
Press and hold the two buttons simultaneously for more than 1 second to enter
/ exit the settings or configuration menu.
(CF) Working mode of the UPS as a frequency converter, in the static bypass it is disabled.
Tab. 15.Functionality of the control panel buttons.
7.3.1. Audible alarms.
Description
State of the UPS Bypass mode Battery mode Fault Warning Overload
End of autonomy Faults All
Alarm modulation or tone
Possibility of muting
Beep every 2 minutes. Yes
Beep every 4 seconds.
Continuous.
No
2 beeps every second.
Yes
Beep every 1 seconds.
No
Continuous.
No
Tab. 16.Audible alarms. 7.3.2. Optical indications.
State of the UPS
UPS start-up No output mode Bypass mode
AC mode Battery mode
CF mode ECO mode Battery test
Fault
LEDs
Bypass Line Battery Fault (yellow) (green) (yellow) (red)
: LED illuminated permanently. : LED off.
Tab. 17.Interaction between optical LEDs for the different modes or states of
the UPS.
7.3.3. Location of the adjustment parameters on the display.
Parameter 1
Parameter 2
Parameter 3
Fig. 26. Arrangement of the parameters on the LCD display.
34
SALICRU
· Parameter 1: Code of the settings menu. For more information consult Tab.
18.
· Parameters 2 and 3 are the configuration or value options for each settings
menu. Select with buttons ‘ or
‘ to modify the menus or parameters. All of
the parameter settings are saved when the UPS is completely shut down and
provided that it has connected batteries, whether internal or external. If a
complete shutdown is not carried out, the setting will not be saved to the
memory.
7.3.4. Settings.
Tab. 18 shows a summary of parameter 1’s adjustable codes for each operating
mode.
DEPENDING ON THE DEVICE’S FIRMWARE VERSION, IT IS POSSIBLE TO SHOW SOME
SCREENS IN ADDITION TO THOSE INDICATED IN THIS SECTION. DO NOT CHANGE THE
ORIGINAL FACTORY SETTINGS OF THESE, AS THIS COULD CAUSE FAULTS IN THE UPS,
LOADS OR BOTH DEPENDING ON EACH SETTING.
· Code 02 – Output frequency.
Fig. 28. Parameter 2 setting: Output frequency.
It is possible to choose one of the following values: 50 Hz, 60 Hz or ATO.
With ATO selected, the output frequency is autodetected according to the
normal input at the time of connection of the device to the mains. If it is
between 46 and 54 Hz, it will be set at 50 Hz, and, if it is between 56 and 64
Hz, at 60 Hz. The factory default setting is ATO. Parameter 3 setting:
Frequency mode. Output frequency in CF mode or not CF mode setting. It is
possible to choose between two options:
Code
01 02 05 08 09 10 11 12 17
Description
Output voltage. Output frequency. ECO enable/disable mode. Bypass mode
setting. Maximum battery discharge time setting.
Reserved. Reserved. Hot standby function Reserved.
Bypass mode/ No output mode
YES YES YES YES YES
AC mode
YES YES
YES
YES
Tab. 18.Parameter 1 codes list. Description and settings
ECO mode CF mode Battery mode Battery test
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
YES
YES
YES
YES
Reserved for future options.
Reserved for future options.
YES
YES
YES
YES
Reserved for future options.
· Code 01 – Output voltage.
Fig. 27. Parameter 3 setting: Output voltage.
It is possible to choose one of the following values for the output voltage
between phase and neutral: 208, 220, 230 or 240 V.
CF. Sets the UPS to CF mode. With this option activated, the output
frequency is set to 50 or 60 Hz based on the parameter 2 selection. The input
frequency can be 46 to 64 Hz.
NCF. Sets the UPS to normal mode (not CF mode). With this option activated,
the output frequency is set at 50 or 60 Hz synchronised with the input
frequency based on the parameter 2 selection and its range. If the parameter 2
selection is 50 or 60 Hz, it will be transferred to battery mode (powering
loads) when the frequency is not respectively between 46 and 54 Hz or 56 and
64 Hz.
(*) If ATO is selected in parameter 2, parameter 3 will display the current
frequency.
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
35
· Code 09 – Maximum battery discharge time setting.
Fig. 29. · Code 05 – ECO mode selection.
Fig. 30. Parameter 3 setting: Activates or deactivates the ECO
function. DIS. ECO function disabled. ENA. ECO function enabled. If the
ECO function is disabled, the voltage and frequency range for ECO mode can be
adjusted, but there is no point unless the function itself is enabled. · Code
08 – Bypass mode setting.
Fig. 32. Parameter 3 setting:
000 ~ 999. Sets maximum backup time. The UPS will turn off automatically
once it has elapsed to protect the batteries. The default value is 990 minutes
(16.5 h).
DIS. Disables the battery discharge time protection and the backup time will
depend on the capacity of the batteries.
· Code 10 – Reserved.
Fig. 33. Reserved for future options. · Code 11 – Reserved.
Fig. 31.
Parameter 2 setting. OPN. Bypass permitted. When selecting this option, the
UPS will operate in bypass mode, provided that selection in bypass settings
(parameter 3) has been enabled/disabled. FBD. When selecting this option,
operation in bypass mode is not permitted in any condition.
Parameter 3 setting: ENA. Bypass enabled. When selected, bypass mode is
enabled. DIS. Bypass disabled. If selected, automatic bypass is permitted
but not manual switch to bypass. At this point, manual switch to bypass is
understood as being that which users perform on the UPS. For example, pressing
the OFF button on the front of the device when it is in AC mode transfers the
load to the static bypass.
Fig. 34. Reserved for future options. · Code 12 – Hot standby function.
Fig. 35.
36
SALICRU
Parameter 2 setting. HS.H Enabling or disabling the Hot standby function.
Parameter 3 setting: YES: The Hot standby function is enabled after the
mains are restored even without the batteries being connected to the UPS.
NO: The Hot standby function is disabled. The UPS operates in normal mode. It
will not restart if the batteries are not connected to the UPS.
· Code 17 -Battery module number setting.
7.3.4.1. Operating mode / Description of state.
· In correctly configured parallel UPS systems, the acronym PAR’ will be displayed in the place of the parameter 2 variable and the number corresponding to the device of the system in parallel in parameter 3. The
MASTER’ UPSs will be assigned as 001′ by default and the slaves
002′ and
`003′ respectively. The assigned numbers can be modified dynamically during
operation.
Fig. 36.
In standard devices with internal batteries or B1 devices, it sets the value
to the total number of battery modules including the one belonging to the
standard device, unless it is a B1 which does not have accumulators. Sets
parameter 3 to the number of battery modules. The setting allows values from 0
to 7 and the default setting is 0.
When external batteries are installed independently, equivalence must be found
in order to determine the value to be entered in this variable. Proceed as
follows to define the value: Divide the Ahs of the installed batteries
between 7 Ah for the 4 to 6 kVA models and between 9 Ah for the 8 and 10 kVA
models. If the value obtained is not exact, round down. Example: SLC 5000 TWIN
RT2 device with an external battery pack of 45 Ah belonging to it. 45 Ah / 7
Ah = 6.4 When rounding down, value `6′ must be entered in parameter 3.
· The basic reason for adjusting the setting is as follows, without it
affecting the correct functioning of the device if it is not done, although it
is more than recommended: The charging current of the batteries is directly
related to the capacity of the battery pack. The charger will adapt the
charging factor automatically according to the value of the total capacity
entered, up to the maximum of the current that is possible. This results in
faster charging and therefore greater availability and more immediate backup
in the event of frequent mains failures. Any alteration of the battery pack
will entail a readjustment, so it will be necessary to adapt the value in the
event of future expansions.
USER MANUAL
Fig. 37. Parallel system screen.
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
37
7.3.4.2. Operating mode / Description of state.
Operating mode / state Description. When the UPS is started, the display
screen of this mode is displayed for a few seconds to initialise the CPU and
system.
UPS start-up LCD display.
Description.
If the bypass voltage / frequency is out of range or the bypass is disabled (or prohibited), the UPS will enter no output mode with the inverter running or shut down. The UPS does not supply output voltage. The audible alarm modulated every two minutes is audible.
No output mode LCD display.
Description.
If the input voltage is within the range of the device, the UPS will supply stable AC sine-wave voltage to the load or loads, and charge the batteries.
AC mode LCD display.
Description.
If the input voltage is within the regulation ranges and ECO mode is activated, the UPS supplies the output voltage from the bypass in ECO mode (energy saving).
ECO mode LCD display.
Description.
ECO
When the output frequency is selected as CF in parameter 3 of the settings
menu code 02, the inverter supplies a constant output frequency (50 or 60 Hz).
In this way, the UPS will not supply bypass output voltage, but will charge
the batteries.
CF mode
LCD display.
Description.
When the input / frequency voltage is not within the predefined range of the device or there is an AC mains failure, the UPS powers the loads from the batteries for a limited time due to their own capacity and activates the audible alarm modulated every 4 seconds.
Battery mode LCD display.
Description.
When the input voltage is within the predefined range of the device and the bypass is enabled, when the UPS is switched off, the device enters bypass mode. The audible alarm modulated every two minutes is activated.
Bypass mode LCD display.
38
SALICRU
Operating mode / state Description.
With the UPS in AC mode or CF mode, press the `TEST’ button for more than 0.5 seconds. The audible alarm will beep and the battery test will start. In the electric flow diagram of the display, the line between I / P and the inverter icon flashes for information purposes. This test is useful to check the battery state.
Battery test LCD display.
When an error or fault is detected in the UPS, the inverter will lock. The fault code will be displayed on the screen and the icon will illuminate. Table 13 shows the error or fault codes and the correlation with the description.
Error or fault state
TWIN RT2 4-10kVA
BYPASS
Tab. 19.Operating modes.
7.3.4.3. Warning or alert codes.
Code 01 07 08 09 0A 0B 0D 0E 10 21 22 33 3A 3D 3E 41
42
44
45 46
Warning or alert description Disconnected battery.
Overcharge in the battery. Low battery.
Output overload. Fan fault.
EPO activated. Overtemperature.
Charger fault. L1 input fuse open. Line voltages of UPSs connected in parallel
are different Bypass voltages of UPSs connected in parallel are different UPS
locked in bypass after 3 successive overloads in 30 minutes Maintenance switch
cover open Bypass not available
Start-up fault Bypass no disponible Over temperature in UPS output power
transformer. Applicable to models with transformer with two secondary 110/220
Vac. Loss of redundancy due to shutdown of one of the UPSs belonging to the
parallel N + X system. Loss of redundancy due to overload in parallel N + X
system. Battery test not passed.
Tab. 20.Warning or alert code.
7.3.4.4. Error or fault codes.
Code 01 02 03 04 11 12 13 14 1A 21 24 2A 31 35 36 41 42 43 60 63 6A 6B 6C 6D 6E 77
Error or fault description DC bus start-up fault. DC bus overvoltage. DC bus
undervoltage. DC bus imbalance. Inverter soft start fault
High voltage in the inverter Low voltage in the inverter Inverter output
short-circuited Negative power fault at the output. Battery thyristor short-
circuited. Inverter relay short-circuited. Battery charger short-circuited at
its output CAN communication fault
Parallel cable fault Parallel communication fault
Overtemperature CPU communication fault
Output overload Inverter over current Wrong inverter wave shape Battery start-
up fault PFC current fault in battery mode DC Bus voltage change too fast
Current sensor fault Power supply failure Over temperature in output
transformer
Tab. 21.Error or fault code.
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
39
7.3.4.5. Warning or alert indicators.
Code
Icon (flashing)
Battery voltage low.
Audible alarm Modulated every 1 seconds
Overload.
Modulated twice every 1 seconds
Disconnected battery.
BATT FAULT Modulated every 1 seconds
Battery overcharge
Modulated every 1 seconds
EPO activated.
Modulated every 1 seconds
Fan fault / Overtemperature
Charger fault
TEMP
Modulated every 1 seconds
CHARGING Modulated every 1 seconds BATTERY
Tab. 22.Warning or alert indicators.
40
SALICRU
8. MAINTENANCE, WARRANTY AND SERVICE.
8.1. BATTERY MAINTENANCE.
· Pay attention to all of the safety instructions concerning batteries
indicated in section 1.2.3. of manual EK266*08.
· The service life of the batteries greatly depends on the ambient temperature
and other factors such as the number of charges and discharges, as well as
their depth. The service life is designed to be between 3 and 5 years if the
ambient temperature to which they are exposed is between 10 and 20ºC.
Different types of battery with different service lives are available upon
request.
· SLC TWIN RT2 series UPSs require minimum upkeep. The batteries used in the
standard models are lead acid, sealed, valve regulated and maintenance free.
The only requirement is to charge the batteries regularly to extend their life
expectancy. While the UPS is connected to the mains supply, whether or not it
is running, it will keep the batteries charged and also offer protection from
overcharging and deep discharge.
8.1.1. Notes for the installation and replacement of the battery.
· If it is necessary to replace any connection cables,
original materials can be purchased through our T.S.S. or
authorised distributors. Using inappropriate cables can
lead to overheating in connections, which is a fire hazard.
·
Inside the device, there are permanent dangerous
voltages even without mains supply present through
its connection with the batteries and especially in UPSs
where the electronics and batteries share a box.
It is therefore irrelevant if the input circuit breaker of the
distribution board and/or that of the input of the device in
models with power ratings > 3 kVA is turned to `Off’.
Also take into consideration that the battery circuit is
not isolated from the input voltage, so there is a risk of
discharge with dangerous voltages between the battery
terminals and the earth terminal, which is in turn connected
to earth (any metal part of the device).
· Repair and/or maintenance work must be carried out by our
T.S.S., except for the replacement of batteries, which can
be performed by qualified personnel familiar with them. No
other person should handle them.
Depending on the configuration of the UPS, certain actions
need to be carried out before handling the batteries:
Devices with batteries and electronics sharing the
same box.
Shut down the loads and device completely.
Disconnect the SLC TWIN RT2 from the mains.
Open the device to access the interior.
Remove the fuse or internal battery fuses.
Release the battery holders and replace the
batteries.
Perform the above steps in reverse to return the
device to how it was at the start, including start-up.
UPS with batteries and electronics in separate boxes. Shut down the loads
and device completely. Disconnect the SLC TWIN RT2 from the mains.
Disconnect the battery module from the UPS. Open the battery module to
access the interior. Remove the fuse or internal battery fuses. Release
the battery holders and replace the batteries. Perform the above steps in
reverse to return the device to how it was at the start, including start-up.
8.2. UPS TROUBLESHOOTING GUIDE.
If the UPS does not work properly, check the information shown on the LCD
screen of the control panel and act accordingly depending on the device model.
Using the Tab. 23 and Tab. 24 troubleshooting guides, try to resolve the issue
and, if it persists, consult our Technical Service and Support T.S.S. If it is
necessary to contact our Technical Service and Support T.S.S., provide the
following information: · UPS model and serial number. · Date on which the
issue occurred. · Full description of the issue, including information
provided
by the LCD display or LEDs and state of the alarm. · Power supply conditions,
type of load and level of load
applied to the UPS, ambient temperature, ventilation conditions. · Battery
information (capacity and number of batteries), whether the device is a (B0)
or (B1). · Any other information considered relevant.
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
41
8.2.1. Troubleshooting guide for devices up to 3 kVA.
Symptom
Possible cause
No alarms or indications on the LCD display and mains voltage normal.
The power cable is not connected correctly.
The power cable is connected to an IEC output connector on the UPS.
Solution Check that the power cables are firmly connected to
the mains. Correctly connect the power cable to the respective
IEC connector.
Icon
and warning code flash on the LCD
display and the audible alarm modulated every second
is active.
Icon
and warning code flash on the LCD
display and the audible alarm modulated every two
seconds is active.
The EPO function is activated.
Neutral earth fault detection. Inverted phase and neutral input cables.
Close the EPO signal circuit to deactivate it.
Disconnect the input plug from the AC power socket and invert the connection
of the phase and the supply
neutral (rotate the plug 180º).
Icon
and warning code flash on the LCD
display and the audible alarm modulated every two
The internal or external batteries are badly connected
Check that all batteries are properly connected.
seconds is active.
Fault code 27 and the BATT FAULT message
are shown on the LCD display. The alarm sounds continuously.
The voltage of the batteries is too high or the charger is faulty.
Contact the distributor or seller or, failing that, our T.S.S.
Fault code 28 and the BATT FAULT message are
shown on the LCD display. The audible alarm sounds continuously.
The voltage of the batteries is too low or the charger is faulty.
Contact the distributor or seller or, failing that, our T.S.S.
The UPS is overloaded.
Disconnect the excess loads from the output sockets.
Icon
,
and warning code flash
on the LCD display and the audible alarm modulated
every second is active.
The UPS is overloaded. The connected loads are powered directly from the mains
through the Bypass.
After repeated overloads, the UPS is locked in Bypass mode. The connected
loads are powered directly from the
mains.
Disconnect the excess loads from the output sockets.
Disconnect the excess loads from the output sockets, shut down the device and
restart it.
Fault code 49 is shown on the LCD display. The audible alarm sounds continuously.
UPS input overcurrent.
Disconnect the excess loads from the output sockets.
Fault code 43 is shown on the LCD display. The audible alarm sounds continuously.
The UPS shuts down automatically as a result of an overload in the output of the device.
Disconnect the excess loads from the output sockets and restart it.
Fault code 14 is shown on the LCD display. The
The UPS shuts down automatically as a result of a short Check the output wiring and that the connected loads
audible alarm sounds continuously.
circuit in the output.
are not short-circuited
Fault codes 01, 02, 03, 11, 12, 13 and 41 are shown on the LCD display. The audible alarm sounds continuously.
An internal fault has occurred in the UPS. This is due to one of two
possibilities:
1. The load is still powered, but directly from the mains through the bypass.
2. The load is no longer powered.
Contact the distributor or seller or, failing that, our T.S.S.
Charge the batteries for at least 5 h and then check
The batteries do not charge completely.
their charge state. If the problem persists, contact the
The backup time is shorter than expected.
distributor or seller or, failing that, our T.S.S.
Faulty batteries.
Contact the distributor or seller or, failing that, our T.S.S. for battery replacement.
Fault code 2A is shown on the LCD display. The audible alarm sounds continuously.
Charger short-circuited at its output.
Check whether the connection of the external battery pack connected to the UPS is short-circuited.
Fault code 45 is shown on the LCD display. At the The charger does not provide output and the battery voltage Contact the distributor or seller or, failing that, our
same time, the audible alarm sounds continuously.
is less than 10 V per element.
T.S.S.
Tab. 23.Troubleshooting guide.
42
SALICRU
8.2.2. Troubleshooting guide for 4 kVA to 10kVA devices.
Symptom No alarms or indications on the LCD display and mains
voltage normal.
Possible cause The power cables are not connected correctly.
Solution Check that the power cables are firmly connected to
the mains.
Icon
and warning code flash on the LCD
display and the audible alarm sounds every second.
The EPO function is activated.
Close the EPO signal circuit to deactivate it.
Icon
and the BATT FAULT message flash
on the LCD display and the audible alarm sounds every The internal or external battery is not correctly connected. Check whether all batteries are correctly connected.
second.
The UPS is overloaded.
Disconnect or shut down the excess loads connected to the UPS output.
The UPS is overloaded. The loads connected to the UPS are Disconnect or shut down the excess loads connected
Icon
and warning code flash on the LCD
display and the audible alarm sounds twice a second.
directly powered by the mains through the bypass. After repeated overloads,
the UPS will transfer to bypass mode. The loads connected to the device will
be powered
from the input through the bypass.
to the UPS output.
Disconnect or shut down the excess loads connected to the UPS output, shut
down the device and restart it.
Display of fault code 43. Icon lights up on the LCD display and the audible alarm sounds
The UPS is overloaded for a long time and the device is locked. The UPS shuts down automatically.
continuously.
Display of fault code 14, the audible alarm sounds The UPS shuts down automatically due to a short circuit at
continuously.
the UPS output.
An internal fault has occurred in the UPS. This is due to one One of the
following fault codes, 01, 02, 03, 04, 11, 12,
of two possibilities: 13, 14, 1A, 21, 24, 35, 36, 41, 42 or 43, are displayed
1. The load is still powered, but directly from the mains on the LCD display
and the audible alarm sounds
through the bypass. continuously.
2. The load is no longer powered.
Disconnect or shut down the excess loads connected to the UPS output and
restart it.
Check that the output connection and/or the loads connected to it are not
short-circuited.
Contact the distributor or seller or, failing that, our T.S.S.
The backup time is shorter than expected.
The batteries do not charge completely.
Charge the batteries for at least 7 h and then check their charge state. If
the problem persists, contact the
distributor or seller or, failing that, our T.S.S.
Faulty batteries.
Contact the distributor or seller or, failing that, our T.S.S. for battery replacement.
Icon
and the TEMP message flash on the
LCD display and the audible alarm sounds every
second.
The fan is locked or does not work; or the temperature of Check the fans and contact the distributor or seller or,
the UPS is very high.
failing that, our T.S.S.
Tab. 24.Troubleshooting guide.
8.3. WARRANTY CONDITIONS.
8.3.1. Terms of the warranty.
On our website you will find the warranty conditions for the product you have
purchased where you can also register it. It is recommended to do so as soon
as possible to include it in the database of our Technical Service and Support
(T.S.S.). Among other advantages, it will streamline any regulatory procedures
for the intervention of T.S.S. in the event of a fault.
8.3.2. Exclusions.
Our company will not be bound by the warranty if it notices that the defect in
the product does not exist or was caused by improper use, negligence, improper
installation and/or
verification, attempts at unauthorized repair or modification, or any other
cause beyond the intended use, or by accident, fire, lightning or other
hazards. Nor shall it cover any compensation for damages.
8.4. TECHNICAL SERVICES NETWORK.
Information about our national and international Technical Service and Support
(T.S.S.) centres can be found on our website.
USER MANUAL
SLC TWIN RT2 UNINTERRUPTIBLE POWER SUPPLY SYSTEMS (UPS)
43
9. ANNEXES.
9.1. GENERAL TECHNICAL SPECIFICATIONS.
Models. Available power ratings (kVA / kW). Technology. Rectifier. Input type.
Number of cables. Rated voltage.
Input voltage range.
Frequency. Input frequency range. Total harmonic distortion (THDi), at full
load. Power factor. Inverter. Technology. Waveform. Power factor. Rated
voltage. Output voltage accuracy (battery mode). Total harmonic distortion
(THDv), with linear load.
Frequency.
Frequency synchronous speed. Transfer time, inverter to battery. Performance
at full load, in line mode with battery 100% charged. Performance at full
load, in ECO mode.
Overload in line mode.
Overload in battery mode.
Crest factor. Possibility of parallel connection / No. of devices. Static
Bypass. Type. Rated voltage. Rated frequency. Batteries. Element voltage.
Capacity. Number of batteries in series / group voltage. Blocking voltage for
group end of backup. Internal battery charger. Group fast charge voltage.
Group floating voltage. Maximum charge current. Recharge time. Voltage /
temperature compensation. Optional internal battery charger (B1). Maximum
charge current. Other functions. Cold start. Emergency power off. Frequency
converter.
TWIN RT2
0.7
1
1.5
2
3
4
5
6
8
10
On-line double-conversion, PFC, double DC bus.
Single-phase.
3 cables – Phase R (L) + Neutral (N) and earth.
200 / 208 / 220 / 230 / 240 V AC (1)
208 / 220 / 230 / 240 V AC (2)
176.. 276 V AC with 100 % load.
110.. 300 V AC up to 60 % load.
110.. 300 V AC up to 50 % load.
50 / 60 Hz (auto-detectable)
± 10 Hz (40.. 60 / 50.. 70 Hz)
± 4 Hz (46.. 54 / 56.. 64 Hz)
5 %
4 %
0.99 (at full load).
PWM
Pure sine wave.
1 (3)
200 / 208 / 220 / 230 / 240 V AC (1)
208 / 220 / 230 / 240 V AC (2)
± 1 %
< 2 %
< 1 %
With mains present, synchronised to rated input 47.. 53 Hz. With mains present, synchronised to rated input 56.. 64 Hz.
With mains absent -backup mode- 50 / 60 ±0.1 Hz.
< 1 Hz/sec.
0 ms.
89 %
90 %
91 %
93 %
95 %
96 % 110.. 130 %, 5 min. > 130.. 140 %, 30 sec. > 140.. 150 %, 1.5 sec. > 150 %, 100 ms. 110.. 130 %, 2 min. > 130.. 140 %, 10 sec. > 140.. 150 %, 1.5 sec. > 150 %, 100 ms.
Function not available.
97 % 3:1
99 % 100.. 110 %, 10 min. > 110.. 130 %, 1 min.
130 %, 1 sec. –
100.. 110 %, 30 sec. > 110.. 130 %, 10 sec.
130 %, 1 sec. –
Yes / up to 3 UPSs. (4)
Common line with mains. Mixed (thyristors in antiparallel + relay). That of the mains. That of the mains.
7 Ah 3 / 36 V DC 31.5 V DC
9 Ah 4 / 48 V DC
42 V DC
12 V DC
6 / 72 V DC 63 V DC
7 Ah
9 Ah
16 / 192 V DC
168 V DC
42.5 V DC
56.6 V DC 85 V DC
224 V DC
41.0 V DC
54.7 V DC 81.9 V DC
218.4 V DC
4 A
1 A
< 3 hours to 90%.
5 mV per battery / ºC for temperature > 30 ºC.
20 mV per battery / ºC for temperature > 25 ºC.
12 A
4 A
Yes Yes Yes (5)
Yes (6)
44
SALICRU
Models. Available power ratings (kVA / kW). General. IEC connectors or input terminals. IEC connectors or output terminals. PDU power supply delivered with the device. IEC output connectors on PDU. Communication ports. Potential-free contacts, interface to relays. Digital input and output. ADSL/fax/modem transient protector. Monitoring software. Optional cards (to insert in slot). Noise level at 1 m. Working temperature. Storage temperature. Working altitude. Relative humidity. Protection rating.
Dimensions (mm)
Standard UPS module/B1.
-Depth × Width × Height- Standard battery module.
Optional battery module.
Module height in number of U.
Standard UPS module.
Weight (kg).
B1 UPS module. Battery module.
Optional battery module.
Safety.
Electromagnetic compatibility (EMC).
Operation.
Marking.
Quality system.
0.7
1
1.5
2
TWIN RT2
3
4
5
6
8
10
10 A IEC connector.
16 A IEC connector.
3 (Phase, neutral and earth terminal).
8 x 10A IEC (4 + 4) + 1 x 16A IEC (only in 3 kVA UPS)
3 (Phase, neutral and earth terminal).
–
With 3-wire cable to connect to UPS output terminals.
–
4 x 10A IEC + 2 x 16 A IEC 2 x 10A IEC + 4 x 16 A IEC
2 (RS232 -DB9- and USB, mutually exclusive).
3 relays supplied with the same connector as the RS232.
–
–
1 + 1
Yes (RJ45 connectors)
No
ViewPower (free download).
Interface to relays, SNMP, remote Internet or intranet management.
< 50 dB
< 55 dB
< 58 dB
< 60 dB
0.. +40 ºC
-15.. +50 ºC
2,400 masl (power degradation up to 5,000 m)
0-95 % non-condensing.
IP20
(405 + 35 (7)) x 438 x 88
(490 +35 (7)) x (605 +35 (7)) x
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>