HYTRONIK HCD405D2 DALI-2 HF High-Bay Motion Sensor User Manual

June 4, 2024
HYTRONIK

HYTRONIK HCD405D2 DALI-2 HF High-Bay Motion Sensor

Product Description

HCD405D2 built-in microwave sensor has been certied as DALI-2 input device with daylight sensor instance and HF motion sensor
instance. It is ideal for typical indoor applications such as ofce, classroom, healthcare and other commercial areas.

Features

  • DAL-2 multi-sensor input device
  • Compliant to IEC62386_101, 103, 303, 304
  • Robust HF antenna design against wireless interference
  • 5-Year Warranty

Technical Data

Input Characteristics

Model No. HCD405D2
Input 220-240VAC 50/60Hz
Current Consumption Max. 2mA from DALI Bus
Power Consumption <1W
Output DALI-2 Command
Warming-up 20s

Sensor Data

Model No. HCD405D2
Sensor principle High Frequency (microwave)
Operation frequency 5.8GHz +/- 75MHz
Transmission power <0.5mW

Detection range(Max.)

| Max installation height: 6m

Max detection range:16m (diameter)

Detection angle| 30O   ~ 150O

Safety and EMC

EMC standard (EMC)| EN55015, EN61547,

EN61000-3-2, EN61000-3-3

---|---
Safety standard (LVD)| EN61347-1/-2-11
Radio Equipment (RED)| EN300440, EN301489-1/-3, EN50663
Certifcation| CB, CE , EMC, RED, RCM
Compliance| IEC62386_101, 103, 303, 304

Environment

Operation temperature Ta: -20OC ~ +70OC
Case temperature (Max.) Tc: +75OC
Storage temperature -40°C ~ 70°C
Relative humidity 20 ~ 90%
IP rating IP20
Insulation Class II

HYTRONIK HCD405D2 DALI-2 HF High-Bay Motion Sensor-
fig3

Note: We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false-triggering.

Wire Preparation

To make or release the wire from the terminal, use a screwdriver to push down the button

Wiring Diagram

Note: HCD405D2 has been used as DALI-2 input device to only report DALI instance(light sensor instance and motion sensor instance) to DALI-2 application controller, who is the “main brain” to process the data communication between input devices and the control gear and assign different function.

Detection Pattern

HYTRONIK HCD405D2 DALI-2 HF High-Bay Motion Sensor-
fig6

Sensitivity adjustments:

Factory default is 100% and additional gear range 1-4 value has been predefined in BANK1 offset Ox ll so that DA 2 application controller can find the position to decode it and furtherly adjust sensitivity, the higher the number, the more sensitive it is.
PS: Please check it DAI 2 application controller supplier has right sotware to decode it.

Additional Information / Documents

Regarding precautions tor microwave sensor installation and operation, please kindly reter to www.hytronik.com/download

knowledge ->Microwave Sensors- Precautions tor Product lnstallation and Operation 2. Regarding Hytronik standard guarantee policy, please reter to
www.hytronik.com/download >knowledge ->Hytronik Standard Guarantee Policy

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

HYTRONIK User Manuals

Related Manuals