HYTRONIK HCD405D2 DALI-2 HF High-Bay Motion Sensor User Manual
- June 4, 2024
- HYTRONIK
Table of Contents
HYTRONIK HCD405D2 DALI-2 HF High-Bay Motion Sensor
Product Description
HCD405D2 built-in microwave sensor has been certied as DALI-2 input device
with daylight sensor instance and HF motion sensor
instance. It is ideal for typical indoor applications such as ofce, classroom,
healthcare and other commercial areas.
Features
- DAL-2 multi-sensor input device
- Compliant to IEC62386_101, 103, 303, 304
- Robust HF antenna design against wireless interference
- 5-Year Warranty
Technical Data
Input Characteristics
Model No. | HCD405D2 |
---|---|
Input | 220-240VAC 50/60Hz |
Current Consumption | Max. 2mA from DALI Bus |
Power Consumption | <1W |
Output | DALI-2 Command |
Warming-up | 20s |
Sensor Data
Model No. | HCD405D2 |
---|---|
Sensor principle | High Frequency (microwave) |
Operation frequency | 5.8GHz +/- 75MHz |
Transmission power | <0.5mW |
Detection range(Max.)
| Max installation height: 6m
Max detection range:16m (diameter)
Detection angle| 30O ~ 150O
Safety and EMC
EMC standard (EMC)| EN55015, EN61547,
EN61000-3-2, EN61000-3-3
---|---
Safety standard (LVD)| EN61347-1/-2-11
Radio Equipment (RED)| EN300440, EN301489-1/-3, EN50663
Certifcation| CB, CE , EMC, RED, RCM
Compliance| IEC62386_101, 103, 303, 304
Environment
Operation temperature | Ta: -20OC ~ +70OC |
---|---|
Case temperature (Max.) | Tc: +75OC |
Storage temperature | -40°C ~ 70°C |
Relative humidity | 20 ~ 90% |
IP rating | IP20 |
Insulation | Class II |
Note: We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false-triggering.
Wire Preparation
To make or release the wire from the terminal, use a screwdriver to push down the button
Wiring Diagram
Note: HCD405D2 has been used as DALI-2 input device to only report DALI instance(light sensor instance and motion sensor instance) to DALI-2 application controller, who is the “main brain” to process the data communication between input devices and the control gear and assign different function.
Detection Pattern
Sensitivity adjustments:
Factory default is 100% and additional gear range 1-4 value has been
predefined in BANK1 offset Ox ll so that DA 2 application controller can find
the position to decode it and furtherly adjust sensitivity, the higher the
number, the more sensitive it is.
PS: Please check it DAI 2 application controller supplier has right sotware to
decode it.
Additional Information / Documents
Regarding precautions tor microwave sensor installation and operation, please kindly reter to www.hytronik.com/download
knowledge ->Microwave Sensors- Precautions tor Product lnstallation and Operation 2. Regarding Hytronik standard guarantee policy, please reter to
www.hytronik.com/download >knowledge ->Hytronik Standard Guarantee Policy
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>