POTTER OSYSU-CRH Corrosion Resistant Outside Screw and Yoke Valve Supervisory Switch Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
- POTTER OSYSU-CRH Corrosion Resistant Outside Screw and Yoke Valve
- Features
- Description
- Testing
- Technical Specifications
- Theory of Operation
- Visual Switch Status Indication
- Small Valve Installation – 1/2” Through 2 1/2” Sizes
- Small Valve Installation
- Large Valve Installation – 3” Through 12” Sizes
- Large Valve Installation
- Dimensions
- Breaking Excessive Rod Length
- Switch Terminal Connections Clamping Plate Terminal
- Typical Electrical Connections
- Ordering Information
- Engineering Specifications: OS&Y Valves
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
POTTER OSYSU-CRH Corrosion Resistant Outside Screw and Yoke Valve
Supervisory Switch
Features
- NEMA 4X* (IP 65) and 6P (IP 67)
- Enclosure is 4X. For additional corrosion protection of mounting hardware, use model OSYSU-2 CRH
- -40º to 140º (-40ºC to 60ºC) operating temperature range
- Visual switch indicators
- Two conduit entrances
- Adjustable length trip rod
- Accomodates up to 12AWG wire
- Three position switch detects tampering and valve closure
- Knurled mounting bracket prevents slipping
- Fine adjustment feature for fast, easy installation
- RoHS compliant
- One or two SPDT contact models (-1,-2)
NOTE
Before any work is done on the fire sprinkler or fire alarm system, the
building owner or their authorized representative shall be notified. Before
opening any closed valve, ensure that opening the valve will not cause any
damage from water flow due to open or missing sprinklers, piping, etc.
Important: This document contains important information on the installation and operation of OS&Y valve supervisory switches. Please read all instructions carefully before beginning installation. A copy of this document is required by NFPA 72 to be maintained on site.
Description
The OSYSU is used to monitor the open position of an OS&Y (outside screw and
yoke) type gate valve. This device is available in two models; the OSYSU-1,
containing one set of SPDT (Form C) contacts and the OSYSU-2, containing two
sets of SPDT (Form C) contacts. These switches mount conveniently to most OS&Y
valves ranging in size from 2” to 12” (50mm to 300mm). They will mount on some
valves as small as ½” (12,5mm).
The cover is held in place by two tamper resistant screws that require a
special tool to remove. The tool is furnished with each device.
Testing
The operation of the OSYSU and its associated protective monitoring system shall be inspected, tested, and maintained in accordance with all applicable local and national codes and standards and/or the Authority Having Jurisdiction (manufacturer recommends quarterly or more frequently). A minimum test shall consist of turning the valve wheel towards the closed position. The OSYSU shall operate within the first two revolutions of the wheel. Fully close the valve and ensure that the OSYSU does not restore. Fully open the valve and ensure that the OSYSU restores to normal only when the valve is fully opened.
CAUTION
Close the valve fully to determine that the stem threads do not activate the
switch. The switch being activated by the stem threads could result in a false
valve open indication.
Technical Specifications
Dimensions | See Fig 8 |
---|---|
Weight | 1.6 lbs (0,73 kg) |
enclosure
| Cover: Die Cast Finish: Red powder Coat Base: Die Cast Finish: Black powder Coat
All parts have corrosion resistant finishes
Cover Tamper| Tamper Resistant Screws
Optional Cover Tamper Switch available
Contact Ratings
| OSYSU-1: One Set of SpDT (Form C) OSYSU-2: Two Sets of SpDT (Form C)
10.0 amps at 125/250 VaC
2.0 amps at 30VDC Resistive 10 mamps minimum at 24 VDC
environmental Limitations
| -40º F to 140ºF (-40ºC to 60ºC)
NeMa 4X (Ip 65) and NeMa 6p (Ip 67) enclosure (Use suitably rated conduit and connector)
Indoor or Outdoor Use (See OSYSU-eX Bulletin 5400705 for Hazardous locations)
Conduit entrances| Two Knockouts for 1/2” conduit provided
(See Notice on page 6 and Fig. 9 on page 5)
Service Use| NFpa 13, 13D, 13R, 72
Theory of Operation
The OSYSU is a 3 position switch. The center position is the normal installation position. Normal is when the switch is installed on the OS&Y valve, the valve is fully open and the trip rod of the OSYSU is in the groove of the valve stem. Closing the valve causes the trip rod to ride up out of the groove and activates the switches. Removing the OSYSU from the valve causes the spring to pull the trip rod in the other direction and activates the switches.
Visual Switch Status Indication
There are 3 visual indicators to determine the status of the switches.
Fig 1; the actuator button of the micro switches are on the raised section of
the switch actuator.
Fig 2; the trip rod is perpendicular to the base and lined up with the
alignment mark on the mounting bracket.
Fig 3; the white visual indicator is visible through the window on the back of
the switch actuator.
A final test is to meter the contacts marked COM and N.O. to ensure they are
an open circuit when the valve is open and that they close and have continuity
within 2 revolutions of turning the valve handwheel towards the closed
position and the contacts remain closed as the valve is completely closed and
until the valve is completely opened when the trip rod drops back into the
groove in the valve stem.
Small Valve Installation – 1/2” Through 2 1/2” Sizes
Small Valve Installation
NOTE: If the valve stem is pre-grooved at 1/8” minimum depth; proceed to step 7.
-
Remove and discard “E” ring and roller from the trip rod.
-
With the valve in the FULL OPEN position, locate the OSYSU across the valve yoke as far as possible from the valve gland so that the spring loaded trip rod of the OSYSU is pulled against the non threaded portion of the valve stem. Position the OSYSU with the bracket near the handwheel as shown in Fig. 6 if possible to avoid creating a pinch point between the wheel and the OSYSU.
-
Loosen the locking screw that holds the trip rod in place and adjust the rod length (see Fig. 5). When adjusted properly, the rod should extend past the valve screw, but not so far that it contacts the clamp bar. Tighten the locking screw to 5 in-lbs minimum to hold the trip rod in place and properly seal the enclosure.
NOTE: If trip rod length is excessive, loosen the locking screw and remove the trip rod from the trip lever. Using pliers, break off the one (1) inch long notched section (see Fig. 10). Reinstall trip rod and repeat Step 3 procedure. -
Mount the OSYSU loosely with the carriage bolts and clamp bar supplied. On valves with limited clearance use J-hooks supplied instead of the carriage bolts and clamp bar to mount the OSYSU.
-
Mark the valve stem at the center of the trip rod.
-
Remove the OSYSU. Utilizing a 3/16” or 1/4” diameter straight file, file a 1/8” minimum depth groove centered on the mark on the valve stem. Deburr and smooth the edges of the groove to prevent damage to the valve packing and to allow the trip rod to move easily in and out of the groove as the valve is operated.
NOTE: A groove depth of up to approximately 3/16” can make it easier to install the OSYSU so that it does not restore as it rolls over by the threads of the valve stem. -
Mount the OSYSU on the valve yoke with the spring loaded trip rod of the OSYSU pulled against the valve stem and centered in the groove of the stem. If possible, position the OSYSU with the flat side of the bracket toward the hand wheel, as shown in Fig. 6, to help avoid creating a pinch point between the wheel and OSYSU. When in this preferred mounting position, it is usually best to use the white indicator visible through the window, as illustrated in Fig. 3, to aid in initially locating the OSYSU in the correct position on the yoke. If the unit must be installed inverted with the white indicator no longer easily visible, use the visual indicators of the actuator buttons on the micro-switches, as illustrated in Fig. 1, or the trip rod alignment mark on the bracket, as illustrated in Fig. 2 , to aid in initially locating the OSYSU.
-
Final adjustment can be made by slightly loosening the two screws on the bracket and using the fine adjustment feature (see Fig. 5). The adjustment is correct when the plungers on the switches are depressed by the actuator and there is no continuity between the COM and NO terminals on the switches.
-
Tighten the adjustment screws and all mounting hardware securely (20 in-lbs minimum). Check to insure that the rod moves out of the groove easily and that the switches activate within two turns when the valve is operated from the FULL OPEN towards the CLOSED position.
-
Reinstall the cover and tighten the cover screws to 15 in-lbs minimum to properly seal the enclosure.
CAUTION
Close the valve fully to determine that the stem threads do not activate the switch. The switch being activated by the stem threads could result in a false valve open indication.
Large Valve Installation – 3” Through 12” Sizes
Large Valve Installation
NOTE: If the valve stem is pre-grooved at 1/8” minimum depth; proceed to step 6.
-
With the valve in the FULL OPEN position, locate the OSYSU across the valve yoke as far from the valve gland as possible so that the spring loaded trip rod of the OSYSU is pulled against the non threaded portion of the valve stem. Position the OSYSU with the bracket near the handwheel as shown in Fig. 7 if possible to avoid creating a pinch point between the wheel and the OSYSU.
-
Mount the OSYSU loosely with the carriage bolts and clamp bar supplied.
-
Loosen the locking screw that holds the trip rod in place and adjust the rod length (see Fig. 5). When adjusted properly, the rod should extend past the valve screw, but not so far that it contacts the clamp bar. Tighten the locking screw to 5 in-lbs minimum to hold the trip rod in place and properly seal the enclosure.
NOTE: If trip rod length is excessive, loosen the locking screw and remove the trip rod from the trip lever. Using pliers, break off the one (1) inch long notched section (see Fig. 10). Reinstall trip rod and repeat Step 3 procedure. -
Mark the valve stem at the center of the trip rod.
-
Remove the OSYSU. Utilizing a 3/8” or ½” diameter straight file, file a 1/8” minimum depth groove centered on the mark on the valve stem. Deburr and smooth the edges of the groove to prevent damage to the valve packing and to allow the trip rod to move easily in and out of the groove as the valve is operated.
NOTE: A groove depth of up to approximately 3/16” can make it easier to install the OSYSU so that it does not restore as it rolls over by the threads of the valve stem. -
Mount the OSYSU on the valve yoke with the spring loaded trip rod of the OSYSU pulled against the valve stem and centered in the groove of the stem. If possible, position the OSYSU with the flat side of the bracket toward the hand wheel, as shown in Fig. 7, to help avoid creating a pinch point between the wheel and OSYSU. When in this preferred mounting position, it is usually best to use the white indicator visible through the window, as illustrated in Fig. 3, to aid in initially locating the OSYSU in the correct position on the yoke. If the unit must be installed inverted with the white indicator no longer easily visible, use the visual indicators of the actuator buttons on the micro-switches, as illustrated in Fig. 1, or the trip rod alignment mark on the bracket, as illustrated in Fig. 2 , to aid in initially locating the OSYSU.
-
Final adjustment can be made by slightly loosening the two screws on the bracket and using the fine adjustment feature (see Fig. 5). The adjustment is correct when the plungers on the switches are depressed by the actuator and there is no continuity between the COM and NO terminals on the switches.
-
Tighten the adjustment screws and mounting hardware securely (minimum 20 in-lbs). Check to insure that the rod moves out of the groove easily and that the switches activate within two turns when the valve is operated from the FULL OPEN towards the CLOSED position.
-
Reinstall the cover and tighten the cover screws to 15 in-lbs minimum to properly seal the enclosure.
CAUTION
Close the valve fully to determine that the stem threads do not activate the switch. The switch being activated by the stem threads could result in a false valve open indication.
Dimensions
Breaking Excessive Rod Length
Switch Terminal Connections Clamping Plate Terminal
WARNING
An uninsulated section of a single conductor should not be looped around the
terminal and serve as two separate connections. The wire must be severed,
thereby providing supervision of the connection in the event that the wire
become dislodged from under the terminal. Failure to sever the wire may render
the device inoperable risking severe property damage and loss of life. Do not
strip wire beyond 3/8″ of length or expose an uninsulated conductor beyond the
edge of the terminal block. When using stranded wire, capture all strands
under the clamping plate.
NOTICE
All conduit and connectors selected for the installation of this product shall
be suitable for the environment for which it is to be used and shall be
installed to the manufacturer’s installation instructions. For NEMA 4, 4X, 6,
6P installations, the cover screws are recommended to be tightened to 15 in-
lbs minimum and the trip rod locking screw tightened to 5 in-lbs minimum to
properly seal the enclosure.
Typical Electrical Connections
Ordering Information
Model | Description | Stock No. |
---|---|---|
OSYSU-1 | Outside Screw & Yoke Supervisory Switch (Single switch) | 1010102 |
OSYSU-2 | Outside Screw & Yoke Supervisory Switch (Double switch) | 1010202 |
OSYSU-2 CRH | Outside Screw & Yoke Supervisory Switch (Double Switch). | |
Corrosion resistant hardware of 316 stainless steel | 1010210 | |
Cover Screw | 5490424 | |
Hex Key for Cover Screws and Installation adjustments | 5250062 | |
Optional Cover Tamper Switch Kit | 0090200 |
Engineering Specifications: OS&Y Valves
UL, CUL Listed / FM Approved and CE Marked valve supervisory switches shall be furnished and installed on all OS&Y type valves that can be used to shut off the flow of water to any portion of the fire sprinkler system, where indicated on the drawings and plans and as required by applicable local and national codes and standards. The supervisory switch shall be NEMA 4X and 6P rated and capable of being mounted in any position indoors or out and be completely submerged without allowing water to enter the enclosure.. The enclosure shall be held captive by tamper resistant screws. The device shall contain two ½” conduit entrances and one or two Single Pole Double Throw (SPDT) switches. There shall be a visual indicator to display the status of the switches. To aid in installation, it shall be possible to make fine adjustments to the position of the switch on the valve without loosening the mounting bracket from the valve. The device shall contain an adjustable length trip rod and roller, the trip rod shall be held captive by a set screw accessible upon removal of the cover. The switch contacts shall be rated at 10A, 125/250VAC and 2A, 30VDC. OS&Y Valve supervisory switch shall be model OSYSU-1 for the single switch model and OSYSU-2 for the two switch model manufactured by Potter Electric Signal Company LLC
NOTICE
Supervisory switches have a normal service life of 10-15 years. However, the
service life may be significantly reduced by local environmental conditions.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • www.pottersignal.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>