Function and area of use
In this document we show how to set IP address, Subnet Mask and Gateway for G-Series network adapters GL-9089 and GN-9289.
About this Startup document
This Startup document should not be considered as a complete manual. It is an aid to be able to startup a normal application quickly and easily.
Copyright © Beijer Electronics, 2023
This documentation (below referred to as ‘the material’) is the property of
Beijer Electronics. The holder or user has a nonexclusive right to use the
material.
The holder is not allowed to distribute the material to anyone outside his/her
organization except in cases where the material is part of a system that is
supplied by the holder to his/her customer.
The material may only be used with products or software supplied by Beijer
Electronics.
Beijer Electronics assumes no responsibility for any defects in the material,
or for any consequences that might arise from the use of the material.
It is the responsibility of the holder to ensure that any systems, for
whatever applications, which is based on or includes the material (whether in
its entirety or in parts), meets the expected properties or functional
requirements.
Beijer Electronics has no obligation to supply the holder with updated
versions.
This Start Up document should not be considered as a complete manual. It is an aid to be able to start up a normal application quickly and easily.
Use the following software and drivers in order to obtain a stable application:
In this document we have used following hardware and software
- Modbus TCP/Ethernet IP network adapter light GL-9089
- Modbus TCP/Ethernet IP network adapter GN-9289
- BootpServerVer1000_Beijer Link to BootP
- Windows 10 64 bit
For further information we refer to
For further information refer to
- Manual name/number
- Beijer Electronics knowledge database, HelpOnline
This document and other Startup documents can be obtained from our homepage.
Please use the address
support.europe@beijerelectronics.com
for feedback about our Quick Start documents.
Setup network address in GL-9089 and GN-9289
Setting of the IP address is made through BOOTP.
Default network settings
Default Setting
IP Address| 192.168.1.100
Subnet Mask| 255.255.255.0
Gateway| 0.0.0.0
Use BOOTP server
BOOTP is a standard protocol that can be used to configure the network settings on a GL-9089 and GN-9289.
Sometimes it’s required to disable all other network devices besides the one being used to configure the GL-9089/GN-9289.
In some rare case the firewall needs to be disabled, select “Turn off…” on all networks and push “OK”.
Remember to reactivate the firewall after the IP address setting is done!
There could be security software (like antivirus programs) that might need to be temporarily disabled.
In some cases when cycling the power of the network adapter, without using a switch between the PC and network adapter, the BOOTP application will loose its reference to the ethernet port. The best and recommended way is to use a switch between the PC and the device.
BootP, method 1
-
Connect the PC with the GL-9089/GN-9289 over Ethernet.
-
Set a fixed IP address on the PC, same subnet as the GL-9089/GN-9289 is to be changed to. The IP address for the PC should not be assigned automatically (DHCP).Se section 4.2. part 1.
-
Always use the latest version of Beijer BOOTP server (included in IOGuidePro or extracted tool).
-
Run IOGuidePro, and select menu Tools > Bootp Server, or start the BOOTP tool from folder. Alternative run the BOOTP server separately (BootpSvr.exe).
-
When the BOOTP Server is launched and to allow G-series device in present version of IOGuidePro. Make sure that option ”Show Beijer device only” is unchecked!
Push the “Add New Device” button and enter the MAC address and desired IP address, subnet and gateway. Select the network interface that the GL-9089/GN-9289 is connected to.
Push “Ok” and “Start Bootp”.
-
Power OFF the GL-9089/GN-9289 and set DIP switch 9 to ON (BOOTP).
-
Power on the GL-9089/GN-9289 device, and the device will get the new IP address from the BootP server, it appears in the upper window.
-
“Stop Bootp” and reset DIP switch 9 to OFF, and reboot the GL-9089/GN-9289 device.
-
If the IP is set to a different subnet then change the IP address of your computer accordingly.
-
Try to ping the device with new IP address.
-
Close the BOOTP Server.
BootP, method 2
-
Connect the PC with the GL-9089/GN-9289 over Ethernet.
-
Set a fixed IP address on the PC, same subnet as the GL-9089/GN-9289 is to be changed to. The IP address for the PC should not be assigned automatically (DHCP). Se section 4.2. part 1.
-
Always use the latest version of the Beijer BOOTP server included in IO Guide Pro or extracted tool.
-
Run IO Guide Pro and select menu Tools > Bootp Server, or start the BOOTP tool from folder. / Alternative run the Bootp server separately (BootpSvr.exe).
-
When the BootP Server is launched and to allow M-series device in present version of IO Guide Pro, make sure that ”Show Beijer device only” is unchecked!
-
Press “Start Bootp”.
-
Power OFF the GL-9089/GN-9289 and set DIP switch 9 to ON (BOOTP).
-
Power on the GL-9089/GN-9289 device, and the device will be shown in the BootP server.
Double click on one of the marked rows above.
The MAC address is default entered, type required IP address, Subnet and Gateway. Select the correct “Interface”, PC:s Ethernet connection to the GL-9089/GN-9289 and push “Ok”.
-
Now press “Stop BootP”.
-
Reset the DIP switch 9 to OFF, and reboot the GL-9089/GN-9289 device.
-
If the IP is set to a different subnet then change the IP address of your computer accordingly.
-
Try to ping the device with new IP address.
-
Close the BOOTP Server.
Note!
MODBUS/TCP IP – Address Setup
If the adapter BOOTP/DHCP enabled (DIP Pole#9 ON), the adapter sends BOOTP/DHCP request message of 20 times every 2sec. If BOOTP/DHCP sever does not response, the Adapter applies its IP Address with EEPROM (Latest saved IP Address).
About Beijer Electronics
Beijer Electronics is a multinational, cross-industry innovator that connects
people and technologies to optimize processes for business-critical
applications. Our offer includes operator communication, solution engineering,
digitalization and communication, and support. As experts in user-friendly
software, hardware and services for the Industrial Internet of Things, we
empower you to meet your challenges through leading-edge solutions.
www.beijergroup.com
Contact us
Global offices and distributors
Customer Support
Beijer Electronics AB − a Beijer Electronics Group company
Head Office
Beijer Electronics AB
P.O. Box 426, Stora Varvsgatan 13a
SE-201 24 Malmö, SWEDEN
Telephone +46 40 35 86 00
Subsidiaries
Reg no. 556701-4328 VAT no SE556701432801/ www.beijerelectronics.com/ info@beijerelectronics.com
References
- Beijer Electronics
- Innovations in industrial digital technology | Ependion
- Innovations in industrial digital technology | Ependion
- Contact us - Beijer Electronics
- Help online - Beijer Electronics
- Help online - Beijer Electronics
- Help online - Beijer Electronics
- Contact us - Beijer Electronics
- Help online - tree view - Beijer Electronics