POTTER RA-6075 LCD Annunciator Installation Guide
- June 9, 2024
- POTTER
Table of Contents
POTTER RA-6075 LCD Annunciator
Description
The RA-6075 is a LCD remote annunciator for the PFC-6075 and PFC-6030 addressable fire control panel. The RA-6075 communicates using a RS-485 connection to the main panel providing common indication of Alarms, Supervisory, Trouble and other system status and control functions. The RA-6075 features a 32 character, 16×2 LCD display with LED’s for Power, Alarm, Supervisory, Trouble, and Silenced conditions. It can be mounted on a single gang electrical box or a four square electrical box. The annunciator is enclosed in a sheet metal enclosure and has a Potter lock securing the keypad.
Features
- Standby Current 20 mA
- Alarm Current 25 mA
- Operating Temperature 0°C-49°C (32°F-120°F) 10%-93% @ 30°C (86°F) non-condensing humidity
- Maximum Wire Length 6500 FT
- Maximum Annunciators 31
- Dimensions (WxHxD) 8” x 6-1/4” x 1-5/8” (Cabinet)
- Wire Gauge 14 AWG-22 AWG
- Display 2 lines x 16 characters
Installation
The RA-6075 is connected to the PFC-6075 using a four wire RS-485 connection. The connection is power limited and supervised. Up to thirty-one (31) RA-6075 LCD annunciators can be connected using Class B or Class A wiring. Class A wiring requires an optional Class A Expander.
NOTICE
Install in accordance with compatible fire alarm panel
DIMENSIONS
RA-6075 Class B Wiring Example
RA-6075 Class A Wiring Example
Address Settings
The RA-6075 address is set by dip switch S1 located on the back of the RA-6075. The address must be set in the range of 1 to 31 to be recognized by the control panel.
RA-6075 Class A (back panel view)
Dip Switch Settings
Refer to the table below for dip switch settings per Annunciator Address
Annunciator Address| Dip Switch Settings| | Annunciator
Address| Dip Switch Settings
---|---|---|---|---
SW- 1| SW- 2| SW- 3| SW- 4| SW-
5| SW- 1| SW- 2| SW- 3| SW- 4|
SW- 5
1| On| Off| Off| Off| Off| 17| On| Off| Off| Off| On
2| Off| On| Off| Off| Off| 18| Off| On| Off| Off| On
3| On| On| Off| Off| Off| 19| On| On| Off| Off| On
4| Off| Off| On| Off| Off| 20| Off| Off| On| Off| On
5| On| Off| On| Off| Off| 21| On| Off| On| Off| On
6| Off| On| On| Off| Off| 22| Off| On| On| Off| On
7| On| On| On| Off| Off| 23| On| On| On| Off| On
8| Off| Off| Off| On| Off| 24| Off| Off| Off| On| On
9| On| Off| Off| On| Off| 25| On| Off| Off| On| On
10| Off| On| Off| On| Off| 26| Off| On| Off| On| On
11| On| On| Off| On| Off| 27| On| On| Off| On| On
12| Off| Off| On| On| Off| 28| Off| Off| On| On| On
13| On| Off| On| On| Off| 29| On| Off| On| On| On
14| Off| On| On| On| Off| 30| Off| On| On| On| On
15| On| On| On| On| Off| 31| On| On| On| On| On
16| Off| Off| Off| Off| On|
- Potter Electric Signal Company, LLC
- St. Louis, MO
- Cust Service : 866-956-1211
- Tech Support : 866-240-1870
- Canada : 888-882-1833
- www.pottersignal.com
References
- Fire Alarm Resources | Download fire alarm documents
- Potter Electric: Fire Alarms & Fire Sprinkler Systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>