POTTER PVX Series Voice Evacuation Panels Accessory Cards
PVX Accessory Cards
- PVX-ZM – Supervised Zone Module
- PVX-SL8 – LED Switch Card
- PVX-IL8 – LED Input Card
- PVX-OL8 – LED Output Card
- All cards connect and communicate over 10 pin ribbon cable
- Up to 16 total cards per panel in any combination
PVX-ZM
Stock Number : 3510014
Supervised Zone Module
Current draw (24VDC input): 51mA (Standby), 130mA (All Call)
- 4 Class B or 2 Class A speaker circuits (Field selectable)
- 25/70 Vrms Field selectable
- Compatible with PVX-SL8 for zone selection
- Circuits rated up to 50W @ 70V and 40W @ 25V
- Circuits rated up to 50W @ 70V and 40W @ 25V
The Potter PVX-ZM Supervised Zone Module is used in conjunction with the PVX
Series Voice Evacuation Panels to provide separately supervised and protected
circuits from a single speaker output. The EVX-ZM is default configured for 4
Class B circuits, but may be converted to 2 Class A with the flip of a switch.
The PVX-ZM can be ganged together to provide a maximum of 64 Class B circuits.
The PVX-ZM in standard operating mode is strictly All Call. On any page,
alarm, or message function all circuits activate. If separate zoning is
required, the PVX-ZM has zone selection inputs which may be activated by a
N.O. dry contact. Additionally, the PVX-SL8(LED Switch Card) may be employed
to provide both Zone and Message selection by switch.
Each speaker circuit employs smart power metering to insure short circuit
conditions are isolated from the other circuits. Each circuit is rated 50W @
70V and 40W @ 25V
PVX-SL8
Stock Number : 3510015
LED Switch Module
Current draw (On primary module battery back-up): 3mA (Standby), 5.16mA (All
Call)
- 8 Momentary switches
- 8 Tri-color LED’s (green/red/amber)
- Programmable for multiple functions
The Potter PVX-SL8 LED Switch Module provides switch selection for message
activation, paging, and control functions.
When used in conjunction with the PVX-ZM zone module, the SL8 can be
programmed for page zone control. LEDs for switches assigned to page zones
will indicate Red for page and flashing Red for alarm.
The LED will indicate Amber if the associated speaker circuit is in a fault
condition.
Switches can be programmed to control corresponding points on the PVX-OL8.
Switch LEDs will indicate steady Red on activation
PVX-IL8
Stock Number : 3510016
LED Input Module
Current draw (On primary module battery back-up): 3mA (Standby): 5.2mA (All
Call)
- 8 Input points
- 8 Red LED’s
- Programmable for multiple functions
The Potter PVX-IL8 LED Input Module can be used for page zone control, message selection, and control functions. The inputs monitor an external N.O dry contact. PVX-IL8’s are typically used for message/zone activation from an outside system such as Severe Weather Warnings. They can also be used to activate corresponding outputs on the PVX-OL8. On activation, the corresponding LED will indicate red.
PVX-OL8
Stock Number: 3510017
LED Output Module
Current draw (On primary module battery back-up): 3mA (Standby), 28mA (All
Call)
- 8 Input points
- 8 Red LED’s
- N.O. Dry contacts rated at 30mA @ 0-24VDC
The PVX-OL8 LED Output Module provides solid state N.O. dry contacts. It can also be separately tied to a voltage (0-24VDC), with that voltage used as a drive point or trigger. Outputs 1-4 and 5-8 may use different voltage references if desired. The PVX-OL8 outputs may be programmed to follow message activation, page zones, or specific functions like PTT, alarm, or control.